Changing Terminator Settings
The terminator switch is shipped from the factory in the terminated or “IN” position. This is the correct setting if the AGM300 is connected as a single device, or it is the last device on the network chain. If the AGM300 is being installed in the middle of a network, the terminator must be moved to the “OUT” position.
Locate the switch and determine its position. If it needs to be moved, slide the switch to the appropriate position.
Network Node
Address
Switch
Terminator
Switch
INOUT
Node Address DIP Switch Settings
(Refer to Multiple AGM's and Connecting to a Building Management System)
Each AGM300 on the network must have a distinct node address. The node address may be set from 1 to 15. Four dip switches numbered 1, 2, 4, 8 on the main circuit board are used to define this value by setting the correct combination of dip switches to their ON positions. The node address is the sum of the switch numbers that are ON.
Example: - For node address “5” switches 1 and 4 are ON.
-For node address “13” switches 1, 4, & 8 are ON. Power must be cycled to elect this change.
Personal Computer
(Refer to AGM300 PC Software Section)
The AGM300 may be connected to a personal computer using the
Software will be provided upon request or as a download from:
Instruction | 11 |