Bacharach ADM800, AGM300 manual Location, Number of Zones Installed, Alarm Ack Mode, Zone Hold Time

Page 46

Location

This is the name you assign to the AGM300 to identify its location. It may have up to 12 alphanumeric characters.

1.Press the LOCATION key to modify the setting.

2.Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to modify the individual characters.

3.Press ENTER to accept the new entry or QUIT to revert to the previous setting.

Number of Zones Installed

IMPORTANT: Do not change the number of zones to deactivate excess zones. Instead, go to the individual zone that you wish to disable and set its distance to zero (refer to Navigating to the 1st Zone Setup Screen on Page 41). The monitor will perform a self-check on power-up, and if the number of zones detected does not agree with the number of zones installed a fault will occur.

1.Press the NUM ZONES INSTALLED key to adjust the setting.

2.Use the UP/DOWN cursor keys to modify the number.

3.Press ENTER to accept the new number or QUIT to revert to the previous setting.

NOTE: The AGM300 auto setting detects the number of zones present on power-up. DO NOT PLUG ANY ZONES. Plugging a zone will give the monitor a false indication during power up. The number detected on power up is the default value for this parameter.

Alarm Ack Mode

This function programs the relays in the AGM unit for latching or non-latching operation.

1.Press the ALARM ACK MODE key to adjust the setting.

2.Use the UP/DOWN cursor keys to toggle between settings.

AUTO – Non-latching (Alarm relay will automatically de-energize when the gas level drops below its alarm point.)

MANUAL – Latching (Alarm relay remains energized, and will not release until the alarm condition has

been manually acknowledged. Refer to Acknowledging Alarms on Page 52.) 3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.

Audible Alarm

This parameter selects the function of the AGM300’s internal audible alarm device.

1.Press the AUDIBLE ALARM key to adjust the setting.

2.Use the UP/DOWN cursor keys to select unused, monitor on, evacuate, spill, leak, fault, or alarm.

3.Press ENTER to accept the new entry or QUIT to revert to the previous setting.

Zone Hold Time

Sets the length of time a zone will be monitored when the zone hold feature is actuated (see Zone Hold Mode on Page 45). The default is 15 minutes. This parameter can be set to any value between 1 and 999 minutes.

1.Press the ZONE HOLD MINUTES key to adjust this setting.

2.Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to modify the individual numbers.

3.Press ENTER to accept the new entry or QUIT to revert to the previous setting.

Detection Limit

This is essentially a squelch setting that instructs the instrument to interpret PPM readings below the designated level as 0. You can set this value from 1 to 99 PPM.

1.Press the DETECTION LIMIT key to adjust this setting.

2.Use the UP/DOWN cursor keys to modify the setting.

3.Press ENTER to accept the new entry or QUIT to revert to the previous setting.

38

Instruction 3015-4275

Image 46
Contents AGM300 / ADM800 Ammonia Gas Monitoring System Rev MayInstruction Table of Contents Introduction How to Use This ManualPlease Read this Manual Carefully Before Use Safety Precautions Cleaning Hazard Symbols on MonitorInstallation Category Altitude LimitCommunication Options Functional OverviewGeneral Description Suggested Location of Sampling PointsChiller Machine RoomStandard Accessories for a 4 Point System LEDLocating the Monitor AGM300 Installation ConsiderationsInspection Screw Locations InstallationAGM300 Mounting Instructions AGM300 Mounting SpecsAGM300 Side View AGM300 Connecting Air LinesOverview Inlet / Purge PortsConnecting Sample Intake Lines Connecting Purge LineConnecting Exhaust Line Tubing ConsiderationsAGM300 Interior Schematic ON/OFF Do not Apply PowerSwitches / Fuses / OUTAGM300 Electrical Wiring VAC InstallationAGM300 AC Input Power and Ground Connections Ammonia Display Module ADM800 Connection AGM300 Connecting Communication DevicesRS-485 Connector Integrating with Building Management SystemsPersonal Computer Refer to AGM300 PC Software Section Changing Terminator SettingsOUT Multiple AGM’s Connecting to a Building Management SystemRS-485 Connections Between AGM300’s Multiple AGM300’s Connected to a Building Management System Programming the AGM300 Using PC SoftwareAGM300 PC Software Unit Node Terminator Outout Building Management SystemTo Send a Saved Program to an AGM300 Saving the AGM300 Program to a Disk or DriveTo Open a Saved Program Trend DataUSB Type Laptops Sealevel SYSTEMS, INCOptional 4-20 mAdc Outputs Current Loop ConnectorAGM300 Current Loop Interfaces ConnectionAGM300 Connecting External Alarms AGM300 Relay ConnectorLeak Spill Evacuate Fault Typical AGM300 Relay 1 and Relay 2 WiringADM800 Installation ADM800 Oblique PhotoADM800 Installation Considerations ADM800 Mounting Instructions ADM800 Mounting SpecsADM800 Interior Schematic Front Panel ChassisTo Monitors To HostADM800 Electrical Wiring ADM800 AC Input Power and Ground Connections AGM300 Network ADM800 Communication ConnectionsIntegration with Building Management System Changing Terminator Switch Settings To MonitorADM800 Connecting External Alarms ADM800 Relay ConnectorADM800 Exterior Schematic ADM800 OperationADM800 Overview ADM800 Screen Displays System ScreenPassword Protection Setup ParametersADM800 System Programming Setting the Clock ADM800 Setup ProgrammingClock Setup Screen Number of AGM Units Navigating to the 1st ADM Setup ScreenContrast AGM Baud RateEnabling Building Management System Connection Audible AlarmPassword Building Management System Stop BitsADM Setup Screen #2 Navigating to the 2nd ADM Setup ScreenSetting Relay Parameters AGM Node AddressScreen #1 AGM Setup Screen #1 AGM300 Setup ProgrammingNavigating to the 1st and then 2nd AGM Setup Screen AGM Setup Screen #2Location Number of Zones InstalledAlarm Ack Mode Zone Hold TimeAuto Re-Zero ModeLoop 2 Factor Zone ChangeService Timeout Navigating to the 3rd AGM Setup ScreenAGM Setup #3 Screen Zone Setup Screen #1 ADM800 Zone Setup ProgrammingNavigating to the 1st Zone Setup Screen DistanceCurrent PPM Average TemperatureNavigating To the 2nd Zone Setup Screen Log IntervalSpill Level Re-Setting the Peak PPM ValueEvacuation Level Working with the Zone Screen General OperationFunctional Overview Zone ScreenZone Screen Hold Mode Zone Screen Alarm ModeFault Conditions System Screen Alarm Mode Working with the System ScreenAGM Setup #1 Screen Alarm Log ScreenSystem Screen Fault Mode Responding To Alarms Working with AlarmsAlarm Summary Screen Alarm Detail Screen Alarm Detail ScreenAcknowledging Alarms Alarm Summary Screen Acknowledge ModeNavigating To the Trend Screen Working with the Trend ScreenOverview Log Interval Trend ScreenNavigating to the Fault Screen Working with System FaultsFault Screen Reset to Factory Default Settings Critical FaultsViewing Fault Log Clearing System FaultsFault Log Screen Navigating to the Calibration Screen Adjusting Calibration FactorWorking with the Calibration Screen Calibration ScreenCalibration Procedure Diagnostic Screen Overview Working with the Diagnostic ScreenNavigating to the Diagnostic Screen Diagnostic ScreenInstruction Service Mode System Screen Service ModeInstruction Appendix Servicing Air Lines AGM300 / ADM800 MaintenanceServicing Inline Filter Replacing FusesIntake Manifolds Optional AccessoriesMA Interface Board ADM800 Logic Diagram RS-485 Communication Protocol Modbus RTU ProtocolAGM300 Modbus RTU Operation Protocol DetailsModbus Mode RTU only Key Comm Protocol ParametersRegister Name Number Type Description Summary of RegistersData Type Abbreviations TIMUnused REVUnused TIM Minutes RS-485BAUDMSB Service mode register to change this parameterMode. do not Modify use zone hold register or LSBVariable Type Length Description Zone Data Register 0x12xxh R/W 78 bytesGood. do not Modify Instruction Instruction Stpppm To Release the Zone Hold Use the Following Sequence of Steps Fault Log Register Register 0x1900, 0x1901h Bytes Instruction Time record for each of the 100 log points. The format Point to current readingLast 100 log points 2 byes per point Warranty Warranty and ServiceService Products Covered under Warranty and Service Policy Return ProcedureField Repair AGM300 Specifications ADM800 Specifications Instruction Headquarters Hunt Valley Circle, New Kensington, PA

AGM300, ADM800 specifications

The Bacharach ADM 800 and AGM 300 are advanced analyzers designed for efficient monitoring and detection of gases in various applications. Known for their reliability and accuracy, these instruments cater to commercial and industrial sectors, ensuring safety and compliance with environmental regulations.

The Bacharach ADM 800 is a portable gas detection device renowned for its ability to detect multiple refrigerants. With a user-friendly interface, it features a high-resolution display that provides real-time data on refrigerant concentrations, allowing technicians to quickly identify leaks during maintenance operations. One of its standout technologies is a highly sensitive thermal conductivity sensor, which enables the ADM 800 to differentiate between various hydrocarbon refrigerants with precision.

Equipped with data logging capabilities, the ADM 800 can store and retrieve measurement data, making it an invaluable tool for tracking refrigerant trends over time. The device supports USB connectivity for easy transfer of data to computers, facilitating detailed reporting and analysis. Its robust design incorporates a protective casing that ensures durability in challenging work environments, making it ideal for both field use and stationary applications.

On the other hand, the Bacharach AGM 300 is specifically crafted for continuous gas monitoring in HVAC systems. This stationary device excels in measuring concentrations of gases such as CO, CO2, and various refrigerants, ensuring optimal performance and compliance. The AGM 300 uses advanced electrochemical sensors for precise gas measurements, providing real-time feedback and alerting users to any hazardous conditions.

One of the notable features of the AGM 300 is its ability to integrate seamlessly with building management systems, enabling centralized control and monitoring of gas levels across multiple locations. This connectivity enhances the safety of industrial and commercial spaces by allowing for automated responses to detected gas levels, which can significantly mitigate risks associated with gas leaks.

Both models emphasize user-centric design, with intuitive interfaces and clear displays, making them accessible even to those with minimal training. Additionally, their low maintenance requirements and long sensor life contribute to reduced operational costs.

In conclusion, the Bacharach ADM 800 and AGM 300 are exemplary solutions for gas detection and monitoring. Their advanced technologies, robust features, and user-friendly designs make them indispensable for ensuring safety and regulatory compliance in various environments.