D. Gas Pressures

Proper input pressures are required for optimum appli- ance performance. Gas line sizing requirements need to be made following NFPA54.

WARNING

Fire Risk. Explosion Hazard.

High pressure will damage valve.

• Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1/2 psig.

Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1/2 psig.

WARNING

Verify inlet pressures.

• High pressure may cause overfire condition.

• Low pressure may cause explosion.

Verify minimum pressures when other household gas appliances are operating.

Install regulator upstream of valve if line pressure is greater than 1/2 psig.

Pressure requirements for appliance are shown in the table below. Minimum pressures must be met when other household gas appliances are operating.

Pressure

Natural Gas

Propane

Minimum inlet pressure

4.5 inches

11.0 inches

w.c.

w.c.

 

Maximum inlet gas pressure

7.0 inches

14.0 inches

w.c.

w.c.

 

 

 

 

Manifold pressure

3.5 inches

10.0 inches

w.c.

w.c.

 

 

 

 

If the pressure is not sufficient, ensure:

The piping used is large enough.

The supply regulator is adequately adjusted.

That the total gas load for the residence does not exceed the amount supplied.

The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank) should supply gas at the suggested input pressure listed above. Contact the local gas supplier if the regulator is at an improper pressure.

E. Gas Connection

Note: Have the gas supply line installed in accordance with local building codes, if any. If not, follow ANSI

223.1.Installation should be done by a qualified installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter).

Note: A listed (and Commonwealth of Massachusetts ap- proved) 1/2 inch (13 mm) T-handle manual shut-off valve and flexible gas connector are connected to the 1/2 inch (13 mm) control valve inlet.

If substituting for these components, please consult local codes for compliance.

WARNING

Gas Leak Risk

Support control when attaching pipe to prevent bending gas line.

Note: The gap between supply piping and gas access hole may be caulked with high temperature caulk or stuffed with non-combustible, unfaced insulation to prevent cold air infiltration.

Leak test all gas line joints and the gas control valve prior to and after starting the appliance.

Before making the gas connection, ensure that the appliance you are installing is designed for the type of gas being supplied. This information can be found on the ratings label under the appliance. If the appliance has been converted to propane (LP), the valve cover should have a label stating that the appliance has been converted to propane.

Connect the gas line at the 3/8 in. (10 mm) pipe connector on the valve at the back of appliance. We recommend connecting the appliance with an approved flex gas line. If flex gas lines are not approved in your area, you must connect a hard pipe to the gas hookup.

You must supply a manual shut-off valve in a visible location within 3 ft. (914 mm) of the appliance.

Ensure that gas line does not come in contact with outer wrap of appliance. Follow local codes.

Incoming gas line should be piped into the valve compartment and connected to the 1/2 inch connection on the manual shutoff valve.

12

Quadra-Fire • Columbia Bay Insert • 7002-109 Rev. H • 10/08

Image 12
Contents What to do if you smell gas COLBAY-INSDo Discardnot Welcome to the Quadra-Fire Family Table of Contents Listing and Code Approvals Installation to ensure maximum safety and benefit Getting StartedTools and Supplies Needed Framing and Clearances Selecting Appliance LocationClearances to Combustibles HearthTermination Locations Vent Termination Minimum ClearancesVenting and Installation Vent Information Exhaust AIR Vent Pipe Termination CAP Adaptor Gas Information Fuel ConversionsConverting to LP Gas Valve Regulator Replacement Gas Pressures Gas ConnectionHigh Altitude Installations Recommendation for Wire Connecting to the ApplianceStanding Pilot Ignition System Wiring Wire Size Max. LengthPilot Appliance Setup AccessoriesDoor Crown Installation Remove Shipping MaterialsGrille Installation Panel Set InstallationBack of TOP Panel Screws Back of Side Panel Brick Installation Baffle SupportsBaffle Rear Brick Panel Brick ClipsPositioning the Logs Blower Installation Mineral WoolIncluded in kit Blower = 1/4 in mm female spade = 1/4 in mm male spade Air Shutter Adjustment Operating Instructions Before Lighting ApplianceFor Your Safety Read Before Lighting Lighting ApplianceFrequently Asked Questions Initial Break-in ProcedureAfter Appliance is Lit Troubleshooting Symptom Possible Causes Corrective ActionStanding Pilot Ignition System Troubleshooting Symptom Possible Cause Corrective ActionGlass Replacement Door Frame with Glass Assembly ReplacementMaintaining and Servicing Appliance To Replace Separate Glass PiecesMaintenance Tasks Inspect Necessary. USE Caution When CLEANING/HANDLING Ceramic BurnerAppliance Dimension Diagram Reference MaterialsVent Components List HHTLog Set Assembly Service PartsService Parts List Stocked At DepotBottom Firebox Assembly Description Serial # Part NumberCONDITIONS, Exclusions & Limitation of Liability Limited Lifetime Warranty Contact Information