Hearth and Home Technologies 830-0381 Chimney Requirements, Chimney Height, Chimney TOP View

Page 8

R

3100-I ACT WOOD INSERT

CHIMNEY REQUIREMENTS

A chimney must be the required height above the roof or other obstruction for safety and for proper draft oper- ation. The requirement is that the chimney must be at least 3 feet (91cm) higher than the highest point where it passes through the roof, and at least 2 feet (61cm) higher than the highest part of the roof or structure that is within10 feet (305cm) of the chimney, measured hori- zontally. Refer to Figure 8C.

OVALIZING ROUND STAINLESS STEEL

LINERS

Ovalizing round stainless steel liners to acommodate the liner passing through the damper region of a fire- place is an allowable and acceptable practice.

Ensure that the ovalization is minimized to the extent required to fit through the damper.

Figure 8A

Firestopping

Figure 8C

Non-Combustible

Firestopping

Material

 inch (51mm)

Floor

(second Story)

Floor

Ceiling

Caulk

Minimum 1 inch (25mm) clearance from exterior chimney to sheathing

CHIMNEY HEIGHT

At least 3 ft

(91cm)

10 ft

(305cm)

At least  ft

(61cm)

Figure 8B

Figure 8D

Minimum 2 inch (51mm) clearance from combustible material

and insulation

ceiling

Non-combustible fire stopping material

CHIMNEY TOP VIEW

1/2" (12.7mm) airspace

FLUE

5/8" (16mm) Fireclay Flue Liner

Chimney Wall

4" (102mm)

Nominal

Foundation

Page

250-6381D

September 1, 2008

Image 8
Contents ACT Wood Insert Hot glass will cause burnsSample of Serial Number / Safety Label ACT Wood InsertTable of Contents Front View Insert Dimensions TOP ViewSide View ACT Wood Insert Clearances to Combustibles Installation recommendations InstallationListings Chimney HEIGHT/DRAFTGeneral Installation Procedure Alternate Floor Protection WorksheetChimney Requirements Ovalizing Round Stainless Steel LinersChimney Height Chimney TOP ViewInstallation Options Masonry Fireplace Using DIRECT-CONNECT MethodUsa installations only Factory built zero clearance fireplaceInstallation in Canada Use of Leveling BoltsSecuring Liner to Chimney Ring Masonry and HEAT-CIRCULATINGInstallation of Panel SET and Trim Door Handle AssemblyView of L Bracket Installed Description SizeFAN Blower Installation Instructions FAN Speed Control ADJUSTMENT, if NecessaryZero Clearance Adjustable Trim SUPPORT, 2 to See BWood Selection and Storage OverfiringBuilding a Fire ACT Wood Insert Operating Tips Fan operating instructionsASH Removal BTU / Hr Start-Up Air Control Primary ControlAir quality and your Quadra-Fire Insert Story of the Three Burning StagesMaintenance See C Brick replacement instructionsBrick Set Part Number Exploded View DescriptionService parts LVR-31-NLAccessories Glass Size 15-1/2 w x 11-3/8 hService And Maintenance Log Date of Service Performed By Description of ServiceService And Maintenance Log Cont’d Homeowner’s Notes Warranty Policy Hearth & Home Technologies Limited WarrantyHearth & Home Technologies Limited Warranty Cont’d ACT Wood Insert