Models: PUZ-A36NHA2-BS PUY-A12NHA2 PUY-A42NHA2-BS PUY-A30NHA2 PUZ-A36NHA2 PUY-A36NHA2-BS PUZ-A18NHA2 PUZ-A18NHA2-BS PUY-A30NHA2-BS PUZ-A30NHA2-BS PUY-A18NHA2 PUY-A36NHA2 PUZ-A30NHA2 PUY-A12NHA2-BS PUZ-A24NHA2-BS PUZ-A42NHA2 PUY-A18NHA2-BS PUY-A42NHA2 PUZ-A42NHA2-BS PUY-A24NHA2-BS PUZ-A24NHA2 PUY-A24NHA2

1 120
Download 120 pages 22.49 Kb
Page 97
Image 97

13-2. REQUEST CODE LIST

* Certain indoor/outdoor combinations do not have the request code function; therefore, no request codes are displayed.

code

 

 

Description

 

 

 

 

 

Request

Request content

 

Unit

 

 

 

Remarks

 

(Display range)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

Operation state

Referto13-2-1. DetailContentsinRequestCode.

 

 

 

 

1

Compressor-Operating current (rms)

0

– 50

A

 

 

 

 

2

Compressor-Accumulated operating time

0

– 9999

10 hours

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Compressor-Number of operation times

0

– 9999

100 times

 

 

 

 

4

Discharge temperature (TH4)

37 ~ 327

˚F

 

 

 

 

5

Outdoor unit - Liquid pipe 1 temperature (TH3)

-40 ~ 194

˚F

 

 

 

 

 

 

 

 

 

 

 

 

6

Outdoor unit - Liquid pipe 2 temperature

-40 ~ 194

˚F

 

 

 

 

7

Outdoor unit-2-phase pipe temperature (TH6)

-38 ~ 190

˚F

 

 

 

 

8

 

 

 

 

 

 

 

 

9

Outdoor unit-Outside air temperature (TH7)

-38 ~ 190

˚F

 

 

 

 

10

Outdoor unit-Heatsink temperature (TH8)

-40 ~ 327

˚F

 

 

 

 

11

 

 

 

 

 

 

 

 

12

Discharge super heat (SHd)

0

– 327

˚F

 

 

 

 

13

Sub-cool (SC)

0

– 234

˚F

 

 

 

 

14

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

16

Compressor-Operating frequency

0

– 255

Hz

 

 

 

 

17

Compressor-Target operating frequency

0

– 255

Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

18

Outdoor unit-Fan output step

0

– 10

Step

 

 

 

 

19

Outdoor unit-Fan 1 speed

0

– 9999

rpm

 

 

 

 

(Only for air conditioners with DC fan motor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

Outdoor unit-Fan 2 speed

0

– 9999

rpm

"0" is displayed if the air conditioner is a single-fan

(Only for air conditioners with DC fan motor)

type.

 

 

 

 

 

 

 

 

 

 

 

 

 

21

 

 

 

 

 

 

 

 

22

LEV (A) opening

0

– 500

Pulses

 

 

 

 

23

LEV (B) opening

0

– 500

Pulses

 

 

 

 

24

 

 

 

 

 

 

 

 

25

Primary current

0

– 50

A

 

 

 

 

26

DC bus voltage

180 – 370

V

 

 

 

 

27

 

 

 

 

 

 

 

 

28

 

 

 

 

 

 

 

 

29

Number of connected indoor units

0

– 4

Units

 

 

 

 

30

Indoor unit-Setting temperature

62 ~ 86

˚F

 

 

 

 

 

 

 

 

 

 

 

 

31

Indoor unit-Intake air temperature <Measured by thermostat>

46 ~ 102

˚F

 

 

 

 

32

Indoor unit-Intake air temperature (Unit No. 1)

46 ~ 102

˚F

 

"0" is displayed if the target unit is not present.

<Heat mode-4-deg correction>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33

Indoor unit-Intake air temperature (Unit No. 2)

46 ~ 102

˚F

 

 

 

 

<Heat mode-4-deg correction>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

34

Indoor unit-Intake air temperature (Unit No. 3)

46 ~ 102

˚F

 

 

 

 

<Heat mode-4-deg correction>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

35

Indoor unit-Intake air temperature (Unit No. 4)

46 ~ 102

˚F

 

 

 

 

<Heat mode-4-deg correction>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36

 

 

 

 

 

 

 

 

37

Indoor unit - Liquid pipe temperature (Unit No. 1)

-38 ~ 190

˚F

 

"0" is displayed if the target unit is not present.

 

 

 

 

 

 

 

 

38

Indoor unit - Liquid pipe temperature (Unit No. 2)

-38 ~ 190

˚F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

39

Indoor unit - Liquid pipe temperature (Unit No. 3)

-38 ~ 190

˚F

 

 

 

 

 

 

 

 

 

 

 

 

40

Indoor unit - Liquid pipe temperature (Unit No. 4)

-38 ~ 190

˚F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41

 

 

 

 

 

 

 

 

42

Indoor unit-Cond./Eva. pipe temperature (Unit No. 1)

-38 ~ 190

˚F

"0" is displayed if the target unit is not present.

43

Indoor unit-Cond./Eva. pipe temperature (Unit No. 2)

-38 ~ 190

˚F

 

 

 

 

 

 

 

 

 

 

 

 

44

Indoor unit-Cond./Eva. pipe temperature (Unit No. 3)

-38 ~ 190

˚F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45

Indoor unit-Cond./Eva. pipe temperature (Unit No. 4)

-38 ~ 190

˚F

 

 

 

 

 

 

 

 

 

 

 

 

46

 

 

 

 

 

 

 

 

47

 

 

 

 

 

 

 

 

48

Thermostat ON operating time

0

– 999

Minutes

 

 

 

 

49

Test run elapsed time

0

– 120

Minutes

 

 

 

Not possible to activate maintenance mode during the test run.

 

 

 