13-2. REQUEST CODE LIST

* Certain indoor/outdoor combinations do not have the request code function; therefore, no request codes are displayed.

code

 

 

Description

 

 

 

 

 

Request

Request content

 

Unit

 

 

 

Remarks

 

(Display range)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

Operation state

Referto13-2-1. DetailContentsinRequestCode.

 

 

 

 

1

Compressor-Operating current (rms)

0

– 50

A

 

 

 

 

2

Compressor-Accumulated operating time

0

– 9999

10 hours

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Compressor-Number of operation times

0

– 9999

100 times

 

 

 

 

4

Discharge temperature (TH4)

37 ~ 327

˚F

 

 

 

 

5

Outdoor unit - Liquid pipe 1 temperature (TH3)

-40 ~ 194

˚F

 

 

 

 

 

 

 

 

 

 

 

 

6

Outdoor unit - Liquid pipe 2 temperature

-40 ~ 194

˚F

 

 

 

 

7

Outdoor unit-2-phase pipe temperature (TH6)

-38 ~ 190

˚F

 

 

 

 

8

 

 

 

 

 

 

 

 

9

Outdoor unit-Outside air temperature (TH7)

-38 ~ 190

˚F

 

 

 

 

10

Outdoor unit-Heatsink temperature (TH8)

-40 ~ 327

˚F

 

 

 

 

11

 

 

 

 

 

 

 

 

12

Discharge super heat (SHd)

0

– 327

˚F

 

 

 

 

13

Sub-cool (SC)

0

– 234

˚F

 

 

 

 

14

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

16

Compressor-Operating frequency

0

– 255

Hz

 

 

 

 

17

Compressor-Target operating frequency

0

– 255

Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

18

Outdoor unit-Fan output step

0

– 10

Step

 

 

 

 

19

Outdoor unit-Fan 1 speed

0

– 9999

rpm

 

 

 

 

(Only for air conditioners with DC fan motor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

Outdoor unit-Fan 2 speed

0

– 9999

rpm

"0" is displayed if the air conditioner is a single-fan

(Only for air conditioners with DC fan motor)

type.

 

 

 

 

 

 

 

 

 

 

 

 

 

21

 

 

 

 

 

 

 

 

22

LEV (A) opening

0

– 500

Pulses

 

 

 

 

23

LEV (B) opening

0

– 500

Pulses

 

 

 

 

24

 

 

 

 

 

 

 

 

25

Primary current

0

– 50

A

 

 

 

 

26

DC bus voltage

180 – 370

V

 

 

 

 

27

 

 

 

 

 

 

 

 

28

 

 

 

 

 

 

 

 

29

Number of connected indoor units

0

– 4

Units

 

 

 

 

30

Indoor unit-Setting temperature

62 ~ 86

˚F

 

 

 

 

 

 

 

 

 

 

 

 

31

Indoor unit-Intake air temperature <Measured by thermostat>

46 ~ 102

˚F

 

 

 

 

32

Indoor unit-Intake air temperature (Unit No. 1)

46 ~ 102

˚F

 

"0" is displayed if the target unit is not present.

<Heat mode-4-deg correction>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33

Indoor unit-Intake air temperature (Unit No. 2)

46 ~ 102

˚F

 

 

 

 

<Heat mode-4-deg correction>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

34

Indoor unit-Intake air temperature (Unit No. 3)

46 ~ 102

˚F

 

 

 

 

<Heat mode-4-deg correction>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

35

Indoor unit-Intake air temperature (Unit No. 4)

46 ~ 102

˚F

 

 

 

 

<Heat mode-4-deg correction>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36

 

 

 

 

 

 

 

 

37

Indoor unit - Liquid pipe temperature (Unit No. 1)

-38 ~ 190

˚F

 

"0" is displayed if the target unit is not present.

 

 

 

 

 

 

 

 

38

Indoor unit - Liquid pipe temperature (Unit No. 2)

-38 ~ 190

˚F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

39

Indoor unit - Liquid pipe temperature (Unit No. 3)

-38 ~ 190

˚F

 

 

 

 

 

 

 

 

 

 

 

 

40

Indoor unit - Liquid pipe temperature (Unit No. 4)

-38 ~ 190

˚F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41

 

 

 

 

 

 

 

 

42

Indoor unit-Cond./Eva. pipe temperature (Unit No. 1)

-38 ~ 190

˚F

"0" is displayed if the target unit is not present.

43

Indoor unit-Cond./Eva. pipe temperature (Unit No. 2)

-38 ~ 190

˚F

 

 

 

 

 

 

 

 

 

 

 

 

44

Indoor unit-Cond./Eva. pipe temperature (Unit No. 3)

-38 ~ 190

˚F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45

Indoor unit-Cond./Eva. pipe temperature (Unit No. 4)

-38 ~ 190

˚F

 

 

 

 

 

 

 

 

 

 

 

 

46

 

 

 

 

 

 

 

 

47

 

 

 

 

 

 

 

 

48

Thermostat ON operating time

0

– 999

Minutes

 

 

 

 

49

Test run elapsed time

0

– 120

Minutes

 

 

 

Not possible to activate maintenance mode during the test run.

 

 

 

97

Page 97
Image 97
Mitsubishi Electronics PUZ-A42NHA2-BS, PUZ-A30NHA2, PUY-A36NHA2, PUZ-A18NHA2-BS, PUY-A30NHA2-BS Request Code List

PUZ-A36NHA2-BS, PUY-A12NHA2, PUY-A42NHA2-BS, PUY-A30NHA2, PUZ-A36NHA2 specifications

Mitsubishi Electronics has long been a leader in the HVAC industry, and their range of air conditioning units, including the PUY-A24NHA2, PUZ-A24NHA2, PUY-A24NHA2-BS, PUZ-A42NHA2-BS, and PUY-A42NHA2, exemplifies their commitment to innovation and energy efficiency. These models are designed to provide optimal climate control for both residential and commercial applications, ensuring comfort throughout the year.

One of the defining features of these models is their advanced inverter technology, which allows for precise temperature control and reduced energy consumption. The inverter technology adjusts the compressor speed according to the cooling load, significantly lowering operating costs compared to traditional fixed-speed systems. This means that users can enjoy consistent comfort without worrying about surging energy bills.

The PUY and PUZ units come equipped with powerful indoor and outdoor components that enable efficient heat exchange. These systems provide excellent performance even in extreme weather conditions, with reliable operation at low ambient temperatures. This capability ensures that you can maintain a comfortable environment, no matter the season.

Additionally, the models are designed with quiet operation in mind. The outdoor units incorporate noise-reduction technology, ensuring that the systems operate at minimal sound levels. This is especially beneficial for residential areas or office environments, where maintaining a peaceful atmosphere is crucial.

Mitsubishi Electronics has also integrated smart technology into these units. With options for remote control via Wi-Fi, users can manage their air conditioning settings from anywhere, using their smartphones or tablets. This integration enhances user convenience and allows for more efficient scheduling and energy management.

These models are also known for their environmentally friendly refrigerants, such as R410A, which contribute to lower global warming potential and align with modern sustainability practices. By choosing Mitsubishi's PUY and PUZ series, consumers not only prioritize their comfort but also contribute to environmental conservation.

In summary, the Mitsubishi Electronics PUY-A24NHA2, PUZ-A24NHA2, PUY-A24NHA2-BS, PUZ-A42NHA2-BS, and PUY-A42NHA2 air conditioning units are equipped with cutting-edge technology, offering energy efficiency, quiet operation, and smart functionality. Whether for residential or commercial use, these units are designed to meet the demands of modern climate control while prioritizing energy savings and sustainability.