Models: PUZ-A36NHA2-BS PUY-A12NHA2 PUY-A42NHA2-BS PUY-A30NHA2 PUZ-A36NHA2 PUY-A36NHA2-BS PUZ-A18NHA2 PUZ-A18NHA2-BS PUY-A30NHA2-BS PUZ-A30NHA2-BS PUY-A18NHA2 PUY-A36NHA2 PUZ-A30NHA2 PUY-A12NHA2-BS PUZ-A24NHA2-BS PUZ-A42NHA2 PUY-A18NHA2-BS PUY-A42NHA2 PUZ-A42NHA2-BS PUY-A24NHA2-BS PUZ-A24NHA2 PUY-A24NHA2

1 120
Download 120 pages 22.49 Kb
Page 101
Image 101

13-2-1. Detail Contents in Request Code

A

D

[Operation state] (Request code ":0")

C

B

Relay output state

Example) Request code "004" Discharge temperature 156˚F Refrigerant address "00"

A:Mode display

B:Refrigerant address

C:Data display area

D:Request code display area

Data display

C 4

Relay output state

Operation mode

Operation mode

Display Operation mode

0STOP • FAN

C COOL • DRY

H

HEAT

d

DEFROST

Display

Power currently

Compressor

Four-way valve

Solenoid valve

supplied to compressor

 

 

 

 

0

1

 

 

 

ON

2

 

 

ON

 

3

 

 

ON

ON

4

 

ON

 

 

5

 

ON

 

ON

6

 

ON

ON

 

7

 

ON

ON

ON

8

ON

 

 

 

A

ON

 

ON

 

[Indoor unit – Control state] (Request code :" 50 ")

Data display

Unit No. 4 state

Unit No. 3 state

Unit No. 2 state

Unit No. 1 state

Display

State

0Normal

1Preparing for heat operation.

2

3

4Heater is ON.

5Anti-freeze protection is ON.

6Overheat protection is ON.

7Requesting compressor to turn OFF.

F There are no corresponding units.

[Outdoor unit – Control state] (Request code ":51")

 

Data display

 

State

0

 

0

0

 

0

Normal

0

 

0

0

 

1

Preparing for heat operation.

0

 

0

0

 

2

Defrost

[Compressor – Frequency control state] (Request code ":52")

Data display

0 0

Frequency control state 2

Frequency control state 1

Frequency control state 1

Display

Current limit control

0No current limit

1Primary current limit control is ON.

2Secondary current limit control is ON.

Frequency control state 2

Display

Discharge temperature

Condensation temperature

Anti-freeze

Heatsink temperature

overheat prevention

overheat prevention

protection control

overheat prevention

 

0

 

 

 

 

1

Controlled

 

 

 

2

 

Controlled

 

 

3

Controlled

Controlled

 

 

4

 

 

Controlled

 

5

Controlled

 

Controlled

 

6

 

Controlled

Controlled

 

7

Controlled

Controlled

Controlled

 

8

 

 

 

Controlled

9

Controlled

 

 

Controlled

A

 

Controlled

 

Controlled

b

Controlled

Controlled

 

Controlled

C

 

 

Controlled

Controlled

d

Controlled

 

Controlled

Controlled

E

 

Controlled

Controlled

Controlled

F

Controlled

Controlled

Controlled

Controlled

101