Error Code

Abnormal point and detection method

Case

Judgment and action

 

Outdoor fan motor

1 Failure in the operation of

1 Check or replace the DC fan motor.

 

The outdoor fan motor is considered to be

the DC fan motor

 

 

abnormal if the rotational frequency of fan

2 Failure in the outdoor circuit

2 Check the voltage of the outdoor circuit

 

motor is abnormal when detected during

controller board

controller board during operation.

 

operation.

 

3 Replace the outdoor circuit controller

 

Fan motor rotational frequency is abnormal

 

board. (when the failure is still indicated

U8

if;

 

even after performing the remedy 1

• 100 rpm or below detected continuously

 

above.)

(4400)

 

for 15 seconds at 20:[68˚F] or more

 

 

 

 

 

 

outside air temperature

 

 

 

• 50 rpm or below or 1500 rpm or more

 

 

 

detected continuously for 1 minute.

 

 

 

 

 

 

Overvoltage or voltage shortage and

1 Decrease of power supply volt- 1 Check the facility of power supply.

 

synchronous signal to main circuit

age

2 Correct the wiring (U·V·W phase) to com-

 

Abnormal if any of followings are detected

2 Disconnection of compressor

pressor. Refer to 10-9 (Outdoor power circuit

 

wiring

board).

 

during compressor operation;

3 Disconnection or loose con-

3 Check CN52C wiring.

 

• Decrease of DC bus voltage to 310V

nection of CN52C

 

 

Instantaneous decrease of DC bus volt-

4 Defective PFC module of out- 4 Replace outdoor power circuit board.

 

age to 200V

door power board (A12, 18,

(A12, 18, 24N only)

 

Increase of DC bus voltage to

24N only)

 

 

A12, 18, 24N : 420V

5 Defective ACT module (A30,

5 Replace ACT module. (A30, 36, 42N only)

 

A30, 36, 42N : 400V

36, 42N only)

 

 

• Decrease of input current of outdoor unit

6 Defective ACT module drive

6 Replace outdoor power circuit board.

 

to 0.5A only if operation frequency is

circuit of outdoor power circuit

(A30, 36, 42N only)

 

more than or equal to 40Hz or compres-

board (A30, 36, 42N only)

 

 

sor

7 Disconnection or loose con-

7 Check CNAF wiring. (A30, 36, 42N only)

U9

current is more than or equal to 5A.

nection of CNAF (A30, 36, 42N

 

• Abnormal power synchronous (zero

only)

 

(4220)

 

cross) signal

8 Defective 52C drive circuit of

8 Replace outdoor noise filter circuit board.

 

 

• PFC error (overcurrent) when the current

outdoor noise filter circuit

 

 

peak of input current increase A12, 18,

board

 

 

24N: 47A (peak)

9 Disconnection or loose

9 Check CN5 wiring on the outdoor power

 

 

connection of CN5 on the

circuit board.

 

 

outdoor power circuit board

Refer to 10-9.

 

 

0 Disconnection or loose

0 Check CN2 wiring on the outdoor power

 

 

connection of CN2 on the

circuit board.

 

 

outdoor power circuit board

Refer to 10-9.

 

Compressor overcurrent interruption

1 Stop valve is closed.

1 Open stop valve.

 

(When compressor locked)

2 Decrease of power supply

2 Check facility of power supply.

 

Abnormal if overcurrent of DC bus or

voltage

 

 

compressor is detected within 30 seconds

3 Looseness, disconnection or

3 Correct the wiring (U·V·W phase) to

UF

after compressor starts operating.

converse of compressor wiring

compressor.

(4100)

 

connection

Refer to 10-9 (Outdoor power circuit board).

 

4 Defective compressor

4 Check compressor.

 

 

 

 

 

Refer to 10-6.

 

 

5 Defective outdoor power board 5 Replace outdoor power circuit board.

 

 

 

 

 

Current sensor error

1 Disconnection of compressor

1 Correct the wiring (U·V·W phase) to

 

Abnormal if current sensor detects –1.5A

wiring

compressor. Refer to 10-9 (Outdoor power

 

to 1.5A during compressor operation.

 

circuit board).

 

(This error is ignored in case of test run

2 Defective circuit of current

2 Replace outdoor power circuit board.

 

mode.)

sensor on outdoor power

 

UH

w This error is ignored in case of test run

circuit board

 

(5300)

mode.

3 Decrease of power supply

3 Check the facility of power supply.

 

It’s abnormal for 38A the input current or

voltage

 

 

10 seconds continuous 34A or more.

 

 

39

Page 39
Image 39
Mitsubishi Electronics PUZ-A42NHA2 Case Judgment and action Outdoor fan motor, Overvoltage or voltage shortage

PUZ-A36NHA2-BS, PUY-A12NHA2, PUY-A42NHA2-BS, PUY-A30NHA2, PUZ-A36NHA2 specifications

Mitsubishi Electronics has long been a leader in the HVAC industry, and their range of air conditioning units, including the PUY-A24NHA2, PUZ-A24NHA2, PUY-A24NHA2-BS, PUZ-A42NHA2-BS, and PUY-A42NHA2, exemplifies their commitment to innovation and energy efficiency. These models are designed to provide optimal climate control for both residential and commercial applications, ensuring comfort throughout the year.

One of the defining features of these models is their advanced inverter technology, which allows for precise temperature control and reduced energy consumption. The inverter technology adjusts the compressor speed according to the cooling load, significantly lowering operating costs compared to traditional fixed-speed systems. This means that users can enjoy consistent comfort without worrying about surging energy bills.

The PUY and PUZ units come equipped with powerful indoor and outdoor components that enable efficient heat exchange. These systems provide excellent performance even in extreme weather conditions, with reliable operation at low ambient temperatures. This capability ensures that you can maintain a comfortable environment, no matter the season.

Additionally, the models are designed with quiet operation in mind. The outdoor units incorporate noise-reduction technology, ensuring that the systems operate at minimal sound levels. This is especially beneficial for residential areas or office environments, where maintaining a peaceful atmosphere is crucial.

Mitsubishi Electronics has also integrated smart technology into these units. With options for remote control via Wi-Fi, users can manage their air conditioning settings from anywhere, using their smartphones or tablets. This integration enhances user convenience and allows for more efficient scheduling and energy management.

These models are also known for their environmentally friendly refrigerants, such as R410A, which contribute to lower global warming potential and align with modern sustainability practices. By choosing Mitsubishi's PUY and PUZ series, consumers not only prioritize their comfort but also contribute to environmental conservation.

In summary, the Mitsubishi Electronics PUY-A24NHA2, PUZ-A24NHA2, PUY-A24NHA2-BS, PUZ-A42NHA2-BS, and PUY-A42NHA2 air conditioning units are equipped with cutting-edge technology, offering energy efficiency, quiet operation, and smart functionality. Whether for residential or commercial use, these units are designed to meet the demands of modern climate control while prioritizing energy savings and sustainability.