Mitsubishi Electronics PUZ-A42NHA2-BS, PUZ-A30NHA2 From the previous, Fresh Master, Lossnay, Nay

Models: PUZ-A36NHA2-BS PUY-A12NHA2 PUY-A42NHA2-BS PUY-A30NHA2 PUZ-A36NHA2 PUY-A36NHA2-BS PUZ-A18NHA2 PUZ-A18NHA2-BS PUY-A30NHA2-BS PUZ-A30NHA2-BS PUY-A18NHA2 PUY-A36NHA2 PUZ-A30NHA2 PUY-A12NHA2-BS PUZ-A24NHA2-BS PUZ-A42NHA2 PUY-A18NHA2-BS PUY-A42NHA2 PUZ-A42NHA2-BS PUY-A24NHA2-BS PUZ-A24NHA2 PUY-A24NHA2

1 120
Download 120 pages 22.49 Kb
Page 44
Image 44

From the previous page.

Error Code

Abnormal point and detection method

Case

Judgment and action

 

 

 

 

 

 

 

4. If displayed address or attribute is

1 During group operation with

Same as mentioned in “A7” of the previous

 

 

remote controller,

indoor unit of multi- refrigerant

page.

 

 

Indoor unit detects abnormality when

system, if indoor unit transmit

 

 

 

indoor unit transmitted to remote con-

to remote controller while out-

 

 

 

troller and there was no reply (ACK).

door unit power supply of one

 

 

 

 

refrigerant system is turned off

 

 

 

 

or within 2 minutes of restart,

 

 

 

 

abnormality is detected.

 

 

 

 

2 Contact failure of transmission

 

 

 

 

wire of remote controller or

 

 

 

 

indoor unit

 

 

 

 

3 Disconnection of transmission

 

 

 

 

connector (CN2M) of indoor

 

 

 

 

unit

 

 

 

 

4 Defective transmitting receiv-

 

 

 

 

ing circuit of indoor unit or

 

 

 

 

remote controller

 

 

 

 

 

 

 

 

5. If displayed address or attribute is

1 During sequential operation of

 

 

 

FRESH MASTER,

indoor unit and FRESH MAS-

 

 

 

Indoor unit detects abnormality when

TER of other refrigerant sys-

 

 

 

indoor unit transmitted to FRESH MAS-

tem, if indoor unit transmits to

 

 

 

TER and there was no reply (ACK).

FRESH MASTER while out-

 

 

 

 

door unit power supply of

 

 

 

 

same refrigerant system with

 

 

 

 

FRESH MASTER is turned off

 

 

 

 

or within 2 minutes of restart,

 

 

 

 

abnormality is detected.

 

 

 

 

2 Contact failure of transmission

 

 

 

 

wire of indoor unit or FRESH

 

 

 

 

MASTER

 

 

 

 

3 Disconnection of transmission

 

 

 

 

connector (CN2M) of indoor

 

 

 

 

unit or FRESH MASTER

 

 

 

 

4 Defective transmitting receiv-

 

 

 

 

ing circuit of indoor unit or

 

A7

 

FRESH MASTER

 

 

 

 

(6607)

 

 

 

 

 

6. If displayed address or attribute is

1 If the power supply of LOSS-

 

 

 

 

 

 

LOSSNAY,

NAY is turned off, indoor unit

 

 

 

Indoor unit detects abnormality when

detects abnormality when it

 

 

 

indoor unit transmitted to LOSSNAY and

transmits to LOSSNAY.

 

 

 

there was no reply (ACK).

2 During sequential operation of

 

 

 

 

indoor unit and LOSSNAY of

 

 

 

 

other refrigerant system, if

 

 

 

 

indoor unit transmits to LOSS-

 

 

 

 

NAY while outdoor unit power

 

 

 

 

supply of same refrigerant sys-

 

 

 

 

tem with LOSSNAY is turned

 

 

 

 

off or within 2 minutes of

 

 

 

 

restart, abnormality is detect-

 

 

 

 

ed.

 

 

 

 

3 Contact failure of transmission

 

 

 

 

wire of indoor unit of LOSS-

 

 

 

 

NAY

 

 

 

 

4 Disconnection of transmission

 

 

 

 

connector (CN2M) of indoor

 

 

 

 

unit

 

 

 

 

5 Defective transmitting receiv-

 

 

 

 

ing circuit of indoor unit or

 

 

 

 

LOSSNAY

 

 

 

 

 

 

 

 

7. If displayed address or attribute is

1 The unit of former address

 

 

 

nonexistent,

does not exist as address

 

 

 

 

switch has changed while the

 

 

 

 

unit was energized.

 

 

 

 

2 Abnormality is detected when

 

 

 

 

indoor unit transmitted

 

 

 

 

because the address of

 

 

 

 

FRESH MASTER and LOSS-

 

 

 

 

NAY are changed after

 

 

 

 

sequential operation of

 

 

 

 

FRESH MASTER and LOSS-

 

 

 

 

NAY by remote controller.

 

 

 

 

 

 

44

Page 44
Image 44
Mitsubishi Electronics PUZ-A42NHA2-BS, PUZ-A30NHA2, PUY-A36NHA2, PUZ-A36NHA2 From the previous, Fresh Master, Lossnay, Nay