10-4. SELF-DIAGNOSIS ACTION TABLE

<Abnormalities detected when the power is turned on> (Note 1) Refer to indoor unit section for code P and code E.

Error Code

Abnormal point and detection method

Case

Judgment and action

1No voltage is supplied to terminal 1 Check following items.

block(TB1) of outdoor unit.

a) Power supply breaker

a) Power supply breaker is

b) Connection of power supply terminal block

turned off.

(TB1)

b)Contact failure or discon- c) Connection of power supply terminal block

nection of power supply

(TB1)

terminal

 

c) Open phase (L1 or L2

 

phase)

 

2 Electric power is not charged

2 Check following items.

to power supply terminal of

a) Connection of power supply terminal block

outdoor power circuit board.

(TB1)

a) Contact failure of power

b) Connection of terminal on outdoor power

supply terminal

circuit board

b)Open phase on the outdoor A12-A24N: Disconnection of connector R or S

power circuit board

Refer to 10-9.

A12-A24N :Disconnection of

A30-A42N: Disconnection of connector TABT

connector R or S

or TABS Refer to 10-9.

A30-A42N :Disconnection of

 

connector TABT or TABS

 

3Electric power is not supplied to 3 Check connection of the connector (CNDC)

outdoor controller circuit board.

on the outdoor controller circuit board.

a) Disconnection of connector

Check connection of the connector, LD1 and

(CNDC)

LD2 for A12-A24N and CNDC for A30-A36N,

 

on the outdoor power circuit board. Refer to

 

10-9.

None

4Disconnection of reactor (DCL 4 Check connection of reactor. (DCL or ACL)

or ACL)

A12-A24N: Check connection of “LO” and

 

“NO” on the outdoor noise filter circuit board.

 

Check connection of “R” and “S” on the

 

outdoor power circuit board.

 

A30-A42N: Check connection of “L1” and “L2”

 

on the active filter module.(ACTM)

 

Refer to 10-9.

5Disconnection of outdoor noise 5 a) Check connection of outdoor noise filter

filter circuit board or parts failure

circuit board.

in outdoor noise filter circuit

b) Replace outdoor noise filter circuit board.

board

Refer to 10-9.

As for A30-A42N type, it is

 

especially needed to check the

 

resistance RS1 on the noise

 

fiter circuit board.

 

6Defective outdoor power circuit 6 Replace outdoor power circuit board. board

7Defective outdoor controller 7 Replace controller board (When items above

circuit board

are checked but the units cannot be repaired).

63L connector open

1 Disconnection or contact failure

1 Check connection of 63L connector on

Abnormal if 63L connector circuit is open

of 63L connector on outdoor

outdoor controller circuit board.

for 3 minutes continuously after power sup-

controller circuit board

Refer to 10-9.

ply.

2 Disconnection or contact failure

2 Check the 63L side of connecting wire.

63L: Low-pressure switch

of 63L

 

<A42N only>

3 63L is working due to refriger-

3 Check refrigerant pressure.

ant leakage or defective parts.

Charge additional refrigerant.

F3

 

Check continuity by tester.

(5202)

 

 

Replace the parts if the parts are defective.

 

 

 

4 Defective outdoor controller

4 Replace outdoor controller circuit board.

 

circuit board

 

35

Page 35
Image 35
Mitsubishi Electronics PUY-A24NHA2-BS SELF-DIAGNOSIS Action Table, Error Code Abnormal point and detection method Case

PUZ-A36NHA2-BS, PUY-A12NHA2, PUY-A42NHA2-BS, PUY-A30NHA2, PUZ-A36NHA2 specifications

Mitsubishi Electronics has long been a leader in the HVAC industry, and their range of air conditioning units, including the PUY-A24NHA2, PUZ-A24NHA2, PUY-A24NHA2-BS, PUZ-A42NHA2-BS, and PUY-A42NHA2, exemplifies their commitment to innovation and energy efficiency. These models are designed to provide optimal climate control for both residential and commercial applications, ensuring comfort throughout the year.

One of the defining features of these models is their advanced inverter technology, which allows for precise temperature control and reduced energy consumption. The inverter technology adjusts the compressor speed according to the cooling load, significantly lowering operating costs compared to traditional fixed-speed systems. This means that users can enjoy consistent comfort without worrying about surging energy bills.

The PUY and PUZ units come equipped with powerful indoor and outdoor components that enable efficient heat exchange. These systems provide excellent performance even in extreme weather conditions, with reliable operation at low ambient temperatures. This capability ensures that you can maintain a comfortable environment, no matter the season.

Additionally, the models are designed with quiet operation in mind. The outdoor units incorporate noise-reduction technology, ensuring that the systems operate at minimal sound levels. This is especially beneficial for residential areas or office environments, where maintaining a peaceful atmosphere is crucial.

Mitsubishi Electronics has also integrated smart technology into these units. With options for remote control via Wi-Fi, users can manage their air conditioning settings from anywhere, using their smartphones or tablets. This integration enhances user convenience and allows for more efficient scheduling and energy management.

These models are also known for their environmentally friendly refrigerants, such as R410A, which contribute to lower global warming potential and align with modern sustainability practices. By choosing Mitsubishi's PUY and PUZ series, consumers not only prioritize their comfort but also contribute to environmental conservation.

In summary, the Mitsubishi Electronics PUY-A24NHA2, PUZ-A24NHA2, PUY-A24NHA2-BS, PUZ-A42NHA2-BS, and PUY-A42NHA2 air conditioning units are equipped with cutting-edge technology, offering energy efficiency, quiet operation, and smart functionality. Whether for residential or commercial use, these units are designed to meet the demands of modern climate control while prioritizing energy savings and sustainability.