Mitsubishi Electronics PUZ-A36NHA2, PUZ-A42NHA2-BS, PUZ-A30NHA2 Check if there is breaking

Models: PUZ-A36NHA2-BS PUY-A12NHA2 PUY-A42NHA2-BS PUY-A30NHA2 PUZ-A36NHA2 PUY-A36NHA2-BS PUZ-A18NHA2 PUZ-A18NHA2-BS PUY-A30NHA2-BS PUZ-A30NHA2-BS PUY-A18NHA2 PUY-A36NHA2 PUZ-A30NHA2 PUY-A12NHA2-BS PUZ-A24NHA2-BS PUZ-A42NHA2 PUY-A18NHA2-BS PUY-A42NHA2 PUZ-A42NHA2-BS PUY-A24NHA2-BS PUZ-A24NHA2 PUY-A24NHA2

1 120
Download 120 pages 22.49 Kb
Page 50
Image 50

Symptoms: Nothing is displayed on the remote controller 3

LED display of the indoor controller board

LED1 :

LED2 : or

LED3 : —

Diagnosis flow

Cause

Inspection method and

troubleshooting

 

 

Check the voltage of the terminal block (TB6) of the remote controller.

DC 10V to DC 16V?

YES

• Defective

• Replace the

 

 

 

remote controller

remote controller.

NO

 

 

 

Check the status

Lighting

• Breaking or poor

• Check if there is breaking

 

of the LED2.

 

 

contact of the remote

or poor contact of the

 

 

 

 

controller wire

remote controller wire.

Blinking

 

 

Check the voltage of the

 

 

 

terminal block (TB5)

Check the status of the LED2

 

connecting the remote

 

controller wire.

after disconnecting the remote

 

If it is not between DC 10V

controller wire from the terminal

 

and DC16V, the indoor

block (TB5) of the indoor unit.

 

controller board must be

 

 

 

 

 

 

defective.

Check the status

Lighting

• The remote controller

• Check if the remote

 

of the LED2.

 

 

wire short-circuits

controller wire is

 

 

Blinking

 

 

short-circuited.

 

 

 

 

 

• Defective indoor

• Replace the indoor

 

 

controller board

controller board.

50

Page 50
Image 50