Mitsubishi Electronics PUY-A36NHA2, PUZ-A42NHA2-BS LD1-LD2, Dip-Pfc, Dip-Ipm, CN3 CN4 CN5

Models: PUZ-A36NHA2-BS PUY-A12NHA2 PUY-A42NHA2-BS PUY-A30NHA2 PUZ-A36NHA2 PUY-A36NHA2-BS PUZ-A18NHA2 PUZ-A18NHA2-BS PUY-A30NHA2-BS PUZ-A30NHA2-BS PUY-A18NHA2 PUY-A36NHA2 PUZ-A30NHA2 PUY-A12NHA2-BS PUZ-A24NHA2-BS PUZ-A42NHA2 PUY-A18NHA2-BS PUY-A42NHA2 PUZ-A42NHA2-BS PUY-A24NHA2-BS PUZ-A24NHA2 PUY-A24NHA2

1 120
Download 120 pages 22.49 Kb
Page 68
Image 68

Outdoor power circuit board PUZ-A18NHA2 PUZ-A18NHA2-BS PUY-A12/18NHA2 PUY-A12/18NHA2-BS

LD1-LD2

280-380V DC Connect to the outdoor controller circuit board (CNDC)

Brief check of DIP-IPM and DIP-PFC

WUsually, they are in a state of being short-circuited if they are broken. Measure the resistance in the following points (connectors, etc.). If they are short-circuited, it means that they are broken.

1. Check of DIP-IPM

P-U, P-V, P-W, N-U, N-V, N-W 2. Check of DIP-PFC

P-R, P-S, R-N, S-N

R, S

U, V, W

Connect to the ACL

Connect to the compressor (MC)

208/230V AC

Voltage among phases: 5V to 180V AC

DIP-PFC

LD9 Connect to the earth Only A24

DIP-IPM

CN2 Connect to the outdoor controller circuit board (CN2)

1-5:Outdoor power circuit board Transmitting signal to the outdoor controller circuit board (0-5V DC)

2-5: Zero cross signal (0-5V DC)

3-4: Not used

6-5: 16V DC

[1, 2, 6, 75

:: +]

7-5: 16V DC

 

 

CN3

CN4

CN5

Thermistor

Connect from the

Primary current detection

<Heatsink>

outdoor controller

(Connect to the outdoor

(TH8)

circuit board

noise filter circuit board

 

(CN4)

(CN5))

68

Page 68
Image 68
Mitsubishi Electronics PUY-A36NHA2, PUZ-A42NHA2-BS, PUZ-A30NHA2, PUZ-A18NHA2-BS LD1-LD2, Dip-Pfc, Dip-Ipm, CN3 CN4 CN5