Error Code | Abnormal point and detection method | Case | Judgment and action | |
|
|
|
| |
| Communication error with communica- | 1 Data of transmission proces- | Turn off the power supply of outdoor unit and | |
| tion processor | sor or unit processor is not | indoor unit and FRESH MASTER or LOSSNAY | |
| Defective communication between unit | transmitted normally because | at the same time for 2 minutes or more, and | |
| processor and transmission processor | of accidental trouble such as | turn the power on again. System returns to nor- | |
| Note) The address and attribute display at | noise or thunder surge. | mal if abnormality was accidental malfunction. | |
A6 | remote controller indicate the con- | 2 Address forwarding from unit | If the same abnormality generates again, | |
(6606) | troller that detected abnormality. | processor is not transmitted | ||
normally because of defective | tive. | |||
|
| |||
|
| transmission processor hard- |
| |
|
| ware. |
| |
|
|
|
| |
| NO ACK signal | Common factor that has no rela- | Always try the followings when the error | |
| 1. Transmitting side controller detects | tion with abnormality source. | “A7” occurs. | |
| abnormal if a massage was transmitted | 1 The unit of former address |
| |
| but there is no reply (ACK) that a mes- | does not exist as address | 1 Turn off the power supply of outdoor unit and | |
| sage was received. Transmitting side | switch has changed while the | indoor unit and FRESH MASTER or LOSS- | |
| unit was energized. | NAY at the same time for 2 minutes or more, | ||
| detects abnormality every 30 seconds, 6 | |||
| 2 Extinction of transmission wire | and turn the power on again. If malfunction | ||
| times continuously. | voltage and signal is caused by | was accidental, the unit returns to normal. | |
| Note) The address and attribute displayed | |||
| 2 Check address switch of abnormality gener- | |||
| at remote controller is indicate the | |||
| • Maximum distance ······200m | ated address. | ||
| controller that did not reply (ACK). | |||
| [656ft] | 3 Check disconnection or looseness of abnor- | ||
|
| |||
|
| • Remote controller line ··(12m | mality generated or abnormality detected | |
|
| [39ft]) | transmission wire (terminal block and con- | |
|
| 3 Extinction of transmission wire | nector) | |
|
| voltage and signal is caused by | 4 Check if tolerance range of transmission wire | |
|
| is not exceeded. | ||
|
| wire. | 5 Check if type of transmission wire is correct | |
|
| Type ······ | or not. | |
|
| With shield wire- |
| |
|
| CVVS, CPEVS | If there were some troubles of | |
|
| With normal wire (no shield)- | repair the defective, then turn off the power | |
|
| VCTF, VCTFK, CVV | supply of outdoor unit and indoor unit and | |
|
| CVS, VVR, VVF, VCT | FRESH MASTER or LOSSNAY at the same | |
|
| Diameter····1.25mm2 [AWG16] | time for 2 minutes or more, and turn the power | |
|
| or more | on again. | |
|
| 4 Extinction of transmission wire | • If there was no trouble with | |
|
| voltage and signal is caused | gle refrigerant system (one outdoor unit), con- | |
|
| by | troller of displayed address or attribute is | |
|
| 5 Accidental malfunction of | defective. | |
|
| • If there was no trouble with | ||
|
| (noise, thunder surge) | ferent refrigerant system (2 or more outdoor | |
A7 |
| 6 Defective of abnormality gen- | units), judge with 6. | |
(6607) |
| erated controller | 6 If address of abnormality source is the | |
|
| |||
|
|
| ||
| 2. If displayed address or attribute is out- | 1 Contact failure of transmission | address that should not exist, there is the | |
| door unit, Indoor unit detects abnormali- | wire of outdoor unit or indoor | unit that memorizes nonexistent address | |
| ty when indoor unit transmitted to out- | unit | information. Delete useless address informa- | |
| door unit and there was no reply (ACK). | 2 Disconnection of transmission | tion with manual setting function of remote | |
|
| connector (CN2M) of outdoor | controller. | |
|
| unit | Only the system FRESH MASTER or LOSS- | |
|
| 3 Defective transmitting receiv- | NAY are connected to, or the system that is | |
|
| ing circuit of outdoor unit or | equipped with group setting of different | |
|
| indoor unit | refrigerant system. | |
|
|
| If there was no trouble with | |
|
|
| replace the controller board of displayed | |
| 3. If displayed address or attribute is | 1 During group operation with | ||
| address or attribute. | |||
| indoor unit, remote controller detects | indoor unit of multi- refrigerant | ||
| If the unit does not return to normal, | |||
| abnormality when remote controller | system, if remote controller | ||
| troller board of outdoor unit may be defective | |||
| transmitted to indoor unit and there was | transmit to indoor unit while | ||
| (repeater circuit). | |||
| no reply (ACK). | outdoor unit power supply of | ||
| Replace | |||
|
| one refrigerant system is | ||
|
| check if the unit returns to normal. | ||
|
| turned off or within 2 minutes | ||
|
|
| ||
|
| of restart, abnormality is |
| |
|
| detected. |
| |
|
| 2 Contact failure of transmission |
| |
|
| wire of remote controller or |
| |
|
| indoor unit |
| |
|
| 3 Disconnection of transmission |
| |
|
| connector (CN2M) of indoor |
| |
|
| unit |
| |
|
| 4 Defective transmitting receiv- |
| |
|
| ing circuit of indoor unit or |
| |
|
| remote controller |
| |
|
|
|
| |
|
|
| Continued to the next page. |