Models: PUZ-A36NHA2-BS PUY-A12NHA2 PUY-A42NHA2-BS PUY-A30NHA2 PUZ-A36NHA2 PUY-A36NHA2-BS PUZ-A18NHA2 PUZ-A18NHA2-BS PUY-A30NHA2-BS PUZ-A30NHA2-BS PUY-A18NHA2 PUY-A36NHA2 PUZ-A30NHA2 PUY-A12NHA2-BS PUZ-A24NHA2-BS PUZ-A42NHA2 PUY-A18NHA2-BS PUY-A42NHA2 PUZ-A42NHA2-BS PUY-A24NHA2-BS PUZ-A24NHA2 PUY-A24NHA2

1 120
Download 120 pages 22.49 Kb
Page 33
Image 33

10-3-4. Malfunction-diagnosis method by wireless remote controller

<In case of trouble during operation>

When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform unusual stop.

<Malfunction-diagnosis method at maintenance service>

CHECK display

ON/OFF button

CHECK button

CHECK

ON/OFF

TEMP

 

FAN

AUTO STOP

MODE

VANE

AUTO START

CHECK

LOUVER

h

TEST RUN

 

min

SET

RESET CLOCK

[Procedure]

Refrigerant

1. Press the CHECK button twice.

• "CHECK" lights, and refrigerant

 

address "00" blinks.

address

 

 

• Check that the remote controller's

display

 

 

 

display has stopped before continuing.

Temperature

2. Press the temperature

• Select the refrigerant address of the

buttons.

indoor unit for the self-diagnosis.

button

 

Note: Set refrigerant address using the

 

 

 

 

outdoor unit’s DIP switch (SW1).

 

 

(For more information, see the

 

 

outdoor unit installation manual.)

HOUR

3. Point the remote controller at the

• If an air conditioner error occurs, the

sensor on the indoor unit and

indoor unit's sensor emits an intermit-

button

press the HOUR button.

tent buzzer sound, the operation lamp

 

 

 

blinks, and the error code is

 

 

output.

 

 

(It takes 3 seconds at most for error

 

 

code to appear.)

 

4. Point the remote controller at the

• The check mode is cancelled.

 

sensor on the indoor unit and

 

 

press the ON/OFF button.

 