Mitsubishi Electronics PUY-A30NHA2, PUZ-A42NHA2-BS, PUZ-A30NHA2 119, Low pressure switch 63L, Dcl

Models: PUZ-A36NHA2-BS PUY-A12NHA2 PUY-A42NHA2-BS PUY-A30NHA2 PUZ-A36NHA2 PUY-A36NHA2-BS PUZ-A18NHA2 PUZ-A18NHA2-BS PUY-A30NHA2-BS PUZ-A30NHA2-BS PUY-A18NHA2 PUY-A36NHA2 PUZ-A30NHA2 PUY-A12NHA2-BS PUZ-A24NHA2-BS PUZ-A42NHA2 PUY-A18NHA2-BS PUY-A42NHA2 PUZ-A42NHA2-BS PUY-A24NHA2-BS PUZ-A24NHA2 PUY-A24NHA2

1 120
Download 120 pages 22.49 Kb
Page 119
Image 119

OPERATING PROCEDURE

PHOTOS

10. Removing the high pressure switch (63H) and

Photo 8

low pressure switch (63L)

 

(1)Remove the service panel. (See figure 1.)

(2)Remove the top panel. (See figure 1.)

(3)Remove 3 right side panel fixing screws (5 10) in the rear of the unit and remove the right side panel.

(4)Pull out the lead wire of high pressure switch and low pressure switch.

(5)Recover refrigerant.

(6)Remove the welded part of high pressure switch and low pressure switch.

Note 1: Recover refrigerant without spreading it in the air.

Note 2: The welded part can be removed easily by removing the right side panel.

Note 3: When installing the high pressure switch, cover it with a wet cloth to prevent it from heating (210°F or more), then braze the pipes so that the inside of pipes are not oxidized.

High pressure

Low pressure

switch (63H)

switch (63L)

11. Removing the reactor (DCL) and capacitor (CE)

Photo 9

 

 

(1)

Remove the service panel. (See figure 1.)

 

 

 

 

 

 

(2)

Remove the top panel. (See figure 1.)

 

 

 

 

(3)

Remove the electrical parts box. (See photo 3.)

 

 

 

 

<Removing the reactor>

 

 

 

 

(4)

Remove 4 reactor fixing screws (4 10) and remove the

 

 

 

 

 

Reactor

 

 

 

reactor.

 

 

 

 

 

(DCL)

 

Electrical parts box

<Removing the capacitor>

 

 

 

 

 

 

 

 

(4)

Remove 2 capacitor band fixing screws (4 10) and

 

 

 

 

 

remove the capacitor.

 

 

 

 

wThe reactor and capacitor is attached to the rear of the

electrical parts box.

 

Reactor

 

Reactor

fixing

 

screws

 

fixing

 

 

 

screws

 

Capacitor (CE)

Capacitor band

 

 

fixing screws

119

Page 119
Image 119
Mitsubishi Electronics PUY-A30NHA2 119, Low pressure switch 63L, Removing the reactor DCL and capacitor CE, Dcl