Error Code |
| Abnormal point and detection method | Case |
|
| Judgment and action | |||||
|
|
|
|
|
| ||||||
| Open/short circuit of discharge | 1 Disconnection or contact |
|
| 1 Check connection of connector (TH4) on the | ||||||
| temperature thermistor (TH4) | failure of connector (TH4) on |
| outdoor controller circuit board. | |||||||
| Abnormal if open (3: [37˚F] or less) or | the outdoor controller circuit |
| Check breaking of the lead wire for | |||||||
| short (217: [422˚F] or more) is detected | board |
|
| thermistor (TH4). Refer to | ||||||
| during compressor operation. | 2 Defective thermistor |
|
| 2 Check resistance value of thermistor (TH4) or | ||||||
U3 | (Detection is inoperative for 10 minutes of | 3 Defective outdoor controller |
| temperature by microcomputer. | |||||||
| (Thermistor/TH4: Refer to | ||||||||||
compressor starting process and for 10 | circuit board |
|
| ||||||||
(5104) |
|
| |||||||||
|
| (SW2 on | |||||||||
minutes after and during defrosting.) |
|
|
| ||||||||
|
|
|
| ||||||||
|
|
|
| 10.) |
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| 3 Replace outdoor controller board. | |||
|
|
|
| ||||||||
| Open/short of outdoor unit thermistors | 1 Disconnection or contact failure | 1 Check connection of connector (TH3,TH6/TH7) | ||||||||
| (TH3, TH6, TH7, and TH8) | of connectors |
| ) | on the outdoor controller circuit board. | ||||||
| Abnormal if open or short is detected | Outdoor controller circuit |
| Check connection of connector (CN3) on the | |||||||
| during compressor operation. | board: TH3,TH6/TH7 |
| outdoor power circuit board. | |||||||
| Open detection of thermistors TH3 and | Outdoor power circuit board: | Check breaking of the lead wire for thermistor | ||||||||
| TH6 is inoperative for 10 seconds to 10 | (CN3 |
| (TH3,TH6,TH7,TH8). Refer to | |||||||
| minutes after compressor starting and 10 | 2 Defective thermistor |
|
| 2 Check resistance value of thermistor | ||||||
| minutes after and during defrosting. | 3 Defective outdoor controller |
| (TH3,TH6,TH7,TH8) or check temperature by | |||||||
| WCheck which unit has abnormality in its | circuit board |
|
| microcomputer. |
|
| ||||
|
| thermistor by switching the mode of |
|
|
| (Thermistor / TH3, TH6, TH7, TH8 : Refer to | |||||
U4 |
| SW2. |
|
|
|
| (SW2 on | ||||
| (Refer to |
|
|
|
| 10.) |
|
|
| ||
(TH3:5105) |
|
|
|
|
|
|
|
| |||
|
|
|
|
| 3 Replace outdoor controller circuit board. | ||||||
|
|
|
|
|
|
| |||||
(TH6:5107) |
|
|
|
|
|
|
| WEmergency operation is available in case of | |||
(TH7:5106) |
|
|
|
|
|
|
| abnormalities of TH3, TH6 and TH7. | |||
(TH8:5110) |
|
|
|
|
|
|
| Refer to |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Thermistors |
|
| Open detection |
| Short detection |
| |
|
| Symbol |
| Name |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| ||
|
| TH3 |
| Thermistor <Outdoor pipe> | – |
| 90:[194˚F] or above |
| |||
|
| TH6 |
| Thermistor <Outdoor | – |
| 90:[194˚F] or above |
| |||
|
| TH7 |
| Thermistor <Outdoor> | – |
| 90:[194˚F] or above |
| |||
|
| TH8 |
| Thermistor <Heatsink> | – |
| 102:[216˚F] or above |
| |||
|
|
|
|
|
| ||||||
| Temperature of heatsink | 1 The outdoor fan motor is |
|
| 12 Check outdoor fan. | ||||||
| Abnormal if heat sink thermistor(TH8) | locked. |
|
|
|
|
|
| |||
| detects temperature indicated below. | 2 Failure of outdoor fan motor |
| 3 Check airflow path for cooling. | |||||||
| A12, 18, 42N··············84:, 183˚F | 3 Air flow path is clogged. |
|
| |||||||
| A24, 30, 36N··············81:, 177˚F | 4 Rise of ambient temperature |
| 4 Check if there is something which causes | |||||||
|
|
|
|
| 5 Defective thermistor |
|
| temperature rise around outdoor unit. | |||
|
|
|
|
| 6 Defective input circuit of |
|
| (Upper limit of ambient temperature is 46: | |||
|
|
|
|
| outdoor power circuit board |
| [114˚F].) |
|
| ||
|
|
|
|
| 7 Failure of outdoor fan drive |
| Turn off power, and on again to check if U5 | ||||
|
|
|
|
|
| is displayed within 30 minutes. | |||||
U5 |
|
|
|
| circuit |
|
| ||||
|
|
|
|
|
| If U4 is displayed instead of U5, follow the | |||||
(4230) |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
| action to be taken for U4. | ||||
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| 5 Check resistance value of thermistor (TH8) | |||
|
|
|
|
|
|
|
| or temperature by microcomputer. | |||
|
|
|
|
|
|
|
| (Thermistor/TH8: Refer to | |||
|
|
|
|
|
|
|
| (SW2 on | |||
|
|
|
|
|
|
|
| 10.) |
|
|
|
|
|
|
|
|
|
|
| 6 Replace outdoor power circuit board. | |||
|
|
|
|
|
|
|
| 7 Replace outdoor controller circuit board. | |||
|
|
|
|
| |||||||
| Power module |
| 1 Outdoor stop valve is closed. | 1 Open stop valve. | |||||||
| Check abnormality by driving power module | 2 Decrease of power supply voltage | 2 Check facility of power supply. | ||||||||
| in case overcurrent is detected. | 3 Looseness, disconnection or |
| 3 Correct the wiring (U·V·W phase) to | |||||||
U6 | (UF or UP error condition) | converse of compressor wiring | compressor. Refer to | ||||||||
(4250) |
|
|
|
| connection |
|
| circuit board). |
|
| |
|
|
|
|
| 4 Defective compressor |
|
| 4 Check compressor referring to |
5Defective outdoor power circuit 5 Replace outdoor power circuit board. board