Models: PUZ-A36NHA2-BS PUY-A12NHA2 PUY-A42NHA2-BS PUY-A30NHA2 PUZ-A36NHA2 PUY-A36NHA2-BS PUZ-A18NHA2 PUZ-A18NHA2-BS PUY-A30NHA2-BS PUZ-A30NHA2-BS PUY-A18NHA2 PUY-A36NHA2 PUZ-A30NHA2 PUY-A12NHA2-BS PUZ-A24NHA2-BS PUZ-A42NHA2 PUY-A18NHA2-BS PUY-A42NHA2 PUZ-A42NHA2-BS PUY-A24NHA2-BS PUZ-A24NHA2 PUY-A24NHA2

1 120
Download 120 pages 22.49 Kb
Page 37
Image 37

<Abnormalities detected while unit is operating>

Error Code

Abnormal point and detection method

Case

Judgment and action

 

High pressure (High-pressure switch

1 Short cycle of indoor unit

1~6Check indoor unit and repair the defect.

 

63H worked)

2 Clogged filter of indoor unit

 

 

Abnormal if high-pressure switch 63H

3 Decreased airflow caused by

 

 

worked ( w ) during compressor operation.

dirt of indoor fan

 

 

w 4.15 MPa [602PSIG]

4 Dirt of indoor heat exchanger

 

 

63H: High-pressure switch

5 Locked indoor fan motor

 

 

6 Malfunction of indoor fan motor

7 Check if stop valve is fully open.

 

 

7 Defective operation of stop

 

 

valve (Not full open)

 

 

 

8 Clogged or broken pipe

8 Check piping and repair the defect.

 

 

9 Locked outdoor fan motor

9~2 Check outdoor unit and repair the defect.

 

 

0 Malfunction of outdoor fan

 

 

 

motor

 

 

 

1 Short cycle of outdoor unit

 

U1

 

2 Dirt of outdoor heat exchanger

3 Check the inspected temperature of outside

 

3 Decreased airflow caused by

(1302)

 

 

defective inspection of outside

temperature thermistor on LED display.

 

 

 

 

temperature thermistor

(SW2 on A-Control Service Tool : Refer to 10-

 

 

(It detects lower temperature

10.)

 

 

than actual temperature.)

4~6Turn the power off and check F5 is

 

 

4 Disconnection or contact failure

 

 

of connector (63H) on outdoor

displayed when the power is on again.

 

 

controller board

When F5 is displayed, refer to “Judgment

 

 

5 Disconnection or contact failure

and action” for F5.

 

 

of 63H connection

 

 

 

6 Defective outdoor controller

 

 

 

board

7 Check linear expansion valve.

 

 

7 Defective action of linear

 

 

expansion valve

Refer to 10-6, 7.

 

 

8 Malfunction of fan driving

8 Replace outdoor controller board.

 

 

circuit

 

 

 

 

 

 

High discharging temperature

1 Overheated compressor opera-

1 Check intake superheat.

 

(1) Abnormal if discharge temperature ther-

tion caused by shortage of

Check leakage of refrigerant.

 

mistor (TH4) exceeds 125:[257˚F] or

refrigerant

Charge additional refrigerant.

 

110: [230˚F] continuously for 5 min-

2 Defective operation of stop

2 Check if stop valve is fully open.

 

utes.

valve

 

 

Abnormal if condenser/evaporator tem-

3 Defective thermistor

34 Turn the power off and check if U3 is dis-

 

perature thermistor (TH5) exceeds 40:

4 Defective outdoor controller

played when the power is on again.

 

[104˚F] during defrosting and discharge

board

When U3 is displayed, refer to “Judgement

 

temperature thermistor (TH4) exceeds

 

and action” for U3.

 

110: [230˚F].

5 Defective action of linear

5 Check linear expansion valve.

 

(2) Abnormal if discharge superheat

expansion valve

Refer to 10-6, 7.

 

 

 

 

(Cooling: TH4 – TH5 / Heating: TH4 –

 

 

 

TH6) increases.

 

 

 

All the conditions in A or B are detected

 

 

 

simultaneously for 10 minutes continu-

 

 

 

ously after 6 minutes past from com-

 

 

 

pressor start-up (including the thermo-

 

 

U2

stat indication or recovery from defrost-

 

 

ing).

 

 

(1102)

<Condition A>

 

 

 

• Heating mode

 

 

 

• When discharge superheat is less

 

 

 

than 70 deg [126˚F].

 

 

 

• When the TH6 temp is more than the

 

 

 

value obtained by TH7 – 5 deg [9˚F].

 

 

 

• When the condensing temp of TH5 is

 

 

 

less than 35: [95˚F].

 

 

<Condition B>

During comp operation (Cooling and Heating)

When discharge superheat is less than 80 deg [144˚F] in cooling

When discharge super heat is less than 90 deg [162˚F] in heating

When condensing temp of TH6 is more than –40:[–40˚F] (In cooling only)

37

Page 37
Image 37
Mitsubishi Electronics PUY-A12NHA2, PUZ-A42NHA2-BS, PUZ-A30NHA2 Abnormalities detected while unit is operating, 63H worked

PUZ-A36NHA2-BS, PUY-A12NHA2, PUY-A42NHA2-BS, PUY-A30NHA2, PUZ-A36NHA2 specifications

Mitsubishi Electronics has long been a leader in the HVAC industry, and their range of air conditioning units, including the PUY-A24NHA2, PUZ-A24NHA2, PUY-A24NHA2-BS, PUZ-A42NHA2-BS, and PUY-A42NHA2, exemplifies their commitment to innovation and energy efficiency. These models are designed to provide optimal climate control for both residential and commercial applications, ensuring comfort throughout the year.

One of the defining features of these models is their advanced inverter technology, which allows for precise temperature control and reduced energy consumption. The inverter technology adjusts the compressor speed according to the cooling load, significantly lowering operating costs compared to traditional fixed-speed systems. This means that users can enjoy consistent comfort without worrying about surging energy bills.

The PUY and PUZ units come equipped with powerful indoor and outdoor components that enable efficient heat exchange. These systems provide excellent performance even in extreme weather conditions, with reliable operation at low ambient temperatures. This capability ensures that you can maintain a comfortable environment, no matter the season.

Additionally, the models are designed with quiet operation in mind. The outdoor units incorporate noise-reduction technology, ensuring that the systems operate at minimal sound levels. This is especially beneficial for residential areas or office environments, where maintaining a peaceful atmosphere is crucial.

Mitsubishi Electronics has also integrated smart technology into these units. With options for remote control via Wi-Fi, users can manage their air conditioning settings from anywhere, using their smartphones or tablets. This integration enhances user convenience and allows for more efficient scheduling and energy management.

These models are also known for their environmentally friendly refrigerants, such as R410A, which contribute to lower global warming potential and align with modern sustainability practices. By choosing Mitsubishi's PUY and PUZ series, consumers not only prioritize their comfort but also contribute to environmental conservation.

In summary, the Mitsubishi Electronics PUY-A24NHA2, PUZ-A24NHA2, PUY-A24NHA2-BS, PUZ-A42NHA2-BS, and PUY-A42NHA2 air conditioning units are equipped with cutting-edge technology, offering energy efficiency, quiet operation, and smart functionality. Whether for residential or commercial use, these units are designed to meet the demands of modern climate control while prioritizing energy savings and sustainability.