Mitsubishi Electronics PUZ-A24NHA2-BS Easy Maintenance Function, Switching to maintenance mode

Models: PUZ-A36NHA2-BS PUY-A12NHA2 PUY-A42NHA2-BS PUY-A30NHA2 PUZ-A36NHA2 PUY-A36NHA2-BS PUZ-A18NHA2 PUZ-A18NHA2-BS PUY-A30NHA2-BS PUZ-A30NHA2-BS PUY-A18NHA2 PUY-A36NHA2 PUZ-A30NHA2 PUY-A12NHA2-BS PUZ-A24NHA2-BS PUZ-A42NHA2 PUY-A18NHA2-BS PUY-A42NHA2 PUZ-A42NHA2-BS PUY-A24NHA2-BS PUZ-A24NHA2 PUY-A24NHA2

1 120
Download 120 pages 22.49 Kb
Page 85
Image 85

11 EASY MAINTENANCE FUNCTION

Reduces maintenance work drastically.

Enables you to check operation data of the indoor and outdoor units by remote controller.

Furthermore, use of maintenance stable-operation control that fixes the operating frequency, allows smooth inspection, even

for inverter models.

Smooth Mainte-

Discharge temperature 147˚F

Conventional inspection work

nance Function

 

Easy maintenance information (unit)

 

Compressor

 

Outdoor unit

 

Indoor unit

1

Accumulated operating

4

Heat exchanger

7

Intake air

 

time (o10 hours)

 

temperature (˚F)

 

temperature (˚F)

2

Number of ON/OFF

5

Discharge

8

Heat exchanger

 

times (o10 times)

 

temperature (˚F)

 

temperature (˚F)

3

Operating

6

Outside air

9

Filter operating

current (A)

temperature (˚F)

time* (Hours)

 

 

 

 

 

 

* The filter operating time is the time that has elapsed since the filter was reset.

Outdoor unit

Remove the

service panel.

Measure the discharge

temperature.

Indoor unit

Measure the intake air temperature.

Measure the outside air temperature

11-1.MAINTENANCE MODE OPERATION METHOD

*If you are going to use the "11-2.GUIDE FOR OPERATION CONDITION", set the airflow to "High" before activating maintenance mode.

Switching to maintenance mode

Maintenance mode can be activated either when the air conditioner is operated or stopped. It cannot be activated during test run.

w Maintenance information can be viewed even if the air conditioner is stopped.

Remote controller button information

A C B

D

Operation mode

Compressor information Outdoor unit information Indoor unit information

Confirm

Activate/cancel maintenance mode

(1) Press the TEST button for 3 seconds to switch to maintenance mode.

[Display A] MAINTENANCE

If stable operation is unnecessary or if you want to check the data with the air conditioner stopped, skip to step (4).

Fixed Hz operation

The operating frequency can be fixed to stabilize operation of inverter model. If the air conditioner is currently stopped, start it by this operation.

(2) Press the MODE button to select the desired operation mode.

[Display A]

 

Stable cooling

 

Stable heating

 

Stable operation

 

operation

 

operation

 

cancellation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL

 

 

 

HEAT

 

 

 

STABLE MODE

 

 

 

 

STABLE MODE

 

 

 

STABLE MODE

 

 

 

CANCEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(3) Press the FILTER ( ) button to check the setting.

 

[Display D] Waiting for stabilization

Stabilized

After 10 to 20 minutes

85