"TEST RUN" and the currently selected operation mode are displayed altemately.

Displays the remaining test run time.

59 °F

B

C

A[TEST] button

Pipe (liquid) temperature

Operating procedures

While the room temperature display on the remote

 

controller is “PLEASE WAIT”, the remote controller is disabled.

 

Wait until “PLEASE WAIT” disappears before using remote controller.

1.Turn on the main power supply. “PLEASE WAIT” appears for about 2 minutes after power supply is turned on. w1

2.Press A TEST button twice. The TEST RUN appears on the screen.

3. Press B OPERATION SWITCH

Cooling mode: Check if cool air blows and water is drained.

Heating mode: Check if warm air blows. (It takes a little

button.

while until warm air blows.)

4.PressC AIR DIRECTION button. Check for correct motion of auto-vanes.

5. Check the outdoor unit fan for

The outdoor unit features automatic capacity control to

correct running.

provide optimum fan speeds. Therefore, the fan keeps

running at a low speed to meet the current outside air

 

 

condition unless it exceeds its available maximum power.

 

Then, in actuality, the fan may stop or run in the reverse

 

direction depending on the outside air, but this does not

 

mean malfunction.

6.Press the ON/OFF button to reset the test run in progress.

7.Register the contact number.

In case of test run, the OFF timer will be activated, and the test run will automatically stop after 2 hours.

The room temperature display section shows the pipe temperature of indoor units during the test run.

Check that all the indoor units are running properly in case of simultaneous twin operation. Malfunctions may not be displayed regardless of incorrect wiring.

w1 After turning on the power supply, the system will go into startup mode, “PLEASE WAIT” will blink on the display section of the room temperature, and lamp(green) of the remote controller will blink.

As to INDOOR BOARD LED, LED1 will be lit up, LED2 will either be lit up in case the address is 0 or turned off in case the address is not 0. LED3 will blink.

As to OUTDOOR BOARD LED, LED1(green) and LED2(red) will be lit up. (After the startup mode of the system finishes, LED2(red) will be turned off.)

In case OUTDOOR BOARD LED is digital display, and will be displayed alternately every second.

If one of the above operations doesn’t function correctly, the causes written below should be considered. Find causes from the symptoms.

The below symptoms are under test run mode. “startup” in the table means the display status of w1 written above.

Symptoms in test run mode

Cause

Remote Controller Display

OUTDOOR BOARD LED Display

< > indicates digital display.

 

 

Remote controller displays “PLEASE

After “startup” is displayed, only

• After power is turned on, “PLEASE WAIT” is displayed for 2

 

WAIT”, and cannot be operated.

green lights up. <00>

minutes during system startup. (Normal)

 

After “startup” is displayed,

• Incorrect connection of outdoor terminal block (L1, L2, and

 

green (once) and red (once)

After power is turned on, “PLEASE WAIT”

S1, S2, S3.)

blink alternately. <F1>

is displayed for 3 minutes, then error code

 

 

 

After “startup” is displayed,

 

 

is displayed.

green (once) and red (twice)

• Outdoor unit’s protection device connector is open.

 

blink alternately. <F3, F5, F9>

 

 

 

After “startup” is displayed,

• Incorrect wiring between the indoor and outdoor unit (Polarity

No display appears even when remote

green (twice) and red (once)

is wrong for S1, S2, S3.)

blink alternately. <EA. Eb>

• Remote controller transmission wire is short.

controller operation switch is turned on.

After “startup” is displayed, only

• There is no outdoor unit of address 0.

(Operation lamp does not light up.)

 

green lights up. <00>

(Address is other than 0.)

 

• Remote controller transmission wire is open.

 

 

Display appears but soon disappears

After “startup” is displayed, only

• After canceling function selection, operation is not possible for

even when remote controller is operated.

green lights up. <00>

about 30 seconds. (Normal)

w Press the remote controller’s CHECK button twice to perform self-diagnosis. See the table below for the contents of LCD display.

LCD

Contents of inferior phenomena

LCD

 

Contents of inferior phenomena

P1

Abnormality of room temperature thermistor

U1~UP

Malfunction outdoor unit

P2

Abnormality of pipe temperature thermistor/Liquid

F3~F9

Malfunction outdoor unit

P4

Abnormality of drain sensor/Float switch connector open

E0~E5

Remote controller transmitting error

P5

Drain overflow protection is working.

E6~EF

Indoor/outdoor unit communication error

P6

Freezing/overheating protection is working.

----

No

error history

P8

Abnormality of pipe temperature

FFFF

No applied unit

P9

Abnormality of pipe temperature thermistor/Cond./Eva

PA

Forced compressor stop(due to water leakage abnormality)

Fb

Abnormality of indoor controller board

 

 

 

See the table below for details of the LED display (LED 1, 2, 3) on the indoor controller board.

LED1 (microcomputer power supply)

Lits when power is supplied.

LED2 (remote controller)

Lits when power is supplied for wired remote controller.

The indoor unit should be connected to the outdoor unit with address “0” setting.

 

LED3 (indoor/outdoor communication)

Blinks when indoor and outdoor unit are communicating.

 

 

29

Page 29
Image 29
Mitsubishi Electronics PUY-A42NHA2-BS Operating procedures, Symptoms in test run mode Cause Remote Controller Display

PUZ-A36NHA2-BS, PUY-A12NHA2, PUY-A42NHA2-BS, PUY-A30NHA2, PUZ-A36NHA2 specifications

Mitsubishi Electronics has long been a leader in the HVAC industry, and their range of air conditioning units, including the PUY-A24NHA2, PUZ-A24NHA2, PUY-A24NHA2-BS, PUZ-A42NHA2-BS, and PUY-A42NHA2, exemplifies their commitment to innovation and energy efficiency. These models are designed to provide optimal climate control for both residential and commercial applications, ensuring comfort throughout the year.

One of the defining features of these models is their advanced inverter technology, which allows for precise temperature control and reduced energy consumption. The inverter technology adjusts the compressor speed according to the cooling load, significantly lowering operating costs compared to traditional fixed-speed systems. This means that users can enjoy consistent comfort without worrying about surging energy bills.

The PUY and PUZ units come equipped with powerful indoor and outdoor components that enable efficient heat exchange. These systems provide excellent performance even in extreme weather conditions, with reliable operation at low ambient temperatures. This capability ensures that you can maintain a comfortable environment, no matter the season.

Additionally, the models are designed with quiet operation in mind. The outdoor units incorporate noise-reduction technology, ensuring that the systems operate at minimal sound levels. This is especially beneficial for residential areas or office environments, where maintaining a peaceful atmosphere is crucial.

Mitsubishi Electronics has also integrated smart technology into these units. With options for remote control via Wi-Fi, users can manage their air conditioning settings from anywhere, using their smartphones or tablets. This integration enhances user convenience and allows for more efficient scheduling and energy management.

These models are also known for their environmentally friendly refrigerants, such as R410A, which contribute to lower global warming potential and align with modern sustainability practices. By choosing Mitsubishi's PUY and PUZ series, consumers not only prioritize their comfort but also contribute to environmental conservation.

In summary, the Mitsubishi Electronics PUY-A24NHA2, PUZ-A24NHA2, PUY-A24NHA2-BS, PUZ-A42NHA2-BS, and PUY-A42NHA2 air conditioning units are equipped with cutting-edge technology, offering energy efficiency, quiet operation, and smart functionality. Whether for residential or commercial use, these units are designed to meet the demands of modern climate control while prioritizing energy savings and sustainability.