11.0 Error Codes
UR = User Reset, AR = Automatic Reset, ARP = Automatic Reset after Power Down |
|
|
|
|
| |||
|
|
|
|
|
|
|
| |
NOTE: An automatic reset is only done if the fault condition has cleared. | 11.1 |
| List of Error Codes (cont) | |||||
|
|
|
|
|
| |||
|
|
|
|
|
| |||
Error code: Display | Description |
| Lockout/reset action |
| ||||
|
|
|
|
|
| Eng | Sup |
|
280 : Engine dome overtemp | Engine dome overtemp has operated |
| AR |
|
| |||
282: G83/ENS/G1M | G83/ENS module has detected an unhealthy mains condition |
| AR |
|
| |||
285: Alternator Short | Power monitor IC has detected a |
| AR |
|
| |||
287: Eng head under temp | Engine head temperature thermocouple measurement below |
|
|
|
| |||
| 103 degrees C when the CX relay is energised |
| AR |
|
| |||
298: False flame engine | Ionisation probe of engine burner detected false flame |
| AR |
|
| |||
299: False flame supplementary | Ionisation probe of supplementary burner detected false flame |
|
| AR |
| |||
300: Eng head under temp | Engine head control temperature less than 150 degrees C when |
|
|
|
| |||
| CX relay is energised |
| UR |
|
| |||
301: Eng head over temp | Engine head control temperature greater than 540 degrees C |
| AR |
|
| |||
302: Eng head thermocouple | Magnitude of the difference between the engine head control |
|
|
|
| |||
| and limit thermocouples is greater than 100 degrees C |
| UR |
|
| |||
303: Control thermocouple | Engine head control thermocouple failure |
| UR |
|
| |||
304: Limit thermocouple | Engine head limit thermocouple failure |
| UR |
|
| |||
309: Power fail detection | Power failure to fan detected 24v dc supply |
| AR |
|
| |||
310: Power monitor comm. | No data received from the power meter IC in the last 10 seconds |
|
|
|
| |||
| or the power monitor failed to register with the EGC |
|
|
|
| |||
| microcontroller within 10 seconds of power up |
| AR |
|
| |||
311: EGC comm. failure | Communication timeout or communication failure |
| AR |
|
| |||
421: Eng bu exc temp diff h’ex | Engine burner excessive temperature difference across the |
|
|
|
| |||
| heat exchanger |
| AR |
|
| |||
422: BCU Eng bu inconsistent | Transmitted state of the engine burner BCU isn’t consistent |
| AR |
|
| |||
423: BCU Supp bu inconsistent | Transmitted state of the supplementary burner BCU isn’t consistent |
| AR |
| ||||
424: Rep. loss of flame Eng bu | Repeated loss of flame engine burner |
| UR |
|
| |||
425: Rep. loss of flame Supp bu | repeated loss of flame supplementary burner |
|
| UR |
| |||
|
|
|
|
|
|
|
|
|
This is a shortened list of the error codes, which will be displayed on the Programmer or on the room unit. If more than one error is active, the one with the higher priority or the one that appeared first will be displayed.
Error codes 157,274,261,262 and 300 can be reset by the user by pressing the user reset button for 2 seconds, turning the dial to alter the flashing NO to a YES and then pressing the OK button. After a few seconds the error should clear enabling a restart of the appliance. Errors 261 and 262 may indicate a problem with the gas supply.
Errors 157,164,274 and 300 may indicate a problem with the central heating water fill or pump. If the problem persists contact the installer with the error code.
Error 158 indicates a possible blockage in the condense drain.
Error codes 10 through to 99 (except 97) are linked to installation and commissioning of your system and as such you should contact your installer to complete commissioning.
Error codes that are shown as automatic reset will disappear once the fault has cleared. The appliance will restart if there is a demand except in the case of errors 263 and 264 when the appliance must be switched off and on again to enable a restart.
All other error codes indicate a fault condition, which will require the attention of a service engineer.
© Baxi Heating UK Ltd 2010 | 19 |