Sears 153.33262 manual Water System Piping, Piping Installation

Page 21

3 FT.

Minimum

Support Strap

Maintain

Clearance*

Vent

Connector

Slope Up

1/4 Inch

Per Foot

Minimum

2 FT. Minimum Above

Any Object Within

10 FT. Horizontally

Type B Double

Wall Vent Pipe

**Maintain Specified Clearance

WATER SYSTEM PIPING

Piping Installation

Piping, fittings, and valves should be installed according to the installation drawing (Figure 23). If the indoor installation area is subject to freezing temperatures, the water piping must be protected by insulation.

The water supply pressure should not exceed 80 psi. If this occurs, a pressure reducing valve with a bypass should be installed in the cold water inlet line. This should be placed on the supply to the entire house in order to maintain equal hot and cold water pressures.

IMPORTANT: Heat cannot be applied to the water fittings on the heater as they may contain nonmetallic parts. If solder connections are used, solder the pipe to the adapter before attaching the adapter to the hot and cold water fittings.

Venting Gas Vent System With Type B Double Wall Vent Pipe.

 

 

 

 

 

 

 

 

 

 

 

 

FIGURE 21.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Listed Vent Cap

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maintain Manufacturer’s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Specified Minimum Clearance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**Maintain

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Support Strap

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Specified

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maintain

 

 

 

 

 

 

 

 

 

Seal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Clearance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Clearance*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vent Connector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slope Up

 

 

 

 

 

 

 

 

 

Unused Chimney

 

 

 

 

 

 

 

 

 

 

 

 

1/4 Inch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flue Or Masonry

 

 

 

 

 

 

 

 

 

 

 

 

Per Foot

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum

 

 

 

 

 

 

 

 

 

 

 

Enclosure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Venting Through Chimney With Type B Double Wall Vent Pipe.

FIGURE 22.

*Maintain vent pipe clearance requirements to local, state and/or the “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current edition.

**NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances states that these chimneys are intended to be installed in accordance with the installation instructions provided with each chimney support assembly. Minimum air space clearance to combustible materials should be maintained as marked on the chimney sections.

IMPORTANT: Always use a good grade of joint compound and be certain that all fittings are drawn up tight.

1.Install the water piping and fittings as shown in Figure 23. Connect the cold water supply (3/4” NPT) to the cold water inlet fitting. Connect the hot water piping (3/4” NPT) to the hot water outlet fitting.

IMPORTANT: Some models may contain energy saving heat traps to prevent the circulation of hot water within the pipes. Do not remove the inserts within the heat traps.

2.The installation of unions in both the hot and cold water supply lines is recommended for ease of removing the water heater for service or replacement.

3.The manufacturer of this water heater recommends installing a mixing valve or an anti-scald device in the domestic hot water line as shown in Figure 24. These valves reduce the point-of-use temperature of the water by mixing cold and hot water and are readily available for use.

4.If installing the water heater in a closed water system, install an expansion tank in the cold water line as specified under Closed System/Thermal Expansion.

5.Install a shut-off valve in the cold water inlet line. It should be located close to the water heater and be easily accessible. Know the location of this valve and how to shut off the water to the heater.

6.A temperature and pressure relief valve must be installed in the opening marked “Temperature and Pressure (T & P) Relief Valve” on the water heater. A discharge line must be added to the opening of the T&P Relief Valve. Follow the instructions under Temperature and Pressure Relief Valve.

7.After piping has been properly connected to the water heater, remove the aerator at the nearest hot water faucet. Open the hot water faucet and allow the tank to completely fill with water. To purge the lines of any excess air, keep the hot water faucet open for 3 minutes after a constant flow of water is obtained. Close the faucet and check all connections for leaks.

21

Image 21
Contents Gas Water Heater Safety Precautions Safe INSTALLATION, USE and ServiceBreathing Hazard Carbon Monoxide Gas Fire or Explosion HazardTable of Contents Troubleshooting Chart Year Limited Warranty on Water Heater Product WarrantyImportant Information About This Water Heater Customer ResponsibilitiesGAS PER Hour DIA. Inches Product SpecificationsMaterials Needed Materials and Basic Tools NeededGET to Know Your Water Heater GAS Models Typical InstallationImportant Information about this Water Heater Installation ChecklistWater Heater Location Combustion Air Supply and VentilationRemoving the Old Water Heater Installation InstructionsLocation Requirements Site LocationCarbon Monoxide Poisoning Hazard High Altitude Installation Clearances and AccessibilityGAS Supply Gas Pressure TestingGas Requirements Gas PipingGas Pipe Capacity Table Unconfined Space Combustion AIR & VentilationConfined Space SquareLouvers and Grilles All Air from the BuildingAll Air from Outdoors Vent Pipe System Draft Hood InstallationVent Pipe Size Vent ConnectorsChimney Connection Vertical Exhaust Gas VentWater System Piping Piping InstallationClosed System/Thermal Expansion Temperature and Pressure Relief ValveRelief Valve and Pipe Insulation Temperature & Pressure Relief ValveSolar Installation ElectricalElectrical Connections Operating Instructions Operating Your Water HeaterChecking the Draft Water Heater OperationBurn Hazard Do not touch vent Doing so can result in burnsWater Temperature Regulation Burner FlamesEmergency Shut Down Hotter Cooler Routine Preventive Maintenance Service and AdjustmentDraining and Flushing Explosion HarzardReplacement Parts Maintenance of Your Water HeaterRemoving the Burner from the Manifold/ Burner Assembly Removing the Manifold/Burner AssemblyReplacing the Manifold/Burner Assembly Cleaning the Combustion Chamber and Air Diverter AssemblyRemoving and Replacing the Gas Control Valve/Thermostat Removing the Gas Control Valve/ThermostatReplacing the Gas Valve Start Up Conditions Troubleshooting GuideOperational Conditions ServiceCondensation Smoke OdorLeakage Checkpoints Troubleshooting Chart Pressurized Combustion Chamber System Operational ChecklistSIZZLING-RUMBLING Electronic Control Display Troubleshooting Control Display Status Problem Solution Control Display Status Problem Solution YES Troubleshooting FlowchartParts Order List Pressurized Combustion ChamberKey Parts Description 153.332620 153.332640 Page MY-HOME1-800-469-4663 Get it fixed, at your home or ours

153.33262 specifications

Sears 153.33262 is a well-regarded electronic device in the field of household tools, specifically known as a versatile and reliable multi-function meter. Designed for both novice users and seasoned professionals, this meter is an essential instrument for a wide range of applications, including electrical diagnostics and home repair tasks.

One of the key features of the Sears 153.33262 is its capability to measure both AC and DC voltage, making it suitable for a variety of electrical projects. The device supports voltage measurements up to a specific range, allowing users to conduct thorough checks on outlets, circuits, and battery-powered systems. This versatility makes it an invaluable tool for electricians, technicians, and DIY enthusiasts alike.

In addition to voltage measurement, the Sears 153.33262 also boasts a multimeter functionality that includes current and resistance measurement capabilities. Users can easily measure current in different ranges, which is essential for assessing circuit loads and diagnosing electrical issues. The resistance measurement feature is beneficial for checking the integrity of wiring and components, ensuring that users can troubleshoot and resolve problems efficiently.

The design of the Sears 153.33262 emphasizes user-friendly operation. The meter typically incorporates a large, easy-to-read display that provides clear readings in various lighting conditions. The rotating selector switch allows users to switch between different measurement modes with ease, streamlining the workflow and minimizing the risk of errors.

This device is built with durability in mind, often featuring a rugged casing that can withstand the wear and tear associated with frequent use in various environments. Its portability is enhanced by its lightweight construction, allowing users to carry it easily to different job sites or locations within the home.

Furthermore, the Sears 153.33262 may also include features such as audible alerts for continuity testing, data hold functions, and battery-saving modes, further enhancing its functionality. The availability of probes and leads designed specifically for the meter ensures that users receive accurate measurements consistently.

In summary, the Sears 153.33262 is a multi-function electrical meter that stands out for its combination of versatility, user-friendly features, and robust construction. Whether one is performing simple checks around the house or engaged in complex electrical diagnostics, this meter serves as a reliable companion for all electrical measurement needs.