Sears 153.33262 Vent Pipe Size, Vent Connectors, Chimney Connection, Vertical Exhaust Gas Vent

Page 20

40 Gal. Water Heater: Align the reducer flue over top of baffle as

shown in Figure 19 (NOTE: reducer flue must be installed on 40 gal. water heater above elevation 5,400 Ft. (1,646 m) from sea level).

40 & 50 Gal. Water Heaters: Align the legs of the draft hood with the slots provided. Insert the legs and secure the draft hood to the water heater’s top with the four screws provided as shown in Figure 19. Do not alter the draft hood in any way. If you are replacing an existing water heater, be sure to use the draft hood supplied with this water heater.

Vent Pipe Size

It is important that you follow the guidelines in these instructions for sizing a vent pipe system. If a transition to a larger vent size is required, the vent transition connection must be made at the draft hood outlet.

Vent Connectors

1.Type B, Double wall, U.L. Listed Vent Pipe.

2.Single wall Vent Pipe.

Maintain the manufacturer’s specified minimum clearance from combustible materials when using type B double wall vent pipe.

Vent connectors made of type B, double wall vent pipe material may pass through walls or partitions constructed of combustible material if the minimum listed clearance is maintained.

Maintain a six inch minimum clearance from all combustible materials when using single wall vent pipe.

IMPORTANT: Single wall vent pipe cannot be used for water heaters located in attics and may not pass through attic spaces, crawl spaces or any confined or inaccessible location. A single wall metal vent connector cannot pass through any interior wall.

When installing a vent connector, please note the following (See Figures 20-22):

Install the vent connector avoiding unnecessary bends, which create resistance to the flow of vent gases.

Install without dips or sags with an upward slope of at least 1/4-inch per foot.

Joints must be fastened by sheet metal screws or other approved means. It must be supported to maintain clearances and prevent separation of joints and damage.

The length of the vent connector cannot exceed 75% of the vertical vent height.

The vent connector must be accessible for cleaning, inspection, and replacement.

Vent connectors cannot pass through any ceiling, floor, firewall, or fire partition.

It is recommended (but not mandatory) that a minimum 12 inches of vertical vent pipe be installed on the draft hood prior to any elbow in the vent system.

IMPORTANT: Existing vent systems must be inspected for obstructions, corrosion, and proper installation.

Chimney Connection

IMPORTANT: Before connecting a vent to a chimney, make sure the chimney passageway is clear and free of obstructions. The chimney must be cleaned if previously used for venting solid fuel appliances or fireplaces. Also consult local and state codes for proper chimney sizing and application or, in the absence

of local and state codes, the “National Fuel Gas Code”, ANSI

Z223.1(NFPA 54)-current edition.

The connector must be installed above the extreme bottom of the chimney to prevent potentially blocking the flue gases.

The connector must be firmly attached and sealed to prevent it from falling out.

To aid in removing the connector, a thimble or slip joint may be used.

The connector must not extend beyond the inner edge of the chimney as it may restrict the space between it and the opposite wall of the chimney (Figure 20).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

FT.

 

 

 

 

 

 

 

 

 

 

 

2 FT. Minimum Above Any Object

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Within 10 FT. Horizontally

Support Strap

Minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maintain

 

 

 

 

 

 

 

Seal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Clearance*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Do Not Extend

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vent Beyond Edge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Of Chimney

Vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connector

 

 

Slope

Up

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/4 Inch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Per Foot

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Chimney Termination Vent System

FIGURE 20.

Do not terminate the vent connector in a chimney that has not been certified for this purpose. Some local codes may prohibit the termination of vent connectors in a masonry chimney.

Vertical Exhaust Gas Vent

Vertical exhaust gas vents must be installed with U.L. listed type B vent pipe according to the vent manufacturer’s instructions and the terms of its listing.

It must be connected to the water heater’s draft hood by a listed vent connector or by directly originating at the draft hood opening.

Vertical gas vents must terminate with a listed cap or other roof assembly and be installed according to their manufacturer’s instructions.

Gas vents must be supported to prevent damage, joint separation, and maintain clearances to combustible materials (Figures 21 and 22).

IMPORTANT: This gas vent must be terminated in a vertical position to facilitate the removal of the burnt gases.

An unused chimney flue or masonry enclosure may be used as a passageway for the installation of a gas vent (Figure 22).

Common (combined) venting is allowable with vertical type B vent systems and lined masonry chimneys as long as proper draft for the water heater is established under all conditions of operation. CAUTION: DO NOT common vent this water heater with any power vented appliance.

Figures 20-22 are examples of vent pipe system installations and may or may not be typical for your specific application. Consult the “National Fuel Gas Code”, NFPA 54, ANSI Z223.1-current edition and the guidelines set forth by prevailing local codes.

20

Image 20
Contents Gas Water Heater Safe INSTALLATION, USE and Service Safety PrecautionsFire or Explosion Hazard Breathing Hazard Carbon Monoxide GasTable of Contents Troubleshooting Chart Product Warranty Year Limited Warranty on Water HeaterCustomer Responsibilities Important Information About This Water HeaterProduct Specifications GAS PER Hour DIA. InchesMaterials and Basic Tools Needed Materials NeededTypical Installation GET to Know Your Water Heater GAS ModelsInstallation Checklist Important Information about this Water HeaterWater Heater Location Combustion Air Supply and VentilationInstallation Instructions Removing the Old Water HeaterCarbon Monoxide Poisoning Hazard Location RequirementsSite Location Clearances and Accessibility High Altitude InstallationGas Pressure Testing GAS SupplyGas Requirements Gas PipingGas Pipe Capacity Table Combustion AIR & Ventilation Unconfined SpaceConfined Space SquareAll Air from Outdoors Louvers and GrillesAll Air from the Building Draft Hood Installation Vent Pipe SystemVent Connectors Vent Pipe SizeChimney Connection Vertical Exhaust Gas VentPiping Installation Water System PipingTemperature and Pressure Relief Valve Closed System/Thermal ExpansionTemperature & Pressure Relief Valve Relief Valve and Pipe InsulationElectrical Connections Solar InstallationElectrical Operating Your Water Heater Operating InstructionsWater Heater Operation Checking the DraftBurn Hazard Do not touch vent Doing so can result in burnsEmergency Shut Down Water Temperature RegulationBurner Flames Hotter Cooler Service and Adjustment Routine Preventive MaintenanceDraining and Flushing Explosion HarzardMaintenance of Your Water Heater Replacement PartsRemoving the Burner from the Manifold/ Burner Assembly Removing the Manifold/Burner AssemblyCleaning the Combustion Chamber and Air Diverter Assembly Replacing the Manifold/Burner AssemblyReplacing the Gas Valve Removing and Replacing the Gas Control Valve/ThermostatRemoving the Gas Control Valve/Thermostat Troubleshooting Guide Start Up ConditionsService Operational ConditionsCondensation Smoke OdorLeakage Checkpoints Pressurized Combustion Chamber System Operational Checklist Troubleshooting ChartSIZZLING-RUMBLING Electronic Control Display Troubleshooting Control Display Status Problem Solution Control Display Status Problem Solution Troubleshooting Flowchart YESKey Parts Description 153.332620 153.332640 Parts Order ListPressurized Combustion Chamber Page Get it fixed, at your home or ours MY-HOME1-800-469-4663

153.33262 specifications

Sears 153.33262 is a well-regarded electronic device in the field of household tools, specifically known as a versatile and reliable multi-function meter. Designed for both novice users and seasoned professionals, this meter is an essential instrument for a wide range of applications, including electrical diagnostics and home repair tasks.

One of the key features of the Sears 153.33262 is its capability to measure both AC and DC voltage, making it suitable for a variety of electrical projects. The device supports voltage measurements up to a specific range, allowing users to conduct thorough checks on outlets, circuits, and battery-powered systems. This versatility makes it an invaluable tool for electricians, technicians, and DIY enthusiasts alike.

In addition to voltage measurement, the Sears 153.33262 also boasts a multimeter functionality that includes current and resistance measurement capabilities. Users can easily measure current in different ranges, which is essential for assessing circuit loads and diagnosing electrical issues. The resistance measurement feature is beneficial for checking the integrity of wiring and components, ensuring that users can troubleshoot and resolve problems efficiently.

The design of the Sears 153.33262 emphasizes user-friendly operation. The meter typically incorporates a large, easy-to-read display that provides clear readings in various lighting conditions. The rotating selector switch allows users to switch between different measurement modes with ease, streamlining the workflow and minimizing the risk of errors.

This device is built with durability in mind, often featuring a rugged casing that can withstand the wear and tear associated with frequent use in various environments. Its portability is enhanced by its lightweight construction, allowing users to carry it easily to different job sites or locations within the home.

Furthermore, the Sears 153.33262 may also include features such as audible alerts for continuity testing, data hold functions, and battery-saving modes, further enhancing its functionality. The availability of probes and leads designed specifically for the meter ensures that users receive accurate measurements consistently.

In summary, the Sears 153.33262 is a multi-function electrical meter that stands out for its combination of versatility, user-friendly features, and robust construction. Whether one is performing simple checks around the house or engaged in complex electrical diagnostics, this meter serves as a reliable companion for all electrical measurement needs.