Trane BAS-SVP10A-EN manual MV15 Sequence of Operation values for Note, Additional MV values

Page 16

BACnet Object Properties

Table 9. MV15 (Sequence of Operation) values for Note 2

 

 

Default Value is

Default Value is

MV15 Index

Function

BV50 Enabled

BV50 Disabled

1

Cooling Only

Cool

Cool

 

 

 

 

2

Cooling with Reheat

Auto

Heat

 

 

 

 

3

Heating Only

Heat

Heat

 

 

 

 

4

Heating with Reheat

Heat

Heat

 

 

 

 

5

Cooling/Heating 4 Pipes

Auto

Heat

 

 

 

 

6

Cooling/Heating 4 Pipes with Reheat

Auto

Heat

 

 

 

 

Table Notes: (continued)

3Enumeration sets for MV17 depends on Fan Mode Sequence (MV58) value upon device discovery. If required enumeration is not present, set MV58 to desired value and rediscover MV17 object. Available enumeration will now reflect required

configuration.

4, 5 Available state text and default value depends on Fan Mode Sequence (MV58) value upon device discovery.

 

Function MV58

 

MV17 Index

State Text Index

Default Value

1

1 Low - 2 Med - 3 High

High

 

 

 

2

1 Low - 2 High

High

 

 

 

3

1 Low - 2 Med - 3 High

High

 

- 4 Auto

 

4

1 Low - 2 High - 3 Auto

High

 

 

 

5

1 Auto -2 On

Auto

 

 

 

Table 10. Additional MV values

Object Name

Object ID

BACnet Index

Text

Default value

Heating Valve Status

MV 26

Table

Table

Table

Table Note 6

 

Note 7

Note 7

Note 7

Cooling Valve Status

MV 27

Table

Table

Table

Table Note 8

Note 9

Note 9

Note 9

 

 

 

 

 

 

 

 

1

Off

 

 

 

 

 

 

Fan Status

MV 28

2

Low

Off

 

 

3

Med

 

 

 

 

 

 

 

 

 

 

4

High

 

 

 

 

 

 

 

 

1

Occupied

 

 

 

 

 

 

Effective Occupancy

MV 33

2

Unoccupied

Depends on local

 

 

occupancy

3

Temporary Occupied

 

 

 

 

 

 

 

 

 

4

Stand-by

 

 

 

 

 

 

Table Notes:

6Enumeration sets for MV26 depends on Control Type (BV75) value and Pipe Number (MV52) value upon device discovery. If required enumeration is not present, set BV75 and MV52 to desired value and rediscover MV26 object. Available enu- meration will now reflect required configuration.

7Available object name, state text and default value depends on Control Type (BV75) value and Pipe Number (MV52) upon device discovery as shown in Table 11.

Table 11. Various object indexes and values for Note 7

 

 

MV26 Object

Function MV26 State Text

 

BV75 Value

MV52 Index

Name

Index

Default Value

On/Off

1 (2 pipe)

Unused Output

N/A

N/A

 

 

 

 

 

 

2 (4 pipe)

Heating Valve

1 Closed – 2 Open

Closed

 

Status

 

 

 

 

 

 

 

 

 

Floating

1 (2 pipe)

Unused Output

N/A

N/A

 

 

 

 

 

 

2 (4 pipe)

Heating Valve

1 Stopped - 2 Opening - 3

Stopped

 

Status

Closing

 

 

 

 

 

 

 

 

8Enumeration sets for MV27 depends on Control Type (BV75) value and Pipe Number (MV52) value upon device discovery. If required enumeration is not present, set BV75 and MV52 to desired value and rediscover MV27 object. Available enu-

16

BAS-SVP10A-EN

Image 16
Contents Integration Manual Copyright Table of Contents Objects and Parameters Tracer SC Network Configuration Overview Product DescriptionHow To Information Related DocumentsPlanning Your Integration OverviewSupported BACnet Services Default Device Name and Default Device IDSummary of BACnet Objects BACnet Interoperability Building BlocksFan Coil Objects Summary of BACnet ObjectsX13511541010 and -2010 Rooftop and Heat Pump Models Objects table for fan coilsOutput Configuration Options GRP PresentValue R General Options GRP PresentValue RRooftop and Heat Pump Objects Rooftop and heat pump ungrouped objectsType Rooftop Object Name Instance Object Property 1010 2010Economizer Model GRP PresentValue R Configuration Options Stages Configuration GRP PresentValue R OptionsHeatpump Model GRP PresentValue R Configuration Options Standard Object Types Supported Standard object types supportedConfiguration Objects for Fan Coils Configuration Objects for Rooftop and Heat Pump UnitsList of Proprietary Properties Proprietary PropertiesFan Coil Object Properties BACnet Object PropertiesList of property value range restrictions Object Name Object ID BACnet Index Text Default value BACnet Object PropertiesList of property enumeration sets for MV objects Table NoteObject Name Object ID BACnet Index Text Default value Function MV58 MV17 Index State Text Index Default ValueMV15 Sequence of Operation values for Note Additional MV valuesFunction MV26 BV75 Value MV52 Index MV27 Object Name State Text IndexHour Hours Rooftop and Heat Pump Object Properties Object Type Under Range Object NameValue Over Range ValueList of property enumeration sets for BI and BV objects Object Type Object Name Instance InactiveText ActiveTextUnder Range Instance Value Over Range ValueObject Name Instance BACnet Index Text Object TypeNone RemNSB DI1 Configuration MV65 RemOVR Filter Service Objects You Can Use in Site Graphics Fan CoilsRooftop and Heat Pump Units Objects You Can Use in Site GraphicsWiring Requirements for Communicating Thermostats BACnet MS/TP Link WiringWiring Requirements for Communicating Thermostats Daisy chain configuration for BACnet wiringProduct Specifications Communicating Thermostat SpecificationsNetwork Adapter DetailsTroubleshooting Causes and solutions for error conditionPossible Cause Solution Communicating Thermostat Status LEDsMS/TP Network Integration Additional Information and ConsiderationsFan Coils Objects and Parameters Additional Information and Considerations Tracer SC Network Configuration No automatic installationNight Purge disabled No priority arrayHeat only/cool only Parameters not supportedDischarge air temp requirements No active setpoint or heat/cool mode dataInappropriate text on graphic displays BAS-SVP10A-EN Example Occupancy Request Data NormalizationTemplate TStatFanCoilTrane Reading from fan coil to Tracer SC Heat Cool Mode Request Tracer SC writing to the fan coil Heat Cool Mode RequestData Normalization Reading from fan coil to tracer SC Fan Mode BAS Tracer SC writing to the fan coil Fan Mode BASTracer SC Point name Supply Fan Staged Speed Status Template TStatHeatPumpTrane Tracer SC writing to the heat pump Occupancy StatusReading from heat pump to Tracer SC Occupancy Status Tracer SC writing to the heat pump Occupancy RequestTracer SC writing to the heat pump Heat Cool Mode Request Reading from Heat Pump to Tracer SC Heat Cool Mode RequestTemplate TStatRTUTrane Tracer SC writing to the rooftop unit Occupancy StatusTracer SC writing to the rooftop unit Occupancy Request Reading from rooftop unit to Tracer SC Occupancy RequestTrane Communicating Thermostat Points List TStatFanCoilTranePoints Available in the TStatFanCoilTrane Template TStat Device PointTStatHeatPumpTrane Template Trane Communicating Thermostat Points ListPoints Available in the TStatHeatPumpTrane Template Point Type Instance TionTStatRTUTrane Template Points Available in the TStatRTUTrane TemplatePoint Type YesAUX Page

BAS-SVP10A-EN, Trane Communicating Thermostats (BACnet) specifications

The Trane BAS-SVP10A-EN is a part of the Trane Communicating Thermostats series designed to facilitate efficient and effective building temperature control in HVAC systems. These thermostats work with BACnet (Building Automation and Control Network), a widely adopted communication protocol in building automation for networked control of HVAC systems, lighting, access control, and fire systems.

One of the standout features of the Trane BAS-SVP10A-EN is its compatibility with various Trane equipment and other BACnet-compliant devices. This versatility allows for seamless integration into existing building systems, enhancing operational efficiency. The thermostat is designed to support zoning applications, offering precise temperature control to individual areas or rooms, thus significantly improving occupant comfort while also minimizing energy consumption.

The Trane communicating thermostat is built with advanced technologies that ensure optimal performance. It utilizes digital communication, enabling real-time data exchange between the thermostat and the HVAC system. This capability enhances the responsiveness of the HVAC system, allowing it to adjust more accurately to changing environmental conditions. The thermostat features an intuitive interface with a clear display, making it user-friendly for building occupants and facility managers alike.

Another important characteristic is its advanced scheduling capabilities. Users can program customized heating and cooling schedules, promoting energy savings while maintaining comfort levels. Additionally, its remote access feature allows for monitoring and control from smartphones, tablets, or computers, making it convenient for users to manage their HVAC systems from virtually anywhere.

The Trane BAS-SVP10A-EN also boasts robust diagnostic and reporting functions. It can provide feedback on system performance, enabling proactive maintenance and troubleshooting, which increases the reliability of HVAC operations. Overall, the Trane Communicating Thermostat represents a sophisticated solution for modern building management, focusing on comfort, energy efficiency, and ease of integration into existing systems. With its commitment to leveraging cutting-edge technology, Trane continues to lead in providing innovative solutions for heating, ventilation, and air conditioning needs in diverse building environments.