Trane Communicating Thermostat Points List

Table 44. Points Available in the TStat_Fan_Coil_Trane Template (continued)

 

 

 

 

Data

 

TStat Device Point

Point

Point

Normaliza-

Tracer SC Point Name

Name

Type

Instance

tion

 

Cooling Valve Status

MV

27

 

 

 

 

 

 

 

BI 1 Configuration

MV

46

 

 

 

 

 

 

 

BI 2 Configuration

MV

47

 

 

 

 

 

 

 

UI 3 Configuration

MV

48

 

 

 

 

 

 

 

Pipe Number

MV

52

 

 

 

 

 

 

 

AUX Configuration

MV

54

 

 

 

 

 

 

 

Fan Mode Sequence

MV

57

 

 

 

 

 

 

 

Proportional Band

MV

65

 

 

 

 

 

 

 

Floating Motor Timing

MV

76

 

 

 

 

 

 

 

On Off Control CPH

MV

77

 

 

 

 

 

 

TStat_HeatPump_Trane Template

Table 45. Points Available in the TStat_HeatPump_Trane Template

 

 

 

 

Data

 

TStat Device Point

 

Point

Normaliza-

Tracer SC Point Name

Name

Point Type

Instance

tion

Cool Output 1 Status

Y1 Cool

BI

26

 

 

 

 

 

 

Cool Output 2 Status

Y2 Cool

BI

27

 

 

 

 

 

 

Diagnostic Present

Service Alarm

BI

39

 

 

 

 

 

 

Dirty Filter Alarm

Filter Alarm

BI

38

 

 

 

 

 

 

Discharge Air Temperature

Supply Temperature

AI

16

 

 

 

 

 

 

Display Temperature Scale

Temperature Scale

BV

47

 

 

 

 

 

 

Fan Mode BAS

Fan Mode

MV

15

 

 

 

 

 

 

Fan Output Status

G Fan

BI

25

 

 

 

 

 

 

Heat Cool Mode Request

System Mode HP

MV

13

Yes

 

 

 

 

 

Heat Output 1 Status

W1 Heat

BI

28

 

 

 

 

 

 

In Defrost

Frost Protection

BV

55

 

 

 

 

 

 

Keypad Lockout

Keypad Lockout

MV

18

 

 

 

 

 

 

Low Temperature Alarm

Frost Alarm

BI

36

 

 

 

 

 

 

Minimum Heating Cooling Setpoint

Deadband

AV

52

 

Differential

 

 

 

 

 

 

 

 

 

 

Occupancy Input

Local Motion

BI

33

 

 

 

 

 

 

Occupancy Request

Occupancy Command

MV

12

Yes

 

 

 

 

 

Occupancy Status

Effective Occupancy

MV

34

Yes

 

 

 

 

 

Occupied Cooling Setpoint

Occupied Cool Setpoint

AV

43

 

 

 

 

 

 

Occupied Heating Setpoint

Occupied Heat Setpoint

AV

42

 

 

 

 

 

 

Outdoor Air Temperature

Outdoor Temperature

AV

9

 

 

 

 

 

 

Reversing Valve

Reversing Valve

BI

30

 

 

 

 

 

 

Space Temperature Active

Room Temperature

AV

7

 

 

 

 

 

 

Supply Fan Configuration Command

Fan Control

BV

62

 

 

 

 

 

 

Supply Fan Failure

Fan Lockout Alarm

BI

40

 

 

 

 

 

 

Timed Override Duration Setpoint

Temporary Occupancy Time

MV

61

 

 

 

 

 

 

Unoccupied Cooling Setpoint

Unoccupied Cool Setpoint

AV

45

 

 

 

 

 

 

Unoccupied Heating Setpoint

Unoccupied Heat Setpoint

AV

44

 

 

 

 

 

 

 

PI Heating Demand

AV

20

 

 

 

 

 

 

 

PI Cooling Demand

AV

21

 

 

 

 

 

 

 

Heating Setpoint Limit

AV

48

 

 

 

 

 

 

 

Cooling Setpoint Limit

AV

49

 

 

 

 

 

 

BAS-SVP10A-EN

43

Image 43
Contents Integration Manual Copyright Table of Contents Objects and Parameters Tracer SC Network Configuration Product Description OverviewOverview How To InformationRelated Documents Planning Your IntegrationBACnet Interoperability Building Blocks Supported BACnet ServicesDefault Device Name and Default Device ID Summary of BACnet ObjectsObjects table for fan coils Fan Coil ObjectsSummary of BACnet Objects X13511541010 and -2010 Rooftop and Heat Pump ModelsGeneral Options GRP PresentValue R Output Configuration Options GRP PresentValue RObject Name Instance Object Property 1010 2010 Rooftop and Heat Pump ObjectsRooftop and heat pump ungrouped objects Type RooftopEconomizer Model GRP PresentValue R Configuration Options Stages Configuration GRP PresentValue R OptionsHeatpump Model GRP PresentValue R Configuration Options Standard object types supported Standard Object Types SupportedProprietary Properties Configuration Objects for Fan CoilsConfiguration Objects for Rooftop and Heat Pump Units List of Proprietary PropertiesFan Coil Object Properties BACnet Object PropertiesList of property value range restrictions Table Note Object Name Object ID BACnet Index Text Default valueBACnet Object Properties List of property enumeration sets for MV objectsAdditional MV values Object Name Object ID BACnet Index Text Default valueFunction MV58 MV17 Index State Text Index Default Value MV15 Sequence of Operation values for NoteMV27 Object Name State Text Index Function MV26 BV75 Value MV52 IndexHour Hours Over Range Value Rooftop and Heat Pump Object PropertiesObject Type Under Range Object Name ValueInstance Value Over Range Value List of property enumeration sets for BI and BV objectsObject Type Object Name Instance InactiveText ActiveText Under RangeObject Type Object Name Instance BACnet Index TextNone RemNSB DI1 Configuration MV65 RemOVR Filter Service Fan Coils Objects You Can Use in Site GraphicsObjects You Can Use in Site Graphics Rooftop and Heat Pump UnitsBACnet MS/TP Link Wiring Wiring Requirements for Communicating ThermostatsDaisy chain configuration for BACnet wiring Wiring Requirements for Communicating ThermostatsDetails Product SpecificationsCommunicating Thermostat Specifications Network AdapterCommunicating Thermostat Status LEDs TroubleshootingCauses and solutions for error condition Possible Cause SolutionMS/TP Network Integration Additional Information and ConsiderationsFan Coils Objects and Parameters Additional Information and Considerations No priority array Tracer SC Network ConfigurationNo automatic installation Night Purge disabledParameters not supported Heat only/cool onlyDischarge air temp requirements No active setpoint or heat/cool mode dataInappropriate text on graphic displays BAS-SVP10A-EN Example Occupancy Request Data NormalizationTemplate TStatFanCoilTrane Reading from fan coil to Tracer SC Heat Cool Mode Request Tracer SC writing to the fan coil Heat Cool Mode RequestData Normalization Reading from fan coil to tracer SC Fan Mode BAS Tracer SC writing to the fan coil Fan Mode BASTracer SC Point name Supply Fan Staged Speed Status Tracer SC writing to the heat pump Occupancy Request Template TStatHeatPumpTraneTracer SC writing to the heat pump Occupancy Status Reading from heat pump to Tracer SC Occupancy StatusTracer SC writing to the rooftop unit Occupancy Status Tracer SC writing to the heat pump Heat Cool Mode RequestReading from Heat Pump to Tracer SC Heat Cool Mode Request Template TStatRTUTraneReading from rooftop unit to Tracer SC Occupancy Request Tracer SC writing to the rooftop unit Occupancy RequestTStat Device Point Trane Communicating Thermostat Points ListTStatFanCoilTrane Points Available in the TStatFanCoilTrane TemplatePoint Type Instance Tion TStatHeatPumpTrane TemplateTrane Communicating Thermostat Points List Points Available in the TStatHeatPumpTrane TemplateYes TStatRTUTrane TemplatePoints Available in the TStatRTUTrane Template Point TypeAUX Page

BAS-SVP10A-EN, Trane Communicating Thermostats (BACnet) specifications

The Trane BAS-SVP10A-EN is a part of the Trane Communicating Thermostats series designed to facilitate efficient and effective building temperature control in HVAC systems. These thermostats work with BACnet (Building Automation and Control Network), a widely adopted communication protocol in building automation for networked control of HVAC systems, lighting, access control, and fire systems.

One of the standout features of the Trane BAS-SVP10A-EN is its compatibility with various Trane equipment and other BACnet-compliant devices. This versatility allows for seamless integration into existing building systems, enhancing operational efficiency. The thermostat is designed to support zoning applications, offering precise temperature control to individual areas or rooms, thus significantly improving occupant comfort while also minimizing energy consumption.

The Trane communicating thermostat is built with advanced technologies that ensure optimal performance. It utilizes digital communication, enabling real-time data exchange between the thermostat and the HVAC system. This capability enhances the responsiveness of the HVAC system, allowing it to adjust more accurately to changing environmental conditions. The thermostat features an intuitive interface with a clear display, making it user-friendly for building occupants and facility managers alike.

Another important characteristic is its advanced scheduling capabilities. Users can program customized heating and cooling schedules, promoting energy savings while maintaining comfort levels. Additionally, its remote access feature allows for monitoring and control from smartphones, tablets, or computers, making it convenient for users to manage their HVAC systems from virtually anywhere.

The Trane BAS-SVP10A-EN also boasts robust diagnostic and reporting functions. It can provide feedback on system performance, enabling proactive maintenance and troubleshooting, which increases the reliability of HVAC operations. Overall, the Trane Communicating Thermostat represents a sophisticated solution for modern building management, focusing on comfort, energy efficiency, and ease of integration into existing systems. With its commitment to leveraging cutting-edge technology, Trane continues to lead in providing innovative solutions for heating, ventilation, and air conditioning needs in diverse building environments.