Trane Communicating Thermostat Points List

The following tables provide side by side lists of Tracer SC points and Communicating Thermostat device point names and related information.

TStat_Fan_Coil_Trane

Table 44. Points Available in the TStat_Fan_Coil_Trane Template

 

 

 

 

Data

 

TStat Device Point

Point

Point

Normaliza-

Tracer SC Point Name

Name

Type

Instance

tion

Diagnostic Present

Service Alarm

BI

37

 

 

 

 

 

 

Dirty Filter Alarm

Filter Alarm

BI

36

 

 

 

 

 

 

Discharge Air Temperature

Supply Temperature

AI

12

 

 

 

 

 

 

Display Temperature Scale

Temperature Scale

BV

51

 

 

 

 

 

 

Emergency Heat Status

AUX Status

BI

25

 

 

 

 

 

 

Fan Mode BAS

Fan Mode

MV

17

Yes

 

 

 

 

 

Heat Cool Mode Request

System Mode

MV

16

Yes

 

 

 

 

 

Keypad Lockout

Keypad Lockout

MV

19

 

 

 

 

 

 

Minimum Heating Cooling Setpoint

Deadband

AV

63

 

Differential

 

 

 

 

 

 

 

 

 

 

Occupancy Input

Local Motion

BI

32

 

 

 

 

 

 

Occupancy Request

Occupancy Command

MV

18

Yes

 

 

 

 

 

Occupancy Status

Effective Occupancy

MV

33

Yes

 

 

 

 

 

Occupied Cooling Setpoint

Occupied Cool Setpoint

AV

40

 

 

 

 

 

 

Occupied Heating Setpoint

Occupied Heat Setpoint

AV

39

 

 

 

 

 

 

Occupied Standby Cooling Setpoint

Stand-by Cool Setpoint

AV

42

 

 

 

 

 

 

Occupied Standby Heating Setpoint

Stand-by Heat Setpoint

AV

41

 

 

 

 

 

 

Outdoor Air Temperature

Outdoor Temperature

AV

9

 

 

 

 

 

 

Space Temperature Active

Room Temperature

AV

7

 

 

 

 

 

 

Supply Fan Staged Speed Status

Fan Status

MV

28

Yes

 

 

 

 

 

Timed Override Duration Setpoint

Temporary Occupancy Time

MV

62

 

 

 

 

 

 

Unoccupied Cooling Setpoint

Unoccupied Heat Setpoint

AV

43

 

 

 

 

 

 

Unoccupied Cooling Setpoint

Unoccupied Cool Setpoint

AV

44

 

 

 

 

 

 

 

PI Heating Demand

AV

21

 

 

 

 

 

 

 

PI Cooling Demand

AV

22

 

 

 

 

 

 

 

Password Value

AV

56

 

 

 

 

 

 

 

Heating Setpoint Limit

AV

58

 

 

 

 

 

 

 

Cooling Setpoint Limit

AV

59

 

 

 

 

 

 

 

Stand-by Time

AV

67

 

 

 

 

 

 

 

Unoccupied Time

AV

68

 

 

 

 

 

 

 

BI 1 Status

BI

29

 

 

 

 

 

 

 

BI 2 Status

BI

30

 

 

 

 

 

 

 

UI 3 Status

BI

31

 

 

 

 

 

 

 

Window Alarm

BI

35

 

 

 

 

 

 

 

Room Temp Override

BV

8

 

 

 

 

 

 

 

AUX Command

BV

14

 

 

 

 

 

 

 

Menu Scroll

BV

49

 

 

 

 

 

 

 

Auto Mode Enable

BV

50

 

 

 

 

 

 

 

Setpoint Type

BV

60

 

 

 

 

 

 

 

Setpoint Function

BV

61

 

 

 

 

 

 

 

Reheat Time Base

BV

64

 

 

 

 

 

 

 

Auto Fan

BV

66

 

 

 

 

 

 

 

Control Type

BV

75

 

 

 

 

 

 

 

Sequence of Operation

MV

15

 

 

 

 

 

 

 

Heating Valve Status

MV

26

 

 

 

 

 

 

42

BAS-SVP10A-EN

Image 42
Contents Integration Manual Copyright Table of Contents Objects and Parameters Tracer SC Network Configuration Overview Product DescriptionPlanning Your Integration How To InformationRelated Documents OverviewSummary of BACnet Objects Supported BACnet ServicesDefault Device Name and Default Device ID BACnet Interoperability Building BlocksX13511541010 and -2010 Rooftop and Heat Pump Models Fan Coil ObjectsSummary of BACnet Objects Objects table for fan coilsOutput Configuration Options GRP PresentValue R General Options GRP PresentValue RType Rooftop Rooftop and Heat Pump ObjectsRooftop and heat pump ungrouped objects Object Name Instance Object Property 1010 2010Stages Configuration GRP PresentValue R Options Economizer Model GRP PresentValue R Configuration OptionsHeatpump Model GRP PresentValue R Configuration Options Standard Object Types Supported Standard object types supportedList of Proprietary Properties Configuration Objects for Fan CoilsConfiguration Objects for Rooftop and Heat Pump Units Proprietary PropertiesBACnet Object Properties Fan Coil Object PropertiesList of property value range restrictions List of property enumeration sets for MV objects Object Name Object ID BACnet Index Text Default valueBACnet Object Properties Table NoteMV15 Sequence of Operation values for Note Object Name Object ID BACnet Index Text Default valueFunction MV58 MV17 Index State Text Index Default Value Additional MV valuesFunction MV26 BV75 Value MV52 Index MV27 Object Name State Text IndexHour Hours Value Rooftop and Heat Pump Object PropertiesObject Type Under Range Object Name Over Range ValueUnder Range List of property enumeration sets for BI and BV objectsObject Type Object Name Instance InactiveText ActiveText Instance Value Over Range ValueObject Name Instance BACnet Index Text Object TypeNone RemNSB DI1 Configuration MV65 RemOVR Filter Service Objects You Can Use in Site Graphics Fan CoilsRooftop and Heat Pump Units Objects You Can Use in Site GraphicsWiring Requirements for Communicating Thermostats BACnet MS/TP Link WiringWiring Requirements for Communicating Thermostats Daisy chain configuration for BACnet wiringNetwork Adapter Product SpecificationsCommunicating Thermostat Specifications DetailsPossible Cause Solution TroubleshootingCauses and solutions for error condition Communicating Thermostat Status LEDsAdditional Information and Considerations MS/TP Network IntegrationFan Coils Objects and Parameters Additional Information and Considerations Night Purge disabled Tracer SC Network ConfigurationNo automatic installation No priority arrayHeat only/cool only Parameters not supportedNo active setpoint or heat/cool mode data Discharge air temp requirementsInappropriate text on graphic displays BAS-SVP10A-EN Data Normalization Example Occupancy RequestTemplate TStatFanCoilTrane Tracer SC writing to the fan coil Heat Cool Mode Request Reading from fan coil to Tracer SC Heat Cool Mode RequestData Normalization Tracer SC writing to the fan coil Fan Mode BAS Reading from fan coil to tracer SC Fan Mode BASTracer SC Point name Supply Fan Staged Speed Status Reading from heat pump to Tracer SC Occupancy Status Template TStatHeatPumpTraneTracer SC writing to the heat pump Occupancy Status Tracer SC writing to the heat pump Occupancy RequestTemplate TStatRTUTrane Tracer SC writing to the heat pump Heat Cool Mode RequestReading from Heat Pump to Tracer SC Heat Cool Mode Request Tracer SC writing to the rooftop unit Occupancy StatusTracer SC writing to the rooftop unit Occupancy Request Reading from rooftop unit to Tracer SC Occupancy RequestPoints Available in the TStatFanCoilTrane Template Trane Communicating Thermostat Points ListTStatFanCoilTrane TStat Device PointPoints Available in the TStatHeatPumpTrane Template TStatHeatPumpTrane TemplateTrane Communicating Thermostat Points List Point Type Instance TionPoint Type TStatRTUTrane TemplatePoints Available in the TStatRTUTrane Template YesAUX Page

BAS-SVP10A-EN, Trane Communicating Thermostats (BACnet) specifications

The Trane BAS-SVP10A-EN is a part of the Trane Communicating Thermostats series designed to facilitate efficient and effective building temperature control in HVAC systems. These thermostats work with BACnet (Building Automation and Control Network), a widely adopted communication protocol in building automation for networked control of HVAC systems, lighting, access control, and fire systems.

One of the standout features of the Trane BAS-SVP10A-EN is its compatibility with various Trane equipment and other BACnet-compliant devices. This versatility allows for seamless integration into existing building systems, enhancing operational efficiency. The thermostat is designed to support zoning applications, offering precise temperature control to individual areas or rooms, thus significantly improving occupant comfort while also minimizing energy consumption.

The Trane communicating thermostat is built with advanced technologies that ensure optimal performance. It utilizes digital communication, enabling real-time data exchange between the thermostat and the HVAC system. This capability enhances the responsiveness of the HVAC system, allowing it to adjust more accurately to changing environmental conditions. The thermostat features an intuitive interface with a clear display, making it user-friendly for building occupants and facility managers alike.

Another important characteristic is its advanced scheduling capabilities. Users can program customized heating and cooling schedules, promoting energy savings while maintaining comfort levels. Additionally, its remote access feature allows for monitoring and control from smartphones, tablets, or computers, making it convenient for users to manage their HVAC systems from virtually anywhere.

The Trane BAS-SVP10A-EN also boasts robust diagnostic and reporting functions. It can provide feedback on system performance, enabling proactive maintenance and troubleshooting, which increases the reliability of HVAC operations. Overall, the Trane Communicating Thermostat represents a sophisticated solution for modern building management, focusing on comfort, energy efficiency, and ease of integration into existing systems. With its commitment to leveraging cutting-edge technology, Trane continues to lead in providing innovative solutions for heating, ventilation, and air conditioning needs in diverse building environments.