Trane BAS-SVP10A-EN Fan Coil Objects, Summary of BACnet Objects, Objects table for fan coils

Page 8

Summary of BACnet Objects

(X13511541010 and -2010) Rooftop and Heat Pump Models

Default Device ID is set to: 7600MAC where MAC is the current MAC address of the device.

The device ID and the Device Name change if you change the device’s MAC address. For example, when a heat pump communicating thermostat with a MAC address of 63 is connected to a network, its default Device Name will be TStat_HeatPump_Trane_63 and its default Device ID will be 760063.

Fan Coil Objects

Table 2. Objects table for fan coils (X13511543010)

Object Name

Type and Instance

Object Property

Room Temperature

AV 7

Present_Value (R,W)

 

 

 

Room Temp Override

BV 8

Present_Value (R,W)

 

 

 

Outdoor Temperature

AV 9

Present_Value (R,W)

 

 

 

Supply Temperature

AI 12

Present_Value (R)

 

 

 

AUX Command

BV 14

Present_Value (R,W)

 

 

 

Sequence of Operation

MV 15

Present_Value (R,W)

 

 

 

System Mode

MV 16

Present_Value (R,W)

 

 

 

Fan Mode

MV 17

Present_Value (R,W)

 

 

 

Occupancy Command

MV 18

Present_Value (R,W)

 

 

 

Keypad Lockout

MV 19

Present_Value (R,W)

 

 

 

 

 

 

Control Output

GRP 20

Present_Value (R)

 

 

 

PI Heating Demand

AV 21

Present_Value (R)

 

 

 

PI Cooling Demand

AV 22

Present_Value (R)

 

 

 

 

 

 

Controller Status

GRP 24

Present_Value (R)

 

 

 

AUX Status

BI 25

Present_Value (R)

 

 

 

Heating Valve Status

MV 26

Present_Value (R)

 

 

 

Cooling Valve Status

MV 27

Present_Value (R)

 

 

 

Fan Status

MV 28

Present_Value (R)

 

 

 

BI 1 Status

BI 29

Present_Value (R)

 

 

 

BI 2 Status

BI 30

Present_Value (R)

 

 

 

UI 3 Status

BI 31

Present_Value (R)

 

 

 

Local Motion

BI 32

Present_Value (R)

 

 

 

Effective Occupancy

MV 33

Present_Value (R)

 

 

 

 

 

 

Controller Alarms

GRP 34

Present_Value (R)

 

 

 

Window Alarm

BI 35

Present_Value (R)

 

 

 

Filter Alarm

BI 36

Present_Value (R)

 

 

 

Service Alarm

BI 37

Present_Value (R)

 

 

 

 

 

 

Temperature Setpoints

GRP 38

Present_Value (R)

 

 

 

Occupied Heat Setpoint

AV 39

Present_Value (R,W)

 

 

 

Occupied Cool Setpoint

AV 40

Present_Value (R,W)

 

 

 

Stand-by Heat Setpoint

AV 41

Present_Value (R,W)

 

 

 

Stand-by Cool Setpoint

AV 42

Present_Value (R,W)

 

 

 

8

BAS-SVP10A-EN

Image 8
Contents Integration Manual Copyright Table of Contents Objects and Parameters Tracer SC Network Configuration Overview Product DescriptionHow To Information Related DocumentsPlanning Your Integration OverviewSupported BACnet Services Default Device Name and Default Device IDSummary of BACnet Objects BACnet Interoperability Building BlocksFan Coil Objects Summary of BACnet ObjectsX13511541010 and -2010 Rooftop and Heat Pump Models Objects table for fan coilsOutput Configuration Options GRP PresentValue R General Options GRP PresentValue RRooftop and Heat Pump Objects Rooftop and heat pump ungrouped objectsType Rooftop Object Name Instance Object Property 1010 2010Heatpump Model GRP PresentValue R Configuration Options Stages Configuration GRP PresentValue R OptionsEconomizer Model GRP PresentValue R Configuration Options Standard Object Types Supported Standard object types supportedConfiguration Objects for Fan Coils Configuration Objects for Rooftop and Heat Pump UnitsList of Proprietary Properties Proprietary PropertiesList of property value range restrictions BACnet Object PropertiesFan Coil Object Properties Object Name Object ID BACnet Index Text Default value BACnet Object PropertiesList of property enumeration sets for MV objects Table NoteObject Name Object ID BACnet Index Text Default value Function MV58 MV17 Index State Text Index Default ValueMV15 Sequence of Operation values for Note Additional MV valuesFunction MV26 BV75 Value MV52 Index MV27 Object Name State Text IndexHour Hours Rooftop and Heat Pump Object Properties Object Type Under Range Object NameValue Over Range ValueList of property enumeration sets for BI and BV objects Object Type Object Name Instance InactiveText ActiveTextUnder Range Instance Value Over Range ValueObject Name Instance BACnet Index Text Object TypeNone RemNSB DI1 Configuration MV65 RemOVR Filter Service Objects You Can Use in Site Graphics Fan CoilsRooftop and Heat Pump Units Objects You Can Use in Site GraphicsWiring Requirements for Communicating Thermostats BACnet MS/TP Link WiringWiring Requirements for Communicating Thermostats Daisy chain configuration for BACnet wiringProduct Specifications Communicating Thermostat SpecificationsNetwork Adapter DetailsTroubleshooting Causes and solutions for error conditionPossible Cause Solution Communicating Thermostat Status LEDsFan Coils Additional Information and ConsiderationsMS/TP Network Integration Objects and Parameters Additional Information and Considerations Tracer SC Network Configuration No automatic installationNight Purge disabled No priority arrayHeat only/cool only Parameters not supportedInappropriate text on graphic displays No active setpoint or heat/cool mode dataDischarge air temp requirements BAS-SVP10A-EN Template TStatFanCoilTrane Data NormalizationExample Occupancy Request Data Normalization Tracer SC writing to the fan coil Heat Cool Mode RequestReading from fan coil to Tracer SC Heat Cool Mode Request Tracer SC Point name Supply Fan Staged Speed Status Tracer SC writing to the fan coil Fan Mode BASReading from fan coil to tracer SC Fan Mode BAS Template TStatHeatPumpTrane Tracer SC writing to the heat pump Occupancy StatusReading from heat pump to Tracer SC Occupancy Status Tracer SC writing to the heat pump Occupancy RequestTracer SC writing to the heat pump Heat Cool Mode Request Reading from Heat Pump to Tracer SC Heat Cool Mode RequestTemplate TStatRTUTrane Tracer SC writing to the rooftop unit Occupancy StatusTracer SC writing to the rooftop unit Occupancy Request Reading from rooftop unit to Tracer SC Occupancy RequestTrane Communicating Thermostat Points List TStatFanCoilTranePoints Available in the TStatFanCoilTrane Template TStat Device PointTStatHeatPumpTrane Template Trane Communicating Thermostat Points ListPoints Available in the TStatHeatPumpTrane Template Point Type Instance TionTStatRTUTrane Template Points Available in the TStatRTUTrane TemplatePoint Type YesAUX Page

BAS-SVP10A-EN, Trane Communicating Thermostats (BACnet) specifications

The Trane BAS-SVP10A-EN is a part of the Trane Communicating Thermostats series designed to facilitate efficient and effective building temperature control in HVAC systems. These thermostats work with BACnet (Building Automation and Control Network), a widely adopted communication protocol in building automation for networked control of HVAC systems, lighting, access control, and fire systems.

One of the standout features of the Trane BAS-SVP10A-EN is its compatibility with various Trane equipment and other BACnet-compliant devices. This versatility allows for seamless integration into existing building systems, enhancing operational efficiency. The thermostat is designed to support zoning applications, offering precise temperature control to individual areas or rooms, thus significantly improving occupant comfort while also minimizing energy consumption.

The Trane communicating thermostat is built with advanced technologies that ensure optimal performance. It utilizes digital communication, enabling real-time data exchange between the thermostat and the HVAC system. This capability enhances the responsiveness of the HVAC system, allowing it to adjust more accurately to changing environmental conditions. The thermostat features an intuitive interface with a clear display, making it user-friendly for building occupants and facility managers alike.

Another important characteristic is its advanced scheduling capabilities. Users can program customized heating and cooling schedules, promoting energy savings while maintaining comfort levels. Additionally, its remote access feature allows for monitoring and control from smartphones, tablets, or computers, making it convenient for users to manage their HVAC systems from virtually anywhere.

The Trane BAS-SVP10A-EN also boasts robust diagnostic and reporting functions. It can provide feedback on system performance, enabling proactive maintenance and troubleshooting, which increases the reliability of HVAC operations. Overall, the Trane Communicating Thermostat represents a sophisticated solution for modern building management, focusing on comfort, energy efficiency, and ease of integration into existing systems. With its commitment to leveraging cutting-edge technology, Trane continues to lead in providing innovative solutions for heating, ventilation, and air conditioning needs in diverse building environments.