Trane BAS-SVP10A-EN manual List of property enumeration sets for BI and BV objects, Under Range

Page 20

BACnet Object Properties

Table 14. List of property value range restrictions for AI and AV objects (continued)

Object Name

Humidifier Output

Object Type

Under Range

and Instance

Value

AV 101

0%

 

 

Over Range Value

100%

Default Value

N/A

Table 15. List of property enumeration sets for BI and BV objects

 

Object Type

 

 

 

Object Name

and Instance

Inactive_Text

Active_Text

Default Value

Room Temp Override

BV 8

Normal

Override

Normal

 

 

 

 

 

Outdoor Temp Override

BV 10

Normal

Override

Normal

 

 

 

 

 

AUX

BI 24

Off

On

Off

 

 

 

 

 

G Fan

BI 25

Off

On

Off

 

 

 

 

 

Y1 Cool

BI 26

Off

On

Off

 

 

 

 

 

Y2 Cool

BI 27

Off

On

Off

 

 

 

 

 

W1 Heat

BI 28

Off

On

Off

 

 

 

 

 

W2 Heat

BI 29

Off

On

Off

 

 

 

 

 

Reversing Valve

BI 30

Off

On

Off

 

 

 

 

 

DI 1 Status

BI 31

Not Activated

Activated

Not Activated

 

 

 

 

 

DI 2 Status

BI 32

Not Activated

Activated

Not Activated

 

 

 

 

 

Local Motion

BI 33

No Motion

Motion

No Motion

 

 

 

 

 

Frost Alarm

BI 36

Off

On

Off

 

 

 

 

 

Clock Alarm

BI 37

Off

On

Off

 

 

 

 

 

Filter Alarm

BI 38

Off

On

Off

 

 

 

 

 

Service Alarm

BI 39

Off

On

Off

 

 

 

 

 

Fan Lock Alarm

BI 40

Off

On

Off

 

 

 

 

 

Temperature Scale

BV 47

°C

°F

°F

 

 

 

 

 

Frost Protection

BV 55

Off

On

Off

 

 

 

 

 

Aux Contact

BV 56

N.O.

N.C.

N.O.

 

 

 

 

 

Menu Scroll

BV 57

No Scroll

Scroll Active

Scroll Active

 

 

 

 

 

Fan Control

BV 62

Off

On

On

 

 

 

 

 

Fan Purge Delay

BV 64

Off

On

Off

 

 

 

 

 

Progressive Recovery

BV 70

Off

Active

Off

 

 

 

 

 

Mechanical Cooling Enabled

BV 79

Off

On

Off

 

 

 

 

 

Comfort Mode

BV 84

Comfort

Economy

Comfort

 

 

 

 

 

Reversing Valve

BV 85

Normally Cool

Normally Heat

Normally Heat

Energized in

Energized in

Configuration

Energized in Heating

 

Cooling

Cooling

 

 

 

 

 

 

 

 

Compressor Interlock

BV 86

Off

On

Off

 

 

 

 

 

RH Display

BV 88

Disabled

Enabled

Disabled

 

 

 

 

 

Dehumidification Lockout

BV 92

Disabled

Enabled

Enabled

Functions

 

 

 

 

 

 

 

 

 

Dehumidification Output

BI 93

Off

On

N/A

Status

 

 

 

 

 

 

 

 

 

20

BAS-SVP10A-EN

Image 20
Contents Integration Manual Copyright Table of Contents Objects and Parameters Tracer SC Network Configuration Overview Product DescriptionHow To Information Related DocumentsPlanning Your Integration OverviewSupported BACnet Services Default Device Name and Default Device IDSummary of BACnet Objects BACnet Interoperability Building BlocksFan Coil Objects Summary of BACnet ObjectsX13511541010 and -2010 Rooftop and Heat Pump Models Objects table for fan coilsOutput Configuration Options GRP PresentValue R General Options GRP PresentValue RRooftop and Heat Pump Objects Rooftop and heat pump ungrouped objectsType Rooftop Object Name Instance Object Property 1010 2010Heatpump Model GRP PresentValue R Configuration Options Stages Configuration GRP PresentValue R OptionsEconomizer Model GRP PresentValue R Configuration Options Standard Object Types Supported Standard object types supportedConfiguration Objects for Fan Coils Configuration Objects for Rooftop and Heat Pump UnitsList of Proprietary Properties Proprietary PropertiesList of property value range restrictions BACnet Object PropertiesFan Coil Object Properties Object Name Object ID BACnet Index Text Default value BACnet Object PropertiesList of property enumeration sets for MV objects Table NoteObject Name Object ID BACnet Index Text Default value Function MV58 MV17 Index State Text Index Default ValueMV15 Sequence of Operation values for Note Additional MV valuesFunction MV26 BV75 Value MV52 Index MV27 Object Name State Text IndexHour Hours Rooftop and Heat Pump Object Properties Object Type Under Range Object NameValue Over Range ValueList of property enumeration sets for BI and BV objects Object Type Object Name Instance InactiveText ActiveTextUnder Range Instance Value Over Range ValueObject Name Instance BACnet Index Text Object TypeNone RemNSB DI1 Configuration MV65 RemOVR Filter Service Objects You Can Use in Site Graphics Fan CoilsRooftop and Heat Pump Units Objects You Can Use in Site GraphicsWiring Requirements for Communicating Thermostats BACnet MS/TP Link WiringWiring Requirements for Communicating Thermostats Daisy chain configuration for BACnet wiringProduct Specifications Communicating Thermostat SpecificationsNetwork Adapter DetailsTroubleshooting Causes and solutions for error conditionPossible Cause Solution Communicating Thermostat Status LEDsFan Coils Additional Information and ConsiderationsMS/TP Network Integration Objects and Parameters Additional Information and Considerations Tracer SC Network Configuration No automatic installationNight Purge disabled No priority arrayHeat only/cool only Parameters not supportedInappropriate text on graphic displays No active setpoint or heat/cool mode dataDischarge air temp requirements BAS-SVP10A-EN Template TStatFanCoilTrane Data NormalizationExample Occupancy Request Data Normalization Tracer SC writing to the fan coil Heat Cool Mode RequestReading from fan coil to Tracer SC Heat Cool Mode Request Tracer SC Point name Supply Fan Staged Speed Status Tracer SC writing to the fan coil Fan Mode BASReading from fan coil to tracer SC Fan Mode BAS Template TStatHeatPumpTrane Tracer SC writing to the heat pump Occupancy StatusReading from heat pump to Tracer SC Occupancy Status Tracer SC writing to the heat pump Occupancy RequestTracer SC writing to the heat pump Heat Cool Mode Request Reading from Heat Pump to Tracer SC Heat Cool Mode RequestTemplate TStatRTUTrane Tracer SC writing to the rooftop unit Occupancy StatusTracer SC writing to the rooftop unit Occupancy Request Reading from rooftop unit to Tracer SC Occupancy RequestTrane Communicating Thermostat Points List TStatFanCoilTranePoints Available in the TStatFanCoilTrane Template TStat Device PointTStatHeatPumpTrane Template Trane Communicating Thermostat Points ListPoints Available in the TStatHeatPumpTrane Template Point Type Instance TionTStatRTUTrane Template Points Available in the TStatRTUTrane TemplatePoint Type YesAUX Page

BAS-SVP10A-EN, Trane Communicating Thermostats (BACnet) specifications

The Trane BAS-SVP10A-EN is a part of the Trane Communicating Thermostats series designed to facilitate efficient and effective building temperature control in HVAC systems. These thermostats work with BACnet (Building Automation and Control Network), a widely adopted communication protocol in building automation for networked control of HVAC systems, lighting, access control, and fire systems.

One of the standout features of the Trane BAS-SVP10A-EN is its compatibility with various Trane equipment and other BACnet-compliant devices. This versatility allows for seamless integration into existing building systems, enhancing operational efficiency. The thermostat is designed to support zoning applications, offering precise temperature control to individual areas or rooms, thus significantly improving occupant comfort while also minimizing energy consumption.

The Trane communicating thermostat is built with advanced technologies that ensure optimal performance. It utilizes digital communication, enabling real-time data exchange between the thermostat and the HVAC system. This capability enhances the responsiveness of the HVAC system, allowing it to adjust more accurately to changing environmental conditions. The thermostat features an intuitive interface with a clear display, making it user-friendly for building occupants and facility managers alike.

Another important characteristic is its advanced scheduling capabilities. Users can program customized heating and cooling schedules, promoting energy savings while maintaining comfort levels. Additionally, its remote access feature allows for monitoring and control from smartphones, tablets, or computers, making it convenient for users to manage their HVAC systems from virtually anywhere.

The Trane BAS-SVP10A-EN also boasts robust diagnostic and reporting functions. It can provide feedback on system performance, enabling proactive maintenance and troubleshooting, which increases the reliability of HVAC operations. Overall, the Trane Communicating Thermostat represents a sophisticated solution for modern building management, focusing on comfort, energy efficiency, and ease of integration into existing systems. With its commitment to leveraging cutting-edge technology, Trane continues to lead in providing innovative solutions for heating, ventilation, and air conditioning needs in diverse building environments.