Trane Trane Communicating Thermostats (BACnet) Stages Configuration GRP PresentValue R Options

Page 11

Summary of BACnet Objects

Table 3. Rooftop and heat pump ungrouped objects

 

 

 

 

 

Dehumidifi-

 

Type and

 

Rooftop

Heat Pump

cation

Object Name

Instance

Object Property

-1010

-2010

-1050

Cooling CPH

MV 54

Present_Value (R,W)

 

 

 

 

 

 

Frost Protection

BV 55

Present_Value (R,W)

 

 

 

 

 

 

Aux Contact

BV 56

Present_Value (R,W)

 

 

 

 

 

 

Menu Scroll

BV 57

Present_Value (R,W)

 

 

 

 

 

 

General Options 2-

GRP 58

Present_Value (R)

 

 

 

 

 

 

Password Value

AV 59

Present_Value (R,W)

 

 

 

 

 

 

Power-up Delay

AV 60

Present_Value (R,W)

 

 

 

 

 

 

Temporary Occupancy

MV 61

Present_Value (R,W)

Time

 

 

 

 

 

 

 

 

 

 

 

Fan Control

BV 62

Present_Value (R,W)

 

 

 

 

 

 

Anticycle

MV 63

Present_Value (R,W)

 

 

 

 

 

 

Fan Purge Delay

BV 64

Present_Value (R,W)

 

 

 

 

 

 

DI 1 Configuration

MV 65

Present_Value (R,W)

 

 

 

 

 

 

DI 2 Configuration

MV 66

Present_Value (R,W)

 

 

 

 

 

 

 

Proportional Band

MV 67

Present_Value (R,W)

 

 

 

 

 

 

Unoccupied Time

AV 68

Present_Value (R,W)

 

 

 

 

 

 

Stages Configuration

GRP 72

Present_Value (R)

 

 

Options

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating Stages

MV 73

Present_Value (R,W)

 

 

 

 

 

 

 

Cooling Stages

MV 74

Present_Value (R,W)

 

 

 

 

 

 

 

Heatpump Stages

MV 75

Present_Value (R,W)

 

 

 

 

 

 

 

 

Economizer Model

GRP 76

Present_Value (R)

 

 

Configuration Options

 

 

 

 

 

 

 

 

 

 

 

 

 

Economizer Changeover

AV 77

Present_Value (R,W)

 

 

Setpoint

 

 

 

 

 

 

 

 

 

 

 

 

 

Economizer Minimum

AV 78

Present_Value (R,W)

 

 

Position

 

 

 

 

 

 

 

 

 

 

 

 

 

Mechanical Cooling

BV 79

Present_Value (R,W)

 

 

Enabled

 

 

 

 

 

 

 

 

 

 

 

 

 

Mixed Air Setpoint

AV 80

Present_Value (R,W)

 

 

 

 

 

 

 

 

Heatpump Model

GRP 81

Present_Value (R)

 

Configuration Options

 

 

 

 

 

 

 

 

 

 

 

High Balance Point

AV 82

Present_Value (R,W)

 

 

 

 

 

 

 

Low Balance Point

AV 83

Present_Value (R,W)

 

 

 

 

 

 

 

Comfort Mode

BV 84

Present_Value (R,W)

 

 

 

 

 

 

 

Reversing Valve

BV 85

Present_Value (R,W)

 

 

Configuration

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Interlock

BV 86

Present_Value (R,W)

 

 

 

 

 

 

 

 

Dehumidification Model

GRP 87

Present_Value (R)

 

 

Configuration Options

 

 

 

 

 

RH Display

BV 88

Present_Value (R,W)

 

 

 

 

 

 

 

 

Dehumidification RH

AV 89

Present_Value (R,W)

 

 

Setpoint

 

 

 

 

 

 

 

 

 

 

 

 

 

Dehumidification

AV 90

Present_Value (R,W)

 

 

Hysterisys

 

 

 

 

 

 

 

 

 

 

 

 

 

Dehumidification Low OA

AV 91

Present_Value (R,W)

 

 

Lockout

 

 

 

 

 

 

 

 

 

 

 

 

 

Dehumidification Lockout

BV 92

Present_Value (R,W)

 

 

Functions

 

 

 

 

 

 

 

 

 

 

 

 

 

Dehumidification Output

BI 93

Present_Value (R)

 

 

Status

 

 

 

 

 

 

 

 

 

 

 

 

 

Humidification Model

GRP 94

Present_Value (R)

 

 

Configuration Options

 

 

 

 

 

 

 

 

 

 

 

 

 

Humidification RH Setpoint

AV 95

Present_Value (R,W)

 

 

 

 

 

 

 

 

BAS-SVP10A-EN

11

Image 11
Contents Integration Manual Copyright Table of Contents Objects and Parameters Tracer SC Network Configuration Product Description OverviewOverview How To InformationRelated Documents Planning Your IntegrationBACnet Interoperability Building Blocks Supported BACnet ServicesDefault Device Name and Default Device ID Summary of BACnet ObjectsObjects table for fan coils Fan Coil ObjectsSummary of BACnet Objects X13511541010 and -2010 Rooftop and Heat Pump ModelsGeneral Options GRP PresentValue R Output Configuration Options GRP PresentValue RObject Name Instance Object Property 1010 2010 Rooftop and Heat Pump ObjectsRooftop and heat pump ungrouped objects Type RooftopHeatpump Model GRP PresentValue R Configuration Options Stages Configuration GRP PresentValue R OptionsEconomizer Model GRP PresentValue R Configuration Options Standard object types supported Standard Object Types SupportedProprietary Properties Configuration Objects for Fan CoilsConfiguration Objects for Rooftop and Heat Pump Units List of Proprietary PropertiesList of property value range restrictions BACnet Object PropertiesFan Coil Object Properties Table Note Object Name Object ID BACnet Index Text Default valueBACnet Object Properties List of property enumeration sets for MV objectsAdditional MV values Object Name Object ID BACnet Index Text Default valueFunction MV58 MV17 Index State Text Index Default Value MV15 Sequence of Operation values for NoteMV27 Object Name State Text Index Function MV26 BV75 Value MV52 IndexHour Hours Over Range Value Rooftop and Heat Pump Object PropertiesObject Type Under Range Object Name ValueInstance Value Over Range Value List of property enumeration sets for BI and BV objectsObject Type Object Name Instance InactiveText ActiveText Under RangeObject Type Object Name Instance BACnet Index TextNone RemNSB DI1 Configuration MV65 RemOVR Filter Service Fan Coils Objects You Can Use in Site GraphicsObjects You Can Use in Site Graphics Rooftop and Heat Pump UnitsBACnet MS/TP Link Wiring Wiring Requirements for Communicating ThermostatsDaisy chain configuration for BACnet wiring Wiring Requirements for Communicating ThermostatsDetails Product SpecificationsCommunicating Thermostat Specifications Network AdapterCommunicating Thermostat Status LEDs TroubleshootingCauses and solutions for error condition Possible Cause SolutionFan Coils Additional Information and ConsiderationsMS/TP Network Integration Objects and Parameters Additional Information and Considerations No priority array Tracer SC Network ConfigurationNo automatic installation Night Purge disabledParameters not supported Heat only/cool onlyInappropriate text on graphic displays No active setpoint or heat/cool mode dataDischarge air temp requirements BAS-SVP10A-EN Template TStatFanCoilTrane Data NormalizationExample Occupancy Request Data Normalization Tracer SC writing to the fan coil Heat Cool Mode RequestReading from fan coil to Tracer SC Heat Cool Mode Request Tracer SC Point name Supply Fan Staged Speed Status Tracer SC writing to the fan coil Fan Mode BASReading from fan coil to tracer SC Fan Mode BAS Tracer SC writing to the heat pump Occupancy Request Template TStatHeatPumpTraneTracer SC writing to the heat pump Occupancy Status Reading from heat pump to Tracer SC Occupancy StatusTracer SC writing to the rooftop unit Occupancy Status Tracer SC writing to the heat pump Heat Cool Mode RequestReading from Heat Pump to Tracer SC Heat Cool Mode Request Template TStatRTUTraneReading from rooftop unit to Tracer SC Occupancy Request Tracer SC writing to the rooftop unit Occupancy RequestTStat Device Point Trane Communicating Thermostat Points ListTStatFanCoilTrane Points Available in the TStatFanCoilTrane TemplatePoint Type Instance Tion TStatHeatPumpTrane TemplateTrane Communicating Thermostat Points List Points Available in the TStatHeatPumpTrane TemplateYes TStatRTUTrane TemplatePoints Available in the TStatRTUTrane Template Point TypeAUX Page

BAS-SVP10A-EN, Trane Communicating Thermostats (BACnet) specifications

The Trane BAS-SVP10A-EN is a part of the Trane Communicating Thermostats series designed to facilitate efficient and effective building temperature control in HVAC systems. These thermostats work with BACnet (Building Automation and Control Network), a widely adopted communication protocol in building automation for networked control of HVAC systems, lighting, access control, and fire systems.

One of the standout features of the Trane BAS-SVP10A-EN is its compatibility with various Trane equipment and other BACnet-compliant devices. This versatility allows for seamless integration into existing building systems, enhancing operational efficiency. The thermostat is designed to support zoning applications, offering precise temperature control to individual areas or rooms, thus significantly improving occupant comfort while also minimizing energy consumption.

The Trane communicating thermostat is built with advanced technologies that ensure optimal performance. It utilizes digital communication, enabling real-time data exchange between the thermostat and the HVAC system. This capability enhances the responsiveness of the HVAC system, allowing it to adjust more accurately to changing environmental conditions. The thermostat features an intuitive interface with a clear display, making it user-friendly for building occupants and facility managers alike.

Another important characteristic is its advanced scheduling capabilities. Users can program customized heating and cooling schedules, promoting energy savings while maintaining comfort levels. Additionally, its remote access feature allows for monitoring and control from smartphones, tablets, or computers, making it convenient for users to manage their HVAC systems from virtually anywhere.

The Trane BAS-SVP10A-EN also boasts robust diagnostic and reporting functions. It can provide feedback on system performance, enabling proactive maintenance and troubleshooting, which increases the reliability of HVAC operations. Overall, the Trane Communicating Thermostat represents a sophisticated solution for modern building management, focusing on comfort, energy efficiency, and ease of integration into existing systems. With its commitment to leveraging cutting-edge technology, Trane continues to lead in providing innovative solutions for heating, ventilation, and air conditioning needs in diverse building environments.