LG Electronics 395CAV installation instructions Unconfined Space, Confined Space, Ð4Ð

Page 4

CAUTION: Air for combustion must not be contami- nated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.

SUPPLY

AIR

VENT THROUGH ROOF

All fuel-burning equipment must be supplied with air for combus- tion of the fuel. Sufficient air MUST be provided to ensure there will not be a negative pressure in the equipment room or space. In addition, a positive seal MUST be made between the furnace cabinet and the return-air duct to prevent pulling air from the burner area and draft safeguard opening.

CAUTION: The operation of exhaust fans, kitchen ven- tilation fans, clothes dryers, or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make-up air MUST BE PROVIDED for the ventilation devices, in addition to that required by the furnace.

The requirements for combustion and ventilation air depend upon whether the furnace is located in an unconfined or confined space.

A.Unconfined Space

An unconfined space must have at least 50 cubic ft for each 1000 Btuh of input for all the appliances (such as furnaces, clothes dryer, water heaters, etc.) in the space.

For Example:

395CAV FURNACE

MINIMUM SQ FT WITH

INPUT BTUH

7-1/2 FT CEILING

44,000

293

66,000

440

88,000

587

110,000

733

132,000

880

154,000

1026

If the unconfined space is constructed unusually tight, air for combustion and ventilation MUST come from either the outdoors or spaces freely communicating with the outdoors. Combustion and ventilation openings must be sized the same as for a confined space. A minimum opening with a total of at least 1 sq in. per 5000 Btuh of total input rating for all equipment must be provided. Return air must not be taken from the room unless an equal or greater amount of air is supplied to the room.

B.Confined Space

A confined space has volume less than 50 cu ft per 1000 Btuh of the total input rating for all appliances installed in that space. A confined space MUST have 2 permanent openings, 1 within 12 in. of the ceiling and the other within 12 in. of the floor. (See Fig. 2.)

NOTE: In determining the free area of an opening, the blocking effect of the louvers, grilles, and screens must be considered. If the free area of a louver or grille design is unknown, it may be assumed that wood louvers have a 20 percent free area, and metal louvers or grilles have a 60 percent free area. Screens, when used, must not be smaller than 1/4-in. mesh. Louvers and grilles must be constructed so they cannot be closed.

The size of the openings depends upon whether the air comes from inside or outside of the structure.

1.All air from inside the structure:

a.Each opening MUST have at least 1 sq in. of free area per 1000 Btuh of the total input for all equipment within the confined space, but not less than 100 sq in. per opening. (See Fig. 2.)

Ð4Ð

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

MAX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IN.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 SQ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PER 1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONFINED SPACE

 

BTUH* IN DOOR

 

 

 

 

 

 

 

 

 

 

 

 

OR WALL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INTERIOR

 

 

 

 

 

 

 

 

 

 

UNCONFINED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPACE

 

HEATED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPACE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6MIN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(FRONT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 SQ IN.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PER 1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BTUH* IN DOOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OR WALL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12MAX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RETURN AIR

*Minimum opening size is 100 square in. with minimum dimensions of 3-In.

Minimum of 3-In. when type-B1 vent is used.

A89012

Fig. 2ÐAir For Combustion and Ventilation (Inside Air)

For Example:

395CAV FURNACE

FREE AREA PER OPENING

INPUT BTUH

(SQ IN.)

44,000

100

66,000

100

88,000

100

110,000

110

132,000

132

154,000

154

b. If the building is constructed unusually tight, a perma- nent opening directly communicating with the outdoors should be provided. This opening shall have a minimum free area of 1 sq in. per 5000 Btuh of total input rating for all equipment in the enclosure.

c. If the furnace is installed on a raised platform to provide a return-air plenum, and return air is taken directly from the hallway or space adjacent to the furnace, all air for combustion must come from outdoors.

2. All air from outside the structure:

a. If combustion air is taken from outdoors through vertical ducts, the openings and ducts MUST have at least 1 sq in. of free area per 4000 Btuh of the total input for all equipment within the confined space. (See Fig. 3.)

b. If combustion air is taken from the outdoors through horizontal ducts, the openings and ducts MUST have at least 1 sq in. of free area per 2000 Btuh of the total input for all equipment within the confined space.

Image 4
Contents Electrostatic Discharge ESD Precautions Safety ConsiderationsÐ1Ð Ðminimum Clearances from Combustible MaterialsÐdimensions Electrostatic Discharge ESD Precautions ProcedureÐ2Ð Unit Size Vent Conn SHIP. WT LBLocation IntroductionII. AIR for Combustion and Ventilation Unconfined Space Confined SpaceÐ4Ð 395CAV Furnace Minimum SQ FT with Input Btuh 2 FT CeilingIII. Filter Arrangement Ð5ÐIV. Leveling Legs if Required Ðfilter Information GAS PipingÐ6Ð Ðmaximum Capacity of PipeWiring AccessoriesVIII. START-UP, ADJUSTMENT, and Safety Check VI. Electrical ConnectionsÐ8Ð Ðelectrical DataSequence of Operation ÐControl Board Ð9Ð→ ÐUnit Wiring Diagram PCBStart-up Procedures AdjustmentsGAS Specific Gravity of Natural GAS Heat Value ExampleBTU/CU FT Ðgas Rate CU FT/HR → ÐRedundant Automatic Gas Control ValveÐcanadian Orifice Size GAS SEA Level High AltitudeÐspeed Selector ChecklistColor Speed Factory Attached to Service Training Ð16Ð