LG Electronics 395CAV Ðfilter Information, GAS Piping, Ð6Ð, Ðmaximum Capacity of Pipe

Page 6

1712-IN. WIDE CASINGS ONLY:

INSTALL FIELD-SUPPLIED FILTER FILLER STRIP UNDER FILTER.

3

24 1/2

1

2412-IN. WIDE CASINGS ONLY: CUT AND FOLD FACTORY-PROVIDED FILTERS AS SHOWN TO DESIRED SIZE.

516

134

516

516

1 34

516

1 34 1 34

WASHABLE

FILTER

 

FILTER

FILTER

 

 

 

 

RETAINER

 

 

SUPPORT

 

 

 

 

 

 

 

 

 

 

 

A96030

Fig. 5ÐBottom Filter Arrangement

 

(Control Removed for Clarity)

 

TABLE 3ÐFILTER INFORMATION (IN.)

 

 

 

 

 

 

 

 

FURNACE

FILTER SIZE*

 

 

 

FILTER TYPE

CASING WIDTH

Side Return

Bottom Return

 

 

 

 

 

 

 

 

 

14-3/16

(1) 16 X 25 X 1²

(1) 14

X 25 X 1

 

Cleanable

17-1/2

(1) 16 X 25 X 1²

(1) 16

X 25

X 1

 

Cleanable

21

(1) 16 X 25 X 1

(1) 20

X 25

X 1²

 

Cleanable

24-1/2

(2) 16 X 25 X 1²

(1) 24

X 25

X 1

 

Cleanable

 

 

 

 

 

 

 

*Filters can be field modified by cutting the frame as marked and folding to the desired size. Alternate sizes can be ordered from your distributor or dealer. ² Factory-provided with the furnace.

4.Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.

V.GAS PIPING

Gas piping must be installed in accordance with national and local codes. Refer to the current edition of the NFGC. Canadian installations must be installed in accordance with NSCNGPIC and all authorities having jurisdiction.

Refer to Table 4 for the recommended gas pipe size. Risers must be used to connect to the furnace and the meter.

Ð6Ð

 

 

 

 

 

 

A89014

Fig. 6ÐLeveling Leg Installation

 

 

 

TABLE 4ÐMAXIMUM CAPACITY OF PIPE*

 

 

 

 

 

 

 

 

 

NOMINAL IRON

INTERNAL

LENGTH OF PIPE (FT)

PIPE SIZE

DIAMETER

 

 

 

 

 

 

10

20

30

40

 

50

(IN.)

(IN.)

 

1/2

0.622

175

120

97

82

 

73

3/4

0.824

360

250

200

170

 

151

1

1.049

680

465

375

320

 

285

1-1/4

1.380

1400

950

770

660

 

580

1-1/2

1.610

2100

1460

1180

990

 

900

*Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table 10-2 NFPA 54-1992.

CAUTION: If a flexible connector is required or al- lowed by the authority having jurisdiction, black iron pipe shall be installed at the gas valve and extend a minimum of 2 in. outside the furnace casing.

Piping should be pressure tested in accordance with local and national plumbing and gas codes before the furnace has been attached. If the pressure exceeds 0.5 psig (14-in. wc), the gas supply pipe must be disconnected from the furnace and capped before the pressure test. If the test pressure is equal to or less than 0.5 psig (14-in. wc), turn off electric shutoff switch located on the gas valve before the test. It is recommended that the ground joint union be loosened before pressure testing. After all connections have been made, purge the lines and check for leakage with regulated gas supply pressure.

Install a sediment trap in the riser leading to the furnace. The trap can be installed by connecting a tee to the riser leading from the furnace. Connect a capped nipple into the lower end of the tee. The capped nipple should extend below the level of the gas controls. (See Fig. 7.)

Apply joint compound (pipe dope) sparingly and only to the male threads of each joint. The compound must be resistant to the action of propane gas.

An accessible manual shutoff valve MUST be installed upstream of the furnace gas controls and within 72 in. of the furnace. A 1/8-in. NPT plugged tapping, accessible for test gage connection, MUST be installed immediately upstream of the gas supply connection to the furnace and downstream of the manual shutoff valve. Place ground joint union between the gas control manifold and the manual shutoff valve.

Image 6
Contents Ð1Ð Electrostatic Discharge ESD PrecautionsSafety Considerations Ðminimum Clearances from Combustible MaterialsÐ2Ð ÐdimensionsElectrostatic Discharge ESD Precautions Procedure Unit Size Vent Conn SHIP. WT LBIntroduction LocationII. AIR for Combustion and Ventilation Ð4Ð Unconfined SpaceConfined Space 395CAV Furnace Minimum SQ FT with Input Btuh 2 FT CeilingÐ5Ð III. Filter ArrangementIV. Leveling Legs if Required Ð6Ð Ðfilter InformationGAS Piping Ðmaximum Capacity of PipeVIII. START-UP, ADJUSTMENT, and Safety Check WiringAccessories VI. Electrical ConnectionsÐelectrical Data Ð8ÐSequence of Operation ÐControl Board Ð9Ð→ ÐUnit Wiring Diagram PCBStart-up Procedures AdjustmentsExample GAS Specific Gravity of Natural GAS Heat ValueBTU/CU FT Ðcanadian Orifice Size Ðgas Rate CU FT/HR→ ÐRedundant Automatic Gas Control Valve GAS SEA Level High AltitudeChecklist Ðspeed SelectorColor Speed Factory Attached to Service Training Ð16Ð