TABLE 9ÐSPEED SELECTOR
COLOR | SPEED | FACTORY- | |
ATTACHED TO | |||
|
| ||
Black | High | Cool | |
Yellow (When | Spare | ||
present) | |||
|
| ||
Blue | Heat | ||
Red | Low | Spare | |
White | Common | COM | |
|
|
|
3.Set thermostat heat anticipator.
The thermostat heat anticipator must be set to match the amp draw of the electrical components in the
NOTE: When using an electronic thermostat, set the cycle rate for 3 cycles per hr.
THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
VOLT/AMMETER
R Y W G
10 TURNS
FROM UNIT
TERMINAL BLOCK
EXAMPLE: | 5.0 AMPS ON AMMETER | = 0.5 AMPS FOR THERMOSTAT SETTING |
| 10 TURNS AROUND JAWS |
A80201
Fig. 14ÐAmp Draw Check With Ammeter
E.Check Safety Controls
The flame sensor, gas valve, and pressure switch were all checked in the
1.Check primary limit control.
This control shuts off the combustion control system and energizes the
The preferred method of checking the limit control is to gradually block off the return air after the furnace has been operating for a period of at least 5 minutes. As soon as the limit has shut off the burners, the
2.Check draft safeguard switch.
The purpose of this control is to permit the safe shutdown of the furnace during certain blocked vent conditions.
a.Disconnect power to furnace and remove vent connector from furnace outlet collar. Be sure to allow time for vent pipe to cool down before removing.
b.Restore power to furnace and set room thermostat above room temperature.
c.After normal
d.Remove blockage and reconnect vent pipe to furnace outlet collar.
e.Wait 5 minutes and then reset draft safeguard switch.
3.Check pressure switch.
This control proves operation of draft inducer blower.
a.Turn off
b.Remove control door and disconnect inducer motor lead wires from wire harness.
c.Turn on
d.Set thermostat to "call for heat" and wait 1 minute. When pressure switch is functioning properly, hot surface ignitor should NOT glow and control center diagnostic light flashes a 31 fault. If hot surface ignitor glows when inducer motor is disconnected, shut down furnace im- mediately. Determine reason pressure switch did not function properly and correct condition.
e.Turn off
f.Reconnect inducer motor wires, replace control door, and turn on
F.Checklist
1.Put away tools, instruments, and clean up debris.
2.Verify manual reset switches have continuity.
3.Ensure blower and control access doors are properly in- stalled.
4.Cycle test furnace with room thermostat.
5.Check operation of accessories per manufacturer's instruc- tions.
6.Review User's Manual with owner.
7.Leave literature packet near furnace.,
Ð14Ð