LG Electronics 395CAV Ð5Ð, III. Filter Arrangement, IV. Leveling Legs if Required

Page 5

For Example:

395CAV FURNACE

FREE AREA PER OPENING

ROUND PIPE

INPUT BTUH

(SQ IN.)

(IN. DIA)

44,000

11.0

4

66,000

16.5

5

88,000

22.0

6

110,000

27.5

6

132,000

33.0

7

154,000

38.5

7

 

 

 

For Example:

395CAV FURNACE

FREE AREA PER OPENING

ROUND PIPE

INPUT BTUH

(SQ IN.)

(IN. DIA)

44,000

22.0

6

66,000

33.0

7

88,000

44.0

8

110,000

55.0

9

132,000

66.0

10

154,000

77.0

10

c.When ducts are used, they must be of the same cross- sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular ducts must not be less than 3 in. (See Fig. 3.)

 

 

 

 

1 SQ IN.

 

DUCTS

 

 

PER 4000

 

 

 

BTUH*

 

TO

 

 

 

 

 

 

 

OUTDOORS

 

 

 

12MAX

 

D

 

12

1 SQ IN.

 

VENT

 

MAX

A

 

 

PER 2000

THROUGH

F

BTUH*

SUPPLY

ROOF

 

1 SQ IN.

 

AIR

 

 

 

 

 

 

PER

 

 

 

 

4000

 

 

 

 

BTUH*

DUCTS

 

CONFINED

SPACE

OUTDOORS

TO

 

OUTDOORS

 

 

 

 

 

 

 

1 SQ IN.

 

 

 

 

PER

 

 

 

 

4000

1 SQ IN.

 

 

 

BTUH*

B

 

E

G

PER 2000

 

BTUH*

 

 

 

12

 

C

 

MAX

12 MAX

 

 

 

 

 

 

12MAX

RETURN AIR

DUCT

1 SQ IN.

 

 

 

 

TO

 

PER 4000

 

 

OUTDOORS

BTUH*

*Minimum dimensions of 3-In.

NOTE: Use any of the following combinations of openings:

A & B C & D D & E F & G

A89013

Fig. 3ÐAir For Combustion and Ventilation

(Outside Air)

Ð5Ð

WARNING: Do not install the furnace on its back; safety control operation will be adversely affected. Never connect return-air ducts to the back of the furnace. A failure to follow this warning can cause a fire, personal injury, or death.

III.FILTER ARRANGEMENT

The factory-supplied filter(s) is shipped in the blower compart- ment. Determine location for the filter and relocate filter retaining wire if necessary. See Fig. 4 for side return application and Fig. 5 for bottom return application. See Table 3 to determine correct filter size for desired filter location. Table 3 indicates filter size, location, and quantity shipped with the furnace.

WASHABLE

FILTER

FILTER

RETAINER

A93045

Fig. 4ÐSide Filter Arrangement (Control Removed for Clarity)

For bottom air-return applications, filter may need to be cut to fit some furnace casing widths. A bottom closure panel is factory installed in the bottom of the furnace. When bottom return inlet is desired, remove and discard the bottom closure panel. Remove side clip(s) and install in hole. Two sets of hardware are needed for furnaces in 24-1/2-in. wide casings using 2 filters for bottom return. All hardware is provided for filter installation.

NOTE: Furnaces with a 17-1/2-in. wide casing require an addi- tional procedure when locating the filter for bottom return-air application. Field fabricate a sheet metal filler strip 1 X 3 X 24-1/2 in. and install it along side of the filter as shown in Fig. 5. Drive 2 screws through the casing side and into the filler strip to secure it in place. Filter should rest on the top of the filler strip when installed.

WARNING: Never operate unit without a filter or with filter access door removed. Failure to follow this warning can cause fire, personal injury, or death.

IV. LEVELING LEGS (IF REQUIRED)

When the furnace is used with side inlet(s) and leveling legs are required, refer to Fig. 6, and install field-supplied, corrosion- resistant 5/16-in. machine bolts and nuts.

NOTE: The maximum length of the bolt should not exceed 1-1/2 in.

1.Lay furnace on its back. Locate and drill 5/16-in. diameter hole in each bottom corner of furnace as shown in Fig. 6.

2.Install nut on bolt and install bolt and nut in hole. (Install flat washer if desired.)

3.Install another nut on other side of furnace base. (Install flat washer if desired.)

Image 5
Contents Safety Considerations Electrostatic Discharge ESD PrecautionsÐ1Ð Ðminimum Clearances from Combustible MaterialsElectrostatic Discharge ESD Precautions Procedure ÐdimensionsÐ2Ð Unit Size Vent Conn SHIP. WT LBII. AIR for Combustion and Ventilation IntroductionLocation Confined Space Unconfined SpaceÐ4Ð 395CAV Furnace Minimum SQ FT with Input Btuh 2 FT CeilingIV. Leveling Legs if Required Ð5ÐIII. Filter Arrangement GAS Piping Ðfilter InformationÐ6Ð Ðmaximum Capacity of PipeAccessories WiringVIII. START-UP, ADJUSTMENT, and Safety Check VI. Electrical ConnectionsSequence of Operation Ðelectrical DataÐ8Ð Ð9Ð ÐControl BoardPCB → ÐUnit Wiring DiagramAdjustments Start-up ProceduresBTU/CU FT ExampleGAS Specific Gravity of Natural GAS Heat Value → ÐRedundant Automatic Gas Control Valve Ðgas Rate CU FT/HRÐcanadian Orifice Size GAS SEA Level High AltitudeColor Speed Factory Attached to ChecklistÐspeed Selector Service Training Ð16Ð