Indoor Drain Kit Installation

The internal drain is installed on the bottom of the wall sleeve when it is required to drain the condensate into a drain system inside of the building.

The components of the wall sleeve drain kit are shown in Detail A. Use components C (2), D, E, mounting screws (6) and the Outdoor drain fitting.

1.The components D, E, and drain fitting of the kit are mounted on the bottom of the wall sleeve prior to the installation of the sleeve. It may be located in a feasible area on the bottom of the sleeve which is inside of the room except when a subbase is used. When a subbase is installed, the drain may be a minimum of 3 1/2 " from the front flange of the wall sleeve. The minimum clearance should provide adequate clearance for the subbase, see Figures 46 and 47.

2.Cut out the template in the lower right hand corner of these instructions to locate the field drilled holes. (Two to mount the plate and one for the Outdoor drain fitting). See Detail A on how the components have to be installed after the holes are drilled in the bottom of the wall sleeve. If the drain fitting is not connected to an indoor drainage system immediately after the wall sleeve is installed, it must be plugged with a cork to prevent indoor water damage in case it rains.

An indoor tube or hose (furnished by others) must be installed on the drain fitting and interconnected to the drain system inside of the building.

Install the two blank-off plates C and gaskets A on the outdoor portion of the wall sleeve as shown in Figure 46. These components may be installed after the sleeve is secured in the wall opening just prior to the installation of the condenser grille and chassis.

Figure 47

Leveling Legs

Part No: AYLL101

Description

Leveling legs are designed to provide extra front support and leveling of the wall sleeve. Two leg assemblies are required per unit and are provided in each kit. Four screws are also provided with each kit for attachment to the wall

sleeve. See Figure 48.

The leveling legs must be installed before the chassis is installed, but after the wall sleeve is in place.

Holes must be drilled in each side of the wall sleeve, below the duct package holes, for attachment to the wall sleeve.

Receiving

Compare kit identification number with sales order to ensure that the correct kit has been received.

Inspect the leveling legs for shipping damage. File damage claims with the delivering carrier immediately.

Installation

The installation and servicing of this equipment should be performed by qualified, experienced technicians.

WARNING

Hazardous Voltage!

Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.

Important Note:

The unit OFF switch does not disconnect all electrical power to this unit.

Checklist

The following is an abbreviated guide to leveling leg installation. Refer to appropriate areas for more detailed information.

Copyright ©2008 LG Electronics. Inc. All right reserved.

- 31 -

Only for training and service purposes

LGE Internal Use Only

 

Image 31
Contents SVC Manual Model LP121CEM-Y8 SpecificationSleeve and the Rear Grille Features and BenefitsQuick Heater Recovery Door Switch/Occupancy SensorOutdoor Air Temperature Switchover Temperature limitsCooling only Model Control LocationsOperation Electric Heating Model VentilationAdditional Controls Temperature LimitingAdditional Controls Removing the Front GrilleRemote Wall Thermostat REMOTE/LOCAL ControlEnergy Saver Front Desk ControlMechanical Parts Disassembly InstructionsFront Grille Control BOX Electric Heater Electric Heater Model only AIR Handling PartsAxial FAN Cross Flow FANCompressor Electrical PartsShroud Outdoor Motor6 P.C.B Power CordCapillary Tube Refrigeration CycleCondenser EvaporatorLGE Internal Use Only Pulling Vacuum Dimension of sleeve assembly optional InstallationHOW to Install the Unit Dimension of air conditionerWall Case Installation Data Wall Sleeve InstallationGeneral Preparation of the Front Grille Installation of Wall Case in Wall OpeningPreparation of the Wall Case for All Types of Construction LGE Internal Use Only Sub-Base Connected Unit Installation 208, 230, and 208/230 Volt Units Electrical SafetyElectrical Requirements Electrical Data for 230/208V ModelDescription Field Installed AccessoriesInstallation Control Panel Key LockHazardous Voltage Condensate Disposal Pump Kit InstallationPlace the top cover assembly back into the unit Spraying Architectural Grille Architecture Grille Aluminum Single PackCondensate Drain kit Drain InstallationOutdoor Drain Kit Installation Outdoor Drain Kit InstallationChecklist Indoor Drain Kit InstallationLeveling Legs Leveling Leg Assembly Installation on Wall Sleeve Leveling Leg AssemblyJunction Box Kit Installation and Wiring Procedure Hard Wire KitUse Copper Conductors Only Volt Units 208/230 Volt UnitsStandard Escutcheon Remote Escutcheon KitSubbase Part/Location Identification Outside Dimensions Troubleshooting GuidePiping System Troubleshooting Guide Fails to Start Complaint Cause Remedy 208/230V 187V 253V Room AIR Conditioner Voltage LimitsComplaint Cause Remedy CN-IDPT Piping DiagramsPart A, there are 3 types Schematic Diagram435300B Exploded ViewEnlarged picture Condenser Outdoor Service Replacement ProcedureFebruary