COMPLAINT

CAUSE

REMEDY

 

 

 

Compressor cycles

Voltage

Check the voltage. See the limits on the preced-

on overload.

 

ing page. If not within limits, call an electrician.

 

 

 

 

Overload

Check overload, if externally mounted.

 

 

Replace if open. (If the compressor temperature

 

 

is high, remove the overload, cool, and retest.)

 

 

 

 

Fan motor

If not running, determine the cause. Replace if

 

 

required.

 

 

 

 

Condenser air flow

Remove the cabinet. inspect the interior surface

 

restriction

of the condenser; if restricted, clean carefully

 

 

with a vacuum cleaner (do not damage fins) or

 

 

brush. Clean the interior base before

 

 

reassembling.

 

 

 

 

Condenser fins

If condenser fins are closed over a large area

 

(damaged)

on the coil surface, head pressures will increase,

 

 

causing the compressor to cycle. Straighten the

 

 

fins or replace the coil.

 

Capacitor

Test capacitor.

 

 

 

 

Wiring

Check the terminals. If loose, repair or replace.

 

Refrigerating system

Check the system for restriction.

Insufficient cooling or

Air filter

If restricted, clean of replace.

heating

Exhaust damper door

Close if open.

 

 

 

 

Unit undersized

Determine if the unit is properly sized for the area to

 

 

be cooled.

Excessive noise.

Cross flow fan

Check the set screw or clamp. If loose or missing,

 

 

correct. If the blower or fan is hitting air guide,

 

 

rearrange the air handling parts.

 

Copper tubing

Carefully rearrange tubing not to contact,

 

 

compressor, shroud, and barrier.

 

 

 

Copyright ©2008 LG Electronics. Inc. All right reserved.

- 43 -

Only for training and service purposes

LGE Internal Use Only

 

Image 43
Contents SVC Manual Model LP121CEM-Y8 SpecificationSleeve and the Rear Grille Features and BenefitsQuick Heater Recovery Door Switch/Occupancy SensorOutdoor Air Temperature Switchover Temperature limitsCooling only Model Control LocationsOperation Electric Heating Model VentilationAdditional Controls Temperature LimitingAdditional Controls Removing the Front GrilleRemote Wall Thermostat REMOTE/LOCAL ControlEnergy Saver Front Desk ControlMechanical Parts Disassembly InstructionsFront Grille Control BOX Electric Heater Electric Heater Model only AIR Handling PartsAxial FAN Cross Flow FANCompressor Electrical PartsShroud Outdoor Motor6 P.C.B Power CordCapillary Tube Refrigeration CycleCondenser EvaporatorLGE Internal Use Only Pulling Vacuum Dimension of sleeve assembly optional InstallationHOW to Install the Unit Dimension of air conditionerWall Case Installation Data Wall Sleeve InstallationGeneral Preparation of the Front Grille Installation of Wall Case in Wall OpeningPreparation of the Wall Case for All Types of Construction LGE Internal Use Only Sub-Base Connected Unit Installation 208, 230, and 208/230 Volt Units Electrical SafetyElectrical Requirements Electrical Data for 230/208V ModelDescription Field Installed AccessoriesInstallation Control Panel Key LockHazardous Voltage Condensate Disposal Pump Kit InstallationPlace the top cover assembly back into the unit Spraying Architectural Grille Architecture Grille Aluminum Single PackCondensate Drain kit Drain InstallationOutdoor Drain Kit Installation Outdoor Drain Kit InstallationChecklist Indoor Drain Kit InstallationLeveling Legs Leveling Leg Assembly Installation on Wall Sleeve Leveling Leg AssemblyJunction Box Kit Installation and Wiring Procedure Hard Wire KitUse Copper Conductors Only Volt Units 208/230 Volt UnitsStandard Escutcheon Remote Escutcheon KitSubbase Part/Location Identification Outside Dimensions Troubleshooting GuidePiping System Troubleshooting Guide Fails to Start Complaint Cause Remedy 208/230V 187V 253V Room AIR Conditioner Voltage LimitsComplaint Cause Remedy CN-IDPT Piping DiagramsPart A, there are 3 types Schematic Diagram435300B Exploded ViewEnlarged picture Condenser Outdoor Service Replacement ProcedureFebruary