LG Electronics LP121CEM-Y8 manual Leveling Leg Assembly

Page 32

Leveling Leg Assembly

To install the leveling leg assembly, complete the following:

1.Drill two 1/8-inch holes in each side of the wall sleeve, as shown in Figure 48, using the leveling leg assembly as a template. Locations near the front of the sleeve provide more support.

2.Adjust the leveling legs to the approximate height needed and install them on either side of the wall sleeve, using the screws provided. Bottom of wall sleeve can be anywhere from three to five inches above the screw base. Caulk around screws to prevent water leaks.

3.Level the sleeve horizontally from side-to-side. Provide a slight slope (one-quarter bubble in the sight glass) toward the outside. Check the level again after the unit has been installed. Adjust the legs as needed.

Figure 48 - Leveling Leg Assembly

Installation on Wall Sleeve

1.Drill four 1/8-inch diameter holes in the wall sleeve, two on each side, using the leveling legs as a template. Caulk around screws to prevent water leaks.

2.Attach the legs to the wall sleeve, using the screws provided.

3.Adjust the leveling legs to level the wall sleeve from side to side and provide a slight pitch to the outside (one-quarter bubble in sight glass).

Figure 49 - Leveling Leg Installation on Wall Sleeve

1/8" Diameter holes

(four required per unit field-drilled)

Leveler Bracket

Speed Grip Nut

Adjuster Screw

1/2"

1"

1/4"

NOTES:

1.Two leveling legs are supplied in each kit.

2.One kit is required per unit.

3.Four mounting screws are provided in each kit.

Copyright ©2008 LG Electronics. Inc. All right reserved.

- 32 -

Only for training and service purposes

LGE Internal Use Only

 

Image 32
Contents SVC Manual Specification Model LP121CEM-Y8Features and Benefits Sleeve and the Rear GrilleDoor Switch/Occupancy Sensor Outdoor Air Temperature SwitchoverTemperature limits Quick Heater RecoveryControl Locations Operation Electric Heating ModelVentilation Cooling only ModelTemperature Limiting Additional ControlsRemoving the Front Grille Additional ControlsREMOTE/LOCAL Control Energy SaverFront Desk Control Remote Wall ThermostatFront Grille Disassembly InstructionsMechanical Parts Control BOX AIR Handling Parts Electric Heater Electric Heater Model onlyCross Flow FAN Axial FANElectrical Parts ShroudOutdoor Motor CompressorPower Cord 6 P.C.BRefrigeration Cycle CondenserEvaporator Capillary TubeLGE Internal Use Only Pulling Vacuum Installation HOW to Install the UnitDimension of air conditioner Dimension of sleeve assembly optionalGeneral Wall Sleeve InstallationWall Case Installation Data Preparation of the Wall Case for All Types of Construction Installation of Wall Case in Wall OpeningPreparation of the Front Grille LGE Internal Use Only Sub-Base Connected Unit Installation Electrical Safety Electrical RequirementsElectrical Data for 230/208V Model 208, 230, and 208/230 Volt UnitsField Installed Accessories InstallationControl Panel Key Lock DescriptionCondensate Disposal Pump Kit Installation Hazardous VoltagePlace the top cover assembly back into the unit Spraying Architecture Grille Aluminum Single Pack Architectural GrilleDrain Installation Condensate Drain kitOutdoor Drain Kit Installation Outdoor Drain Kit InstallationLeveling Legs Indoor Drain Kit InstallationChecklist Leveling Leg Assembly Leveling Leg Assembly Installation on Wall SleeveUse Copper Conductors Only Hard Wire KitJunction Box Kit Installation and Wiring Procedure 208/230 Volt Units Volt UnitsRemote Escutcheon Kit Standard EscutcheonSubbase Part/Location Identification Piping System Troubleshooting GuideOutside Dimensions Troubleshooting Guide Fails to Start Complaint Cause Remedy Room AIR Conditioner Voltage Limits 208/230V 187V 253VComplaint Cause Remedy Piping Diagrams CN-IDPTSchematic Diagram Part A, there are 3 typesExploded View 435300BCondenser Outdoor Service Replacement Procedure Enlarged pictureFebruary