LG Electronics MFL39817303 How to connect wiring to the terminals, For strand wiring

Page 22

Installation

How to connect wiring to the terminals

For strand wiring

(1)Cut the wire end with a wire cutter or wire- cutting pliers, then strip the insulation to expose the strand wiring about 10mm(3/8").

(2)Using a screwdriver, remove the terminal screw(s) on the terminal plate.

(3)Using a round terminal fastener or pliers, securely clamp each stripped wire end with a round terminal.

(4)Position the round terminal wire, and replace and tighten the terminal screw using a screwdriver.

Power supply cable

Strand wire

10mm(3/8")Strip

Round

 

terminal

 

Connecting cable

 

 

Loosening the

Fastening the

terminal block

wire tightly

screw

 

Connecting cable

According to the confirmation of the above conditions, prepare the wiring as follows.

1.Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control cover.

2.The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)

3.Specification of power source.

4.Confirm that electrical capacity is sufficient.

5.See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.

6.Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness.

7.Always install an earth leakage circuit breaker in a wet or moist area.

8.The following would be caused by voltage drop.

Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function of the overload.

9.The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm(0.12") in each active(phase) conductors.

22Room Air Conditioner

Image 22
Contents Room Air Conditioner Table of Contents Installation Instructions Be sure not to do Be sure to follow the instruction No installation may cause a fire and electrical shockIt may cause injury or an accident Operation Otherwise, it may cause vibration or water leakage Otherwise, it may cause water leakageOtherwise, it may cause dispute with the neighbors Otherwise, it may do harm to your healthSymbols used in this Manual FeaturesInstallation Tools Installation PartsRead carefully, and then follow step by step Installation Map Indoor unit Select the best LocationOutdoor unit Piping Length and Elevation Drill a Hole in the Wall Fixing Installation PlateType Burrs removal Flaring WorkCutting Tubes Putting nut onIndoor Connecting the PipingCheck Foamed polyethylene or equivalent is recommendedIndoor unit installation Lbf .ftFor left rear piping Piping for passage through piping hole Good case Bad caseOutdoor Connecting the CablesHow to use the front panel Move the link upward and close the front panelFront panel removing Refix the cover control to the original position Connect the wires to the terminals onWith the screw For strand wiring How to connect wiring to the terminalsConnecting cable Drain piping Checking the DrainageTo check the drainage Pour a glass of water on the evaporatorForming the Piping Air purging Air PurgingAir purging with vacuum pump Finishing the job Soap water methodEvacuation If bubbles come out, the pipes have leakageSettlement of outdoor unit Prepare remote controllerTest Running Evaluation of the performancePump Down Procedure Pump DownInstallation guide at the seaside Selecting the locationOutdoor UnitMemo Room Air Conditioner No. MFL39817303