LG Electronics MFL39817303 installation manual Soap water method, Evacuation, Finishing the job

Page 26

Installation

Soap water method

1.Remove the caps from the 2-way and 3-way valves.

2.Remove the service-port cap from the 3-way valve.

3.To open the 2-way valve turn the valve stem counterclockwise approximately 90°, wait for about 2~3 sec, and close it.

4.Apply a soap water or a liquid neutral detergent on the indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping.

5.If bubbles come out, the pipes have leakage

Evacuation

1.Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit.

Confirm the "Lo" and "Hi" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump. The following table shows the time required for evacuation.

Required time for evacuation when 30 gal/h vacuum

pump is used

If tubing length is less

If tubing length is longer

than 10m (33 ft)

than 10m (33 ft)

 

 

10 min. or more

15 min. or more

2.When the desired vacuum is reached, close the "Lo" and "Hi" knob of the manifold valve and stop the vacuum pump.

Finishing the job

1.With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.

2.Turn the valve stem of gas side valve counter- clockwise to fully open the valve.

3.Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose.

4.Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut securely with an adjustable wrench. This process is very important to prevent leakage from the system.

5.Replace the valve caps at both gas and liquid side service valves and fasten them tight.

This completes air purging with a vacuum pump. The air conditioner is now ready to test run.

Liquid side

Gas side

2-way valve (Open)

3-way valve (Close)

 

Hexagonal wrench

Cap

 

 

 

Indoor unit

 

 

Outdoor unit

 

Manifold valve

 

Lo

Hi

 

Open

Close

 

Vacuum pump

 

26Room Air Conditioner

Image 26
Contents Room Air Conditioner Table of Contents Installation Instructions It may cause injury or an accident No installation may cause a fire and electrical shockBe sure not to do Be sure to follow the instruction Operation Otherwise, it may cause vibration or water leakage Otherwise, it may cause water leakageOtherwise, it may cause dispute with the neighbors Otherwise, it may do harm to your healthSymbols used in this Manual FeaturesRead carefully, and then follow step by step Installation PartsInstallation Tools Installation Map Outdoor unit Select the best LocationIndoor unit Piping Length and Elevation Type Fixing Installation PlateDrill a Hole in the Wall Burrs removal Flaring WorkCutting Tubes Putting nut onIndoor Connecting the PipingCheck Foamed polyethylene or equivalent is recommendedIndoor unit installation Lbf .ftFor left rear piping Piping for passage through piping hole Good case Bad caseOutdoor Connecting the CablesHow to use the front panel Move the link upward and close the front panelFront panel removing With the screw Connect the wires to the terminals onRefix the cover control to the original position Connecting cable How to connect wiring to the terminalsFor strand wiring Drain piping Checking the DrainageTo check the drainage Pour a glass of water on the evaporatorForming the Piping Air purging with vacuum pump Air PurgingAir purging Finishing the job Soap water methodEvacuation If bubbles come out, the pipes have leakageSettlement of outdoor unit Prepare remote controllerTest Running Evaluation of the performancePump Down Procedure Pump DownInstallation guide at the seaside Selecting the locationOutdoor UnitMemo Room Air Conditioner No. MFL39817303