State Industries SUF100199, SUF100150 manual Venting Tables SUF 120, Venting Tables SUF 300,400

Page 10

ULTRAFORCE COMMERCIAL GAS WATER HEATER

SUF 120 thru 400 SERVICE HANDBOOK

VENTING TABLES SUF 120 – 250

Maximum equivalent feet of intake and vent pipe using 3” PVC is 50 feet (15.2m). Equivalent feet must include any 90° elbows (two 45° elbows equal one 90° elbow). Three inch diameter 90° elbows are equivalent to 5' (1.5m) of pipe.

Maximum equivalent feet of intake and vent pipe using 4” PVC is 120 feet (36.6m). Equivalent feet must include any 90° elbows (two 45° elbows equal one 90° elbow). Four inch diameter 90° elbows are equivalent to 5' (1.5m) of pipe.

Vent Length Table Equivalent Feet (Meters) 120 through 250

Number of 90°

3" Minimum

3" Maximum

4"Maximum

Elbows

Pipe (Ft./M.)

Pipe (Ft./M.)

Pipe (Ft./M.)

 

 

 

 

ONE (1)

7/2.1

45/13.7

115/35

 

 

 

 

TWO (2)

7/2.1

40/12.2

110/33.5

 

 

 

 

THREE (3)

7/2.1

35/10.7

105/32

 

 

 

 

FOUR (4)

7/2.1

30/9.1

100/30.5

 

 

 

 

FIVE (5)

7/2.1

---

95/29

 

 

 

 

SIX (6)

7/2.1

---

90/27.4

 

 

 

 

VENTING TABLES SUF 300,400,

Vent Length Table Equivalent Feet (Meters) 300,400,

Number of

4" PVC

90°Elbows

Maximum Feet / meters of Pipe

 

 

ONE (1)

65' / 19.7 m

 

 

TWO (2)

60' / 18.2 m

 

 

THREE (3)

55' / 16.7 m

 

 

FOUR (4)

50' / 15.2 m

 

 

FIVE (5)

45' / 13.6 m

 

 

SIX (6)

40' / 12.1 m

 

 

State Water Heaters – Technical Training Department 9

Ashland City, Tennessee © 2009

Servicing should only be performed by a Qualified Service Agent

198152-002

Image 10
Contents Service Handbook Table of Contents Ultraforce Commercial GAS Water HeaterIntroduction QualificationsTools Required Digital MultimeterGAS Pressure Specifications General InformationAdjustment Procedure GAS Pressure SUF120 and 150 Models High Altitude Installations SUF 120High Altitude Installation GAS OrificeHigh Altitude Adjustment SUF 300,400 SUF 300,400Installation Tips SUF 300 Venting Tables SUF 300,400 Venting Tables SUF 120Vent Length Table Equivalent Feet Meters 120 through Vent Length Table Equivalent Feet Meters 300,400Venting ALL Models Single Pipe Power Vent Using Room AIR Venting ALL Models TWO Pipe Direct Vent Using Outside AIR Vent Termination Direct Vent ALL Models Direct Venting ALL Models Control Overview ALL Models Status Description IconAdjusting Tank Temperature Operating SET Point Differential DisplayChanging the Display Units Fault and Warning Conditions Advanced Diagnostic Information Access to the Current Fault or Warning Viewing Information About the Water Heater Control Sequence Typical ALL Models Control Sequence Flow Chart Controls Central Control Board CCB Remove these Screws to release CoverControls GAS Valve SUF SUF 120 thru 400 Service Handbook Controls GAS Valve SUF 199 Important Note High Altitude InstallationSupply gas pressure Controls GAS Valve , Orifice CHART- SUF300,400 Orifice Chart SUF 300,400Controls Pressure Switches ALL Models Blocked Outlet Proving SwitchTop View of Pressure Switches Controls Pressure Switches SUF 300,400 Blocked Inlet Pressure Switch Odel PressureUltraforce Commercial GAS Water Heater Control Timing HOT Surface Igniter / Flame Sensor / Control TimingFlame Sensor Blower Speed Control SUF 199 ModelAI1 Blower Motor Wires Black White REDGround HOT Neutral LI1 LI2 LI3 LI4SUF Variable Frequency Drive Blower Speed and Pressure ReadingsVoltage Frequency Speed Instructions VFD Model 400Wiring Diagram SUF 120 Wiring Diagram SUF Tennessee Waltz Parkway Ashland City, TN