State Industries SUF100150, SUF100199 manual Vent Termination Direct Vent ALL Models

Page 13

ULTRAFORCE COMMERCIAL GAS WATER HEATER

SUF 120 thru 400 SERVICE HANDBOOK

VENT TERMINATION – DIRECT VENT – ALL MODELS

WHEN LOCATING THE TERMINALS ON A SIDEWALL, THE FOLLOWING SPECIFICATIONS PERTAINING TO TERMINAL LOCATION MUST BE FOLLOWED.

1.The intake vent terminal and the exhaust vent terminal must terminate on the same exterior wall and must be located at a minimum of 24" (61cm) from the vertical centerline of the exhaust vent terminal (see Figure 9).

In colder climates increasing the 24" (61cm) minimum will reduce possibility of frost over from side winds blowing exhaust vapors to the air intake of the direct vent.

2.The horizontal centerline of the intake vent terminal may not be located lower than the horizontal centerline of the exhaust vent terminal

State Water Heaters – Technical Training Department 12

Ashland City, Tennessee © 2009

Servicing should only be performed by a Qualified Service Agent

198152-002

Image 13
Contents Service Handbook Ultraforce Commercial GAS Water Heater Table of ContentsQualifications IntroductionDigital Multimeter Tools RequiredGeneral Information GAS Pressure SpecificationsHigh Altitude Installations SUF 120 Adjustment Procedure GAS Pressure SUF120 and 150 ModelsGAS Orifice High Altitude InstallationSUF 300,400 High Altitude Adjustment SUF 300,400Installation Tips SUF 300 Vent Length Table Equivalent Feet Meters 120 through Venting Tables SUF 120Venting Tables SUF 300,400 Vent Length Table Equivalent Feet Meters 300,400Venting ALL Models Single Pipe Power Vent Using Room AIR Venting ALL Models TWO Pipe Direct Vent Using Outside AIR Vent Termination Direct Vent ALL Models Direct Venting ALL Models Status Description Icon Control Overview ALL ModelsDisplay Adjusting Tank Temperature Operating SET Point DifferentialChanging the Display Units Fault and Warning Conditions Advanced Diagnostic Information Access to the Current Fault or Warning Viewing Information About the Water Heater Control Sequence Typical ALL Models Control Sequence Flow Chart Remove these Screws to release Cover Controls Central Control Board CCBControls GAS Valve SUF Important Note High Altitude Installation SUF 120 thru 400 Service Handbook Controls GAS Valve SUF 199Supply gas pressure Orifice Chart SUF 300,400 Controls GAS Valve , Orifice CHART- SUF300,400Blocked Outlet Proving Switch Controls Pressure Switches ALL ModelsTop View of Pressure Switches Blocked Inlet Pressure Switch Odel Pressure Controls Pressure Switches SUF 300,400Ultraforce Commercial GAS Water Heater Control Timing HOT Surface Igniter / Flame Sensor / Control TimingFlame Sensor Model Blower Speed Control SUF 199Ground HOT Neutral Blower Motor Wires Black White REDAI1 LI1 LI2 LI3 LI4Voltage Frequency Speed Instructions VFD Model Variable Frequency Drive Blower Speed and Pressure ReadingsSUF 400Wiring Diagram SUF 120 Wiring Diagram SUF Tennessee Waltz Parkway Ashland City, TN