State Industries Residential Gas Water Heater Venting, Vent Terminal Installation

Page 16

For 4" Venting, the maximum equivalent feet of pipe allowed is 160 feet (48.8 m). This does not include the Vent Termination (supplied locally) for the water heater. For the 4" venting, one 90° elbow is approximately equal to 8 feet (2.4 m). One 45° elbow is approximately equal to 4 feet (1.2 m). It is recommended that at least 2 feet (0.6 m) of spacing be used in between all 45° elbows and all 90°elbows.

55,000 and 62,500 BTU Units:

For 2" Venting, the maximum equivalent feet of pipe allowed is 35 feet (10.6 m). This does not include the supplied Vent Termination for the water heater. For the 2" venting, one 90° elbow is approximately equal to 5 feet (1.5 m). One 45° elbow is approximately equal to 2.5 feet (0.8 m). It is recommended that at least 2 feet (0.6 m) of spacing be used in between all 45° elbows and all 90°elbows.

For 3" Venting, the maximum equivalent feet of pipe allowed is 80 feet (24.4 m). This does not include the Vent Termination (supplied locally) for the water heater. For the 3" venting, one 90° elbow is approximately equal to 5 feet (1.5 m). One 45° elbow is approximately equal to 2.5 feet (0.8 m). It is recommended that at least 2 feet (0.6 m) of spacing be used in between all 45° elbows and all 90°elbows.

For 4" Venting, the maximum equivalent feet of pipe allowed is 120 feet (36.6 m). This does not include the Vent Termination (supplied locally) for the water heater. For the 4" venting, one 90° elbow is approximately equal to 8 feet (2.4 m). One 45° elbow is approximately equal to 4 feet (1.2 m). It is recommended that at least 2 feet (0.6 m) of spacing be used in between all 45° elbows and all 90°elbows.

VENTING

The vent system must terminate so that proper clearances are maintained as cited in local codes or the current edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, 7.3.4e and 7.8a,b, as follows:

1.The exit terminals of a mechanical vent system shall be not less than 7 feet (2.13 m) above grade when located adjacent to public walkways, see Figure 16.

2.A venting system shall terminate at least 3 feet (0.91 m) above any forced air inlet located within 10 feet (3.1 m), see Figure 16.

3.The venting system shall terminate at least 4 feet (1.2 m) below, 4 feet (1.2 m) horizontally from or, 1 foot (0.31 m) above any door, window or gravity air inlet into any building.

The manufacturer also recommends that the vent termination should not be installed closer than 3 feet (0.91 m) from an inside corner of an L shaped structure and not be less than 1 foot (0.31 m) above grade.

The vent shall terminate a minimum of 12'' (30.5 cm) above expected snowfall level to prevent blockage of vent termination, see Figure 16.

4.In cold climates, it is recommended that vent termination not be mounted directly above or within 3 feet (0.91 m) horizontally from an oil tank vent or gas meter to avoid potential freeze-up from condensation, see Figure 16..

Plan the vent system layout so that proper clearances are maintained from plumbing and wiring.

Vent pipes serving power vented appliances are classified by building codes as “vent connectors”. Required clearances from combustible materials must be provided in accordance with information in this manual under LOCATION OF HEATER and VENTTERMINAL INSTALLATIONS, and with the National Fuel Gas Code and local codes.

VENT TERMINAL INSTALLATION

1.After the point of termination has been determined, use the cover plate as a template to mark the hole for the vent pipe to insert through the wall. BEWARE OF CONCEALED WIRING AND PIPING INSIDE OF WALL.

2.If the Vent Terminal is being installed on the outside of a finished wall, it may be easier to mark both the inside and outside wall. Align the holes by drilling a hole through the center of the template from the inside through to the outside. The template can now be positioned on the outside wall using the drilled hole as a centering point for the template.

3.A) MASONRY SIDE WALLS

Chisel an opening approximately one half inch larger than the marked circle.

B) WOODEN SIDE WALLS

Drill a pilot hole approximately one quarter inch outside of the marked circle. This pilot hole is used as a starting point for a saws-all or sabre saw blade. Cut around the marked circle staying approximately one quarter inch outside of the line. (This will allow the vent pipe to easily slide through the opening. The resulting gap will be covered up by the vent terminal cover plates.) Repeat this step on inside wall if necessary.

16

Image 16
Contents Residential GAS Water Heaters Safe INSTALLATION, USE and Service Important DefinitionsGeneral Safety Table of Contents IntroductionNatural HOT Surface Igniter & Main Burner Typical InstallationPropane HOT Surface Igniter & Main Burner Mixing Valve Usage HotterwatercanscaldLocating the NEW Water Heater Facts to Consider about the LocationInsulation Blankets ALL AIR from Inside Buildings See ALL AIR from Outdoors See Figures 7, 8Water Piping Installing the NEW Water HeaterHotter Water can Scald TEMPERATURE-PRESSURE Relief Valve Valve and Pipe Insulation if suppliedGAS Piping with Flexibleconnector GAS PipingBlower Assembly Installation SequenceofinstallationSediment Traps Filling the Water HeaterVent Connections to Blower Assembly Venting and InstallationCondensate Maximum and Minimum Vent LengthsVent Terminal Installation VentingMasonry Side Walls Wooden Side WallsVertical Vent Through Roof Vertical Vent Termination RestrictionsVent Pipe Preparation Recommended BRUSH* Size for Primer Cement ApplicationsStepb StepeStepf Step GWatertemperatureadjustment PowerbeforeservicingDo not try to light the burner by hand What to do if YOU Smell GASTemperature Regulation Temperature Setting Burns on Adult SkinStart UP Conditions For Your InformationOperational Conditions Periodic Maintenance Burner CleaningVenting System Inspection Burner Operation and InspectionTEMPERATURE-PRESSURE Relief Valve Operation Drain Valve Washer ReplacementAnode ROD Inspection DrainingService Leakage CheckpointsBurner Assembly Drain PAN Outer Door Alternate Repair Parts ListNot Shown Optional Troubleshooting Guidelines Trouble ShootingTroubleshooting Guidelines Page Page Service and Labor Responsibility Claim ProcedureConditions and Exceptions Limitation on Implied WarrantiesTennessee Waltz Parkway Ashland City, TN

Residential Gas Water Heater specifications

State Industries has long been a trusted name in the water heating industry, known for its innovative and reliable residential gas water heaters. With a commitment to quality and efficiency, State Industries offers a range of products designed to meet the needs of homeowners. The State Industries Residential Gas Water Heater is an ideal choice for families seeking hot water solutions that balance performance, affordability, and durability.

One of the standout features of the State Industries gas water heater is its high efficiency. Many models are designed with Energy Factor (EF) ratings that exceed federal standards, allowing homeowners to enjoy lower utility bills while reducing their environmental impact. The use of advanced combustion technology ensures that gas is burned efficiently, maximizing available energy and minimizing waste. This is particularly beneficial in areas where gas prices fluctuate, as users can count on consistent savings.

The water heaters are constructed with robust materials, including a glass-lined tank to prevent corrosion and extend the lifespan of the unit. The insulation surrounding the tank minimizes heat loss, contributing to better energy efficiency. State Industries offers various tank capacities, ranging from 30 to 50 gallons, accommodating different household sizes and hot water demands.

Another notable characteristic is the implementation of safety features, such as a temperature and pressure relief valve that ensures safe operation. Some models are equipped with advanced venting technologies that help reduce exhaust emissions and enhance efficiency. Additionally, many gas models come with a reliable ignition system that allows for quick startups and consistent performance.

Incorporating user-friendly designs, State Industries gas water heaters often feature intuitive controls and easy-to-read gauges. This makes it easier for homeowners to monitor performance and adjust settings according to their needs. The availability of modulating gas valves in certain models allows for precise control over the heating process, providing hot water whenever it's needed.

State Industries also provides excellent customer support and extensive warranties for their products, giving users peace of mind. With a combination of efficiency, durability, and performance, the State Industries Residential Gas Water Heater stands out as a preferred option for homeowners looking to invest in reliable and effective water heating solutions. Regardless of the specific model chosen, users can expect a commitment to quality that is synonymous with the State brand.