CLEARANCES
It is of utmost importance that the clearances to combustible material be scrupulously respected upon installation of the stove you have selected. Refer to the tables below :
Figure 6: Clearances to combustibles
CANADA |
|
| Single pipe / Double pipe |
| |||
|
|
|
|
|
|
|
|
Model | A | B |
| C | D | E | F |
15/12 | 16/16 |
| 12/10 | 20.8/17.8 | 28.7/28.7 | 25.2/23.2 | |
| 19/10 | 19/14 |
| 11/8 | 25.4/16.4 | 33.1/28.1 | 25.5/22.5 |
USA |
|
| Single pipe / Double pipe |
| |||
|
|
|
|
|
|
|
|
Model | A | B |
| C | D | E | F |
15/12 | 16/16 |
| 12/10 | 20.8/17.8 | 28.7/28.7 | 25.2/23.2 | |
| 19/10 | 19/14 |
| 11/8 | 25.4/16.4 | 33.1/28.1 | 25.5/22.5 |
•Floor to ceiling height must be at least 7' (84") in all cases.
•The clearance between the flue pipe and a wall are valid only for vertical walls and for vertical flue pipe.
•The flue pipe must not go through roof trussing, an attic, a wardrobe or similar spaces; neither a floor or combustible partition.
•A flue pipe crossing a combustible wall must have a clearance of 18" minimum.
•To reduce flue pipe clearances from combustible materials, contact your local safety department.
13