Enviro C-10365, EG40 DV owner manual Trouble Shooting, Problem Possible Cause Solution

Page 27

Trouble Shooting

Problem

Possible Cause

Solution

 

 

 

Spark will not light the

Defective piezo ignitor.

• Check connections to ignitor.

pilot after repeatedly

 

• If ignitor connections are good but there is no spark;

pressing the spark ignitor

 

replace ignitor.

 

 

 

 

Broken spark electrode.

• Check for broken ceramic insulation.

 

 

• Replace electrode if broken.

 

 

 

 

Misaligned spark electrode.

• If spark is not arcing from electrode to pilot - adjust

 

 

by loosening the screws on the pilot base. Adjust

 

 

away from burner and retighten.

 

 

 

Pilot will not remain lit

Problem with thermocouple

• Check for proper connection of the thermocouple to

 

circuit.

the rear of the valve. If loose, tighten lightly.

 

 

• Check pilot for full flame impingement around

 

 

thermocouple. If flame is too small, check gas

 

 

pressure, adjust pilot rate screw, check pilot head for

 

 

damage or blockage.

 

 

• Check thermocouple voltage at rear of valve. It must

 

 

be greater than 5 mV. If low, replace thermocouple.

 

 

 

 

Air in gas line (pilot dies

• Bleed line.

 

while knob is depressed).

• Check gas line pressure.

 

 

• Contact dealer.

 

 

 

Burners will not remain

Problem with thermopile

• Check gas line pressure .

lit

circuit.

• Check for flame impingement on thermopile. If low,

 

 

see “Pilot will not remain lit”.

 

 

• Check thermopile for minimum of 200 mV when

 

 

burner is switched on.

 

 

• Check wiring to thermostat for breaks.

Flame lifting

Leak in vent pipe.

• Check for leaks in vent connections.

 

 

 

 

Improper vent

• Check vent configuration with manual.

 

configuration.

 

 

 

 

 

Terminal may be

• Check to see if the terminal is on correctly.

 

recirculating flue gases.

• May need to install high wind termination cap.

 

 

• Contact dealer.

 

 

 

Glass fogs up

Normal Condition: after the appliance warms up the glass will clear.

 

**Due to additives in gas, glass may get hazy during operation** Clean as needed.

 

 

 

Blue Flames

Normal during start up: flames will yellow as the fireplace heats up.

 

 

 

Flames are burning

Flame impingement

• Check log positioning.

“dirty” or sooting

 

• See also “Burners will not remain lit.”

 

 

 

Flame goes out / comes

Defective rocker switch.

• Check rocker switch connections.

on frequently during a

 

• Replace switch if necessary.

short period of time.

 

 

27

Image 27
Contents S H E R W O O D I N D U S T R I E S L T D EG40 DVSafety Precautions For Your SafetyGeneral Table of Contents Codes And Approvals Vented GAS Fireplace Heater EG40 DV NG/LPGThis Enviro EG40 DV Fireplace EG40 Exterior Dimensions SpecificationsQualified Installers only Initial InstallationVent restrictor ring Vent Pipe Types with Part Numbers Venting Terminals Cannot be Recessed Into a Wall or SidingCommon Vertical Installation High temperature Silicone Male Edge Outer pipe. Push Installing Horizontal Vent Termination Do not interfere with the structural integrity of the walls Feet Meters Roof Pitch Minimum HeightMulti-Story Vent Pipe Installation KIT Components Cut away of spacers on Flex Pipe Installation InstructionsAssembly of Venting Kit Assembly of Venting into a Class ‘A’ Chimney Wiring of a Thermostat Turn the unit off and remove the log set 50% turn down HI-LOW Regulator GAS Line Connection To Test Valve PressuresPressure taps are located on the left side of the valve Log Placement Secondary InstallationLog Placement with Embers Water Never USE AN Open Flame for Leak TESTING. If Operating InstructionsWhat to do if YOU Smell GAS Opening the Door Routine Maintenance and ServiceCleaning the Inside of the Firebox Cleaning Plated SurfacesProblem Possible Cause Solution Trouble ShootingParts List Parts List Parts Diagram Chassis Parts Diagram Gas Tray & Door To the Distributor WarrantyInstallation Data Sheet