Burnham BV, BH manual Hot Water Performance Data -- High Motor Speed

Page 17

F.HOT WATER PERFORMANCE DATA (at Standard Conditiions of 200°F Entering Water, 60°F Entering Air and 20°F Water Temperature Drop)

Table 9: Hot Water Performance Data -- High Motor Speed

 

 

 

 

WATER DATA

 

 

 

 

AIR DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drop

 

 

Max.

Heat

 

 

Outlet

Final Air

Model

Model

 

 

(ft. of

Min/Max

Sound

Mounting

Spread at

 

Velocity

Temp.

Type

Number

BTU/Hr.

GPM

water)

GPM

Class**

Height (ft.)*

Max. Height*

Cfm

(Fpm)

(°F)

 

BH-18

13,000

1.3

0.49

0.3/5.0

II

 

9

18

 

400

500

90

DELIVERY

BH-24

17,300

1.7

0.83

0.3/5.0

II

 

10

20

 

450

570

96

BH-33

24,500

2.5

0.12

0.4/10.0

II

 

11

22

 

630

495

96

 

 

 

 

BH-47

33,800

3.4

0.21

0.4/10.0

III

 

13

26

 

730

580

103

 

BH-63

46,500

4.7

0.47

0.5/15.0

III

 

15

30

 

1120

590

98

AIR

BH-86

61,900

6.2

0.79

0.5/15.0

III

 

16

31

 

1340

710

103

BH-108

81,000

8.1

0.85

0.5/20.0

III

 

16

33

 

1550

605

108

 

 

 

HORIZONTAL

BH-121

90,000

9.0

1.04

0.7/20.0

III

 

17

36

 

1775

690

107

BH-165

133,000

13.3

2.48

2.0/30.0

IV

 

18

38

 

2500

735

109

 

 

 

 

BH-193

156,000

15.6

3.35

2.0/30.0

IV

 

19

40

 

2900

850

110

 

BH-258

198,000

19.8

3.54

2.5/40.0

V

 

20

42

 

3900

895

107

 

BH-290

224,000

22.4

4.45

2.5/40.0

V

 

21

46

 

4300

990

108

 

BH-340

273,000

27.3

3.24

2.5/50.0

V

 

22

50

 

5130

945

109

 

BV-42

30,500

3.1

0.09

0.5/10.0

II

11

 

15

17

 

11

950

776

91

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-59

44,300

4.5

0.18

0.8/15.0

II

14

 

19

21

 

15

1150

940

97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-78

58,500

6.0

0.43

1.0/20.0

II

15

 

21

23

 

16

1550

990

96

DELIVERY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-95

71,000

7.2

0.61

1.3/25.0

II

17

 

23

25

 

17

1775

1132

99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-139

111,000

11.3

0.84

1.0/30.0

III

18

 

25

28

 

19

2500

1281

103

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-161

128,800

13.1

1.11

1.3/40.0

III

22

 

30

33

 

21

2900

1488

103

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR

BV-193

142,700

14.5

0.81

1.5/50.0

IV

24

 

33

36

 

24

3900

1640

95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-212

159,000

16.1

0.98

2.0/60.0

IV

25

 

35

37

 

25

4300

1809

96

VERTICAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-247

197,000

19.9

1.65

2.0/60.0

IV

27

 

36

40

 

27

5130

1803

97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-279

220,000

22.2

2.01

2.3/75.0

V

31

 

39

47

 

31

5800

2037

97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-333

265,000

26.7

1.27

2.8/75.0

V

30

 

38

46

 

30

6600

1966

99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-385

308,000

31.1

1.68

3.3/75.0

VI

33

 

40

49

 

33

7860

1928

97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-500

403,000

40.9

2.32

3.0/100.0

VI

40

 

48

60

 

40

10790

2487

94

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BV-610

459,000

46.3

2.42

6.0/100.0

VI

39

 

47

58

 

40

12350

2343

97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 10: Hot Water Performance Data -- Reduced Motor Speed

 

 

 

WATER DATA

 

 

AIR DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pressure

 

 

 

 

 

 

 

 

 

 

Drop

 

Max.

Heat

 

Outlet

Final Air

Model

Model

 

 

(ft. of

Sound

Mounting

Spread at

 

Velocity

Temp.

Type

Number

BTU/Hr.

GPM

water)

Class**

Height (ft.)*

Max. Height*

Cfm

(Fpm)

(°F)

DELIVERY

BH-18

10,660

1.3

0.49

I

9

13

310

390

92

BH-24

14,186

1.7

1.83

I

10

14

350

450

98

 

 

BH-33

20,090

2.5

0.12

I

11

16

490

390

98

AIR

BH-47

27,716

3.4

0.21

II

13

18

565

455

105

BH-63

38,130

4.7

0.47

II

15

21

870

460

101

HORIZONTAL

BH-86

50,758

6.2

0.79

II

16

22

1040

550

105

 

 

BH-108

66,420

8.1

0.85

II

16

23

1240

485

110

 

BH-121

73,800

9.0

1.04

II

17

26

1415

555

108

 

BH-165

109,060

13.3

2.48

III

18

27

1990

590

111

 

BH-193

127,920

15.6

3.35

III

19

28

2310

680

111

*Units with horizontal louvers open 30° from vertical plane, vertical types equipped with cone jet deflector, blades fully opened are shown in bold.

Non-bolded mounting height/spread data is for units without deflectors. Please see page 21 for additional outlet accessory performance data.

**See page 7 for Sound Class Definitions.

17

Image 17
Contents 8144A001R4-2/07 BH and BV Unit HeatersTable of Contents Important Information Read Carefully Before Installation II. General Information III. InstallationUnit Heater Mounting Height Wiring Instructions115V / 60Hz / 1PH Wiring Schematic Hot Water System Piping Recommended Maximum Mounting HeightInitial START-UP IV. OperationPrior to Operation Inspect Regularly MaintenanceMotors CasingsGeneral Guidelines VI. Application GuidelinesTypical BH Unit Arrangement Sound Class Ratings Large Factories, Fabrication ShopsSteam Performance Data -- Reduced Motor Speed Steam Performance DataSteam Performance Data -- High Motor Speed Given Design Conditions Selection Procedure Steam ApplicationApplication Procedure Fata = Eata + Atra Steam Calculation Formulas Steam Heating Capacity Conversion Factors Steam Correction Factors Unit Entering Heater Air Temp Types 100 125 150Steam Unit Heater Mounting Height Correction Factors Air Temperature Rise Conversion FactorsSteam Pressure Psig Correction FactorBtu/lb Properties of SteamGauge Temp Latent Heat Hot Water Performance Data -- Reduced Motor Speed Hot Water Performance Data -- High Motor SpeedWater Temperature Selection Procedure HOT Water ApplicationWater Flow Rate 125,020 Btu/hr Final AirBtuAG = BtuS or BtuA x Glycol Correction Factor HOT Water Calculation FormulasHot Water Heating Capacity Conversion Factors HOT Water Correction FactorsEthylene Glycol Correction Factors Hot Water Unit Heater Mounting Height Correction FactorsField Installed Options for Horizontal and Vertical Models VII. OPTIONS, Accessories and Control SequencesField Installed Options for Horizontal Models only Control SequencesDescription Field Installed Options for Vertical Models onlyVertical Air Outlet Accessory Dimensions Cone-JetLou Truncone No Deflector Anemo Vertical Air Outlet Accessory Maximum Height and Spread123Model BH Dimensions VIII. Dimensional DataBH Dimensional Data Male NPT Fan Ship Model BV Dimensional DataModel BV Dimensions Motor/Power Description Code Motor/Power CodesIX. Motor Data Voltage and Motor TypeLimited Warranty