G.SELECTION PROCEDURE - HOT WATER APPLICATION

Example 1:

GIVEN DESIGN CONDITIONS:

Unit Heater Model: BV-59, Entering Water Temperature: 250°F, Entering Air Temperature: 70°F

APPLICATION PROCEDURE:

1.

Capacity:

BtuA= BtuS x Heating Capacity Factor

￿

The standard capacity of an BV-59 is

 

 

=44,300 x 1.272 = 56,350 Btu/hr

 

44,300 Btu/hr from Table 9.

 

 

 

￿

Steam heating capacity conversion factor

 

 

 

 

for given circumstance is1.272 from Table 11.

2. Water Flow Rate:

Same as standard

￿

The standard capacity on BV-59 is based upon a

 

 

 

 

water flow rateof 4.5 GPM, from Table 9.

3.

Final Air

FATA = EATA + [(460 + EATA) /

￿

The standard airflow of an BV-59 is 1150 CFM,

 

Temperature:

(576 x CfmS) / BtuA -1)]

 

from Table 9.

 

 

FATA = 70°F + [(460 + 70) /

 

 

 

 

(576 x 1150) / 56,350-1)] = 119°F

 

 

4. Max. Mounting

WTDA = BtuA / (480 x GA) = 56,350 /

￿

The standard capacity on BV-59 is based upon a

 

Height:

(480 x 4.5) = 26.09°F

 

water flow rate of 4.5 GPM, from Table 9.

 

 

 

￿

The max. mounting height at standard condition

5. Max. Mounting

MMHA = MMHS x Correction Factor

 

is 14 feet, from Table 9.

 

Height:

= 14 feet x 0.86 = 12.0 feet

￿

The mounting height correction factor is

 

 

 

 

0.86 from Table 14.

 

 

 

 

 

Example 2:

GIVEN DESIGN CONDITIONS:

Horizontal Air Delivery requested, Heating Load: 120,000 Btu/hr, Entering Air Temp.: 50°F, Entering Water Temp.: 180°F

APPLICATION PROCEDURE:

1.

Unit Selection:

BtuS= BtuA x Heating Capacity Factor

￿

Hot Water heating capacity conversion factor for

 

 

=120,000 / 0.940 = 127,660 Btu/hr

 

given circumstance is 0.940 from Table 11.

 

 

(at standard conditions). Select BH-165.

 

 

2.

Actual Heating

The capacity of an BH-165 at actual

￿

Hot Water heating capacity conversion factor for

 

Capacity:

conditions will be BtuA = BtuX x Heating

 

given circumstance is 0.940 from Table 11.

 

 

Capacity Factor = 133,000 x 0.940 =

 

 

 

 

125,020 Btu/hr

 

 

3.

Final Air

FATA = EATA + [(460 + EATA) x (BtuA)/

￿

Cfm for given circumstance is 2500 from

 

Temperature:

(576 x CfmS)] = 50 x [(460 + 50 x

 

Table 9.

 

 

(125,020) / (576 x 2500)] = 94°F

 

 

4. Water Temperature

WTDA = BtuA / (480 x GPMA)

￿

GPMA for given circumstance is 13.3 from

 

Drop:

= 125,020 / (480 x 13.3) = 19.5°F

 

Table 9.

5.

Max. Mounting

MMHA = MMHS x Correction Factor

￿

The mounting height correction factor is 1.08

 

Height:

= 18 x 1.08 = 19.4 feet

 

from Table 14.

18

Image 18
Contents BH and BV Unit Heaters 8144A001R4-2/07Table of Contents Important Information Read Carefully Before Installation III. Installation II. General InformationWiring Instructions Unit Heater Mounting Height115V / 60Hz / 1PH Wiring Schematic Recommended Maximum Mounting Height Hot Water System PipingIV. Operation Prior to OperationInitial START-UP Motors MaintenanceInspect Regularly CasingsTypical BH Unit Arrangement Sound Class Ratings VI. Application GuidelinesGeneral Guidelines Large Factories, Fabrication ShopsSteam Performance Data Steam Performance Data -- High Motor SpeedSteam Performance Data -- Reduced Motor Speed Selection Procedure Steam Application Application ProcedureGiven Design Conditions Steam Calculation Formulas Fata = Eata + AtraUnit Entering Steam Correction FactorsSteam Heating Capacity Conversion Factors Heater Air Temp Types 100 125 150Steam Pressure Psig Air Temperature Rise Conversion FactorsSteam Unit Heater Mounting Height Correction Factors Correction FactorProperties of Steam Gauge Temp Latent HeatBtu/lb Hot Water Performance Data -- High Motor Speed Hot Water Performance Data -- Reduced Motor SpeedWater Flow Rate Selection Procedure HOT Water ApplicationWater Temperature 125,020 Btu/hr Final AirHOT Water Calculation Formulas BtuAG = BtuS or BtuA x Glycol Correction FactorEthylene Glycol Correction Factors HOT Water Correction FactorsHot Water Heating Capacity Conversion Factors Hot Water Unit Heater Mounting Height Correction FactorsField Installed Options for Horizontal Models only VII. OPTIONS, Accessories and Control SequencesField Installed Options for Horizontal and Vertical Models Control SequencesField Installed Options for Vertical Models only DescriptionVertical Air Outlet Accessory Dimensions Vertical Air Outlet Accessory Maximum Height and Spread123 Cone-JetLou Truncone No Deflector AnemoVIII. Dimensional Data BH Dimensional DataModel BH Dimensions BV Dimensional Data Model BV DimensionsMale NPT Fan Ship Model IX. Motor Data Motor/Power CodesMotor/Power Description Code Voltage and Motor TypeLimited Warranty