Burnham BV, BH manual Steam Calculation Formulas, Fata = Eata + Atra

Page 13

D.STEAM CALCULATION FORMULAS

1.Refer to Table 5:

a.To determine the heating capacity (Btu/hr) of a unit heater at a steam pressure and/or entering air temperature other than standard conditions of 2 lb. Steam and 60°F entering air temperature.

b.To find actual unit heater capacity when operating at non-standard (actual) conditions:

BtuA = BtuS x Heating Capacity Factor

c.To select a heater capacity based on standard conditions to meet a heating capacity at non- standard (actual) conditions:

BtuS = BtuA / Heating Capacity Factor

2.Refer to Table 6:

a.To determine the air temperature rise of a unit heater at a steam pressure and/or entering air temperature other than standard conditions of 2 lb. Steam, 60°F entering air temperature.

b.To find actual air temperature rise of unit heater when operating at non-standard (actual) conditions:

ATRA = (FATS - EATS) x Air Temperature Rise Factor

c.To find actual final air temperature of unit heater when operating at non-standard (actual) conditions:

FATA = EATA + ATRA

3.Refer to Table 7:

To determine how non-standard steam pressures (other than 2 lb.) affect mounting height.

Max. Mounting HeightA = Max. Mounting

HeightS x Correction Factor

4.Refer to Table 8:

To determine the rate of condensate production at steam pressures other than 2 lb.

Condensate Rate = BtuA / Latent Heat of Steam

5.Terminology:

a.ATRA = Air temperature rise at non-standard (actual) conditions

b.BtuA = Capacity at actual operating conditions

c.BtuS = Capacity at standard conditions (2 lb. Steam, 60°F entering air temperature) from Tables 3 and 4.

d.EATA = Entering air temperature at non-standard actual) conditions

e.EATS = Entering air temperature at standard conditions (60°F)

f.FATA = Final air temperature at non-standard (actual) conditions

g.FATS = Final air temperature at standard conditions from Tables 3 and 4.

h.Max. Mounting HeightA = Maximum mounting height at actual conditions

i.Max. Mounting HeightS = Maximum mounting height at standard conditions

13

Image 13
Contents 8144A001R4-2/07 BH and BV Unit HeatersTable of Contents Important Information Read Carefully Before Installation II. General Information III. InstallationUnit Heater Mounting Height Wiring Instructions115V / 60Hz / 1PH Wiring Schematic Hot Water System Piping Recommended Maximum Mounting HeightPrior to Operation IV. OperationInitial START-UP Inspect Regularly MaintenanceMotors CasingsGeneral Guidelines VI. Application GuidelinesTypical BH Unit Arrangement Sound Class Ratings Large Factories, Fabrication ShopsSteam Performance Data -- High Motor Speed Steam Performance DataSteam Performance Data -- Reduced Motor Speed Application Procedure Selection Procedure Steam ApplicationGiven Design Conditions Fata = Eata + Atra Steam Calculation FormulasSteam Heating Capacity Conversion Factors Steam Correction FactorsUnit Entering Heater Air Temp Types 100 125 150Steam Unit Heater Mounting Height Correction Factors Air Temperature Rise Conversion FactorsSteam Pressure Psig Correction FactorGauge Temp Latent Heat Properties of SteamBtu/lb Hot Water Performance Data -- Reduced Motor Speed Hot Water Performance Data -- High Motor SpeedWater Temperature Selection Procedure HOT Water ApplicationWater Flow Rate 125,020 Btu/hr Final AirBtuAG = BtuS or BtuA x Glycol Correction Factor HOT Water Calculation FormulasHot Water Heating Capacity Conversion Factors HOT Water Correction FactorsEthylene Glycol Correction Factors Hot Water Unit Heater Mounting Height Correction FactorsField Installed Options for Horizontal and Vertical Models VII. OPTIONS, Accessories and Control SequencesField Installed Options for Horizontal Models only Control SequencesDescription Field Installed Options for Vertical Models onlyVertical Air Outlet Accessory Dimensions Cone-JetLou Truncone No Deflector Anemo Vertical Air Outlet Accessory Maximum Height and Spread123BH Dimensional Data VIII. Dimensional DataModel BH Dimensions Model BV Dimensions BV Dimensional DataMale NPT Fan Ship Model Motor/Power Description Code Motor/Power CodesIX. Motor Data Voltage and Motor TypeLimited Warranty