I.HOT WATER CORRECTION FACTORS
Table 11: Hot Water Heating Capacity Conversion Factors
| Entering Air |
|
|
|
|
| ENTERING AIR TEMPERATURE (°F) |
|
|
|
|
|
|
|
| |||||||||
| Temp. (°F) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 0 | 10 | 20 |
| 30 | 40 |
|
|
| 50 | 60 |
|
| 70 |
| 80 |
| 90 |
|
| 100 | |||
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
| 100 | 0.769 | 0.683 | 0.599 |
| 0.518 | 0.439 |
|
| 0.361 | 0.286 |
| 0.212 |
| 0.140 |
| 0.069 |
| 0.000 | |||||
| 110 | 0.846 | 0.759 | 0.674 |
| 0.592 | 0.512 |
|
| 0.434 | 0.357 |
| 0.283 |
| 0.210 |
| 0.138 |
| 0.068 | |||||
| 120 | 0.923 | 0.835 | 0.749 |
| 0.666 | 0.585 |
|
| 0.506 | 0.429 |
| 0.353 |
| 0.279 |
| 0.207 |
| 0.137 | |||||
| 130 | 1.000 | 0.911 | 0.824 |
| 0.740 | 0.658 |
|
| 0.578 | 0.500 |
| 0.424 |
| 0.349 |
| 0.276 |
| 0.205 | |||||
| 140 | 1.077 | 0.987 | 0.899 |
| 0.814 | 0.731 |
|
| 0.651 | 0.571 |
| 0.494 |
| 0.419 |
| 0.345 |
| 0.273 | |||||
| 150 | 1.154 | 1.063 | 0.974 |
| 0.888 | 0.805 |
|
| 0.723 | 0.643 |
| 0.565 |
| 0.489 |
| 0.414 |
| 0.342 | |||||
| 160 | 1.231 | 1.139 | 1.049 |
| 0.962 | 0.878 |
|
| 0.795 | 0.714 |
| 0.636 |
| 0.559 |
| 0.483 |
| 0.410 | |||||
| 170 | 1.308 | 1.215 | 1.124 |
| 1.036 | 0.950 |
|
| 0.867 | 0.786 |
| 0.706 |
| 0.629 |
| 0.552 |
| 0.478 | |||||
| 180 | 1.385 | 1.291 | 1.199 |
| 1.110 | 1.024 |
|
| 0.940 | 0.857 |
| 0.777 |
| 0.699 |
| 0.621 |
| 0.547 | |||||
| 190 | 1.492 | 1.367 | 1.274 |
| 1.184 | 1.097 |
|
| 1.012 | 0.929 |
| 0.848 |
| 0.768 |
| 0.690 |
| 0.615 | |||||
| 200 | 1.539 | 1.443 | 1.349 |
| 1.258 | 1.170 |
|
| 1.084 | 1.000 |
| 0.918 |
| 0.838 |
| 0.759 |
| 0.684 | |||||
| 210 | 1.615 | 1.519 | 1.424 |
| 1.332 | 1.243 |
|
| 1.157 | 1.071 |
| 0.989 |
| 0.908 |
| 0.828 |
| 0.752 | |||||
| 220 | 1.962 | 1.594 | 1.499 |
| 1.406 | 1.312 |
|
| 1.229 | 1.143 |
| 1.060 |
| 0.978 |
| 0.897 |
| 0.820 | |||||
| 230 | 1.769 | 1.670 | 1.573 |
| 1.480 | 1.390 |
|
| 1.301 | 1.241 |
| 1.130 |
| 1.048 |
| 0.966 |
| 0.889 | |||||
| 240 | 1.846 | 1.746 | 1.649 |
| 1.554 | 1.463 |
|
| 1.373 | 1.286 |
| 1.201 |
| 1.118 |
| 1.035 |
| 0.957 | |||||
| 250 | 1.923 | 1.822 | 1.723 |
| 1.628 | 1.536 |
|
| 1.446 | 1.357 |
| 1.272 |
| 1.188 |
| 1.104 |
| 1.025 | |||||
| 260 | 2.000 | 1.898 | 1.798 |
| 1.702 | 1.609 |
|
| 1.518 | 1.429 |
| 1.342 |
| 1.257 |
| 1.173 |
| 1.094 | |||||
| 270 | 2.077 | 1.974 | 1.873 |
| 1.776 | 1.682 |
|
| 1.590 | 1.500 |
| 1.413 |
| 1.327 |
| 1.242 |
| 1.162 | |||||
| 280 | 2.154 | 2.050 | 1.948 |
| 1.850 | 1.755 |
|
| 1.663 | 1.571 |
| 1.483 |
| 1.397 |
| 1.311 |
| 1.230 | |||||
| 290 | 2.231 | 2.126 | 2.023 |
| 1.924 | 1.829 |
|
| 1.734 | 1.643 |
| 1.554 |
| 1.467 |
| 1.380 |
| 1.300 | |||||
| 300 | 2.308 | 2.202 | 2.098 |
| 1.998 | 1.902 |
|
| 1.807 | 1.714 |
| 1.625 |
| 1.537 |
| 1.449 |
| 1.367 | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Table 12: Correction Factors for Varying Water Temperature Drop* |
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| Water Temperature Drop, (°F) |
| 5 |
| 10 | 15 |
| 20 |
| 25 | 30 | 35 | 40 |
| 45 |
| 50 | 55 | 60 | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
| Btu Correction Factor |
| 1.23 | 1.13 | 1.06 |
| 1.00 |
| 0.95 | 0.90 | 0.86 | 0.82 |
| 0.78 |
| 0.72 | 0.69 | 0.67 | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
| GPM Correction Factor |
| 4.64 | 2.21 | 1.40 |
| 1.00 |
| 0.76 | 0.61 | 0.50 | 0.42 | 0.36 |
| 0.30 | 0.26 | 0.23 | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
| WPD Correction Factor |
| 17.24 | 4.32 | 1.85 |
| 1.00 |
| 0.61 | 0.41 | 0.30 | 0.22 | 0.18 |
| 0.14 | 0.12 | 0.11 | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
* Water temperature drop correction factors valid only for standard 200°F entering water and 60°F air temperature conditions.
Table 13: Ethylene Glycol Correction Factors**
Solution Temperature (°F) |
|
| ETHYLENE GLYCOL SOLUTION % |
|
| |||
|
|
|
|
|
|
| ||
20% | 30% | 40% | 50% | 60% | 70% | 80% | ||
| ||||||||
|
|
|
|
|
|
|
| |
100 | 0.99 | 0.96 | 0.93 | 0.89 | 0.85 | 0.81 | 0.76 | |
|
|
|
|
|
|
|
| |
150 | 0.99 | 0.96 | 0.94 | 0.90 | 0.87 | 0.83 | 0.78 | |
|
|
|
|
|
|
|
| |
200 | 0.99 | 0.97 | 0.94 | 0.92 | 0.88 | 0.85 | 0.81 | |
|
|
|
|
|
|
|
| |
250 | 0.98 | 0.96 | 0.94 | 0.92 | 0.89 | 0.86 | 0.82 | |
|
|
|
|
|
|
|
|
** For Propylene Glycol solution correction factor, multiply Ethylene Glycol correction factor by 0.95.
Table 14: Hot Water Unit Heater Mounting Height Correction Factors***
|
|
|
|
|
| ENTERING WATER TEMPERATURE, °F |
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 140 | 150 | 160 | 170 | 180 | 190 | 200 | 210 | 220 | 230 | 240 | 250 | 260 | 270 | 280 | 290 | 300 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Correction | 1.33 | 1.25 | 1.19 | 1.13 | 1.08 | 1.04 | 1.00 | 0.97 | 0.94 | 0.91 | 0.89 | 0.86 | 0.84 | 0.82 | 0.80 | 0.78 | 0.77 | |
Factor | ||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*** Factors are for use with entering air temperature ranging from 50°F to 70°F.
20