TANKSTAT TEMPERATURE CONTROL

This is a bulb immersion type device that will regulate the water temperature in the storage tank. When the water temperature rises to the set point, the switch opens and shuts off the main burners. As the water cools down, the switch closes and turns on the main burners again to maintain the desired water tem- perature.

FLOW SWITCH

Dual purpose control shuts off heater in case of pump failure or low water flow condition.

Factory mounted on all boilers except 136 and wired in series with main gas valve.

NOTE: Flow switch will not operate if flow is less than 12 GPM.

Fig. # 8643

TemperatureControl

HIGHLIMIT

The high limit is also a bulb immersion type device that limits the water temperature in the heater outlet. It will shut off the main burners when the heater outlet water temperature exceeds the high limit setting, and cycles on again when the water temperature drops to the set point, less the differential.

Models are equipped with manual reset high limit on all models except 136. Model 136 is equipped with an automatic reset high limit.

HIGH LIMIT (Manual Reset)

The manual reset high limit is similar to the auto- matic reset high limit, except the reset button on the front of the case must be pushed in to allow the main burners to operate again after a high limit shutdown.

Models are equipped with manual reset high limit. The temperature setting is usually set 30° to 40°F above the operating temperature.

Fig. # 9314

Manual Reset High Limit

Fig. #9317

Flow Switch

28

Image 28 Contents
Important Warning Catalog NO. RM-001Electric Code ANSI/NFPA Index Construction Features Series GB For circulating tank systems Through 1826 MbtuhSpecification Data Page Shipping Installation Regulations ReceivingequipmentWater Flow Water ConditionsCombustible Floor Base BaserequirementsBoiler Part Combustibleconstructionclearances Protected SurfacesCombustion and Ventilation AIR Supply Recommended Minimum AIR OpeningsMODEL181-399 ModelMODELS926-1758 Models 512Indoorheaters Models Heater Before Heater After Drafthood Installation MODELS181-399Page Fig. #7043.1 Power Venting Vent Damper InstallationModels 136 Through 264 Where Required Location OutdoorwaterheatersMounting Normal Operation SummaryGas Natural Propane BTU/CFSP. GR Pipe SizesTest piping as follows Fig.#8185.1Cold Water Supply WaterGPM NPT HOT Water Supply Heater TanktemperaturecontrolSeries with 115 Volt Supply to the Heater Piping DIAGRAM-1 Heater 1 Tank Thermostat Supplied Installation Water Heater PlumbingSequenceofoperation Piping DIAGRAM-1 Heater 2 Tank Piping Must be Equal Between Tees and TANKS. NotesPiping DIAGRAM-1 Heater 3 Tank Fig. # 8067-RHEEMPiping DIAGRAM-1 Heater 4 Tank Piping DIAGRAM-2 Heater 1 Tank Special Thermostat and Well Energy Saving Pump Control Description of Controls in GeneralElectronicignition Flow Switch Tankstat Temperature ControlHighlimit Electrical Single Stage TankstatSTART-UP ON-OFFOPERATIONTIME/TEMPERATURE Relationships in Scalds ScaldingFor Your Safety Read Before Operating Close all manual gas valves. Turn off electric power To Shut DownMonthly Inspectionand MaintenanceproceduresSix Months System Shut Down Procedure Service AssistanceBurner Inspection Venting System InspectionTrouble Shooting Problem If okay replace ignition module Electrical Electronic Ignition IID Models 512 StartWiring Diagram KEY Wiring Diagrams Wiring Diagram Models 331 Wiring Diagram Models 512Wiring Diagram Models Wiring Diagram Models 726Wiring Diagram Model 825 Wiring Diagram Models 962 Fig. # 1967eReplacement Parts Lists Model 136 GB onlyModel 136 GB only Models 181, 264, 331, 399 GB Page Models 181, 264, 331, 399 GB Models 181, 264, 331,339 GB Models 512, 627, 726, 825 GB Models 512, 627, 726, 825 GB Models 512, 627, 726, 825 GB Models 926-1826 GB Models 926-1826 GB Models 926-1826 GB