Rheem 136-1826 installation instructions

Page 14
14
Fig # 8119
HEATER
DRAFT HOOD
VENT PIPE
5' MIN
2' MIN
2' MIN
VENT CAP
10' OR LESS
Vent piping the same size or larger than the draft hood outlet is recommended, however, when the total vent height is at least ten (10) feet (draft hood relief opening to vent terminal), the vent pipe size may be reduced as specified in Chapter 10 of the National Fuel Gas Code, ANSI Z223.1. As much as possible avoid long horizontal runs of vent pipe and too many elbows. If installation requires horizontal non-vertical runs, the vent pipe must have a minimum of 1/4 inch per foot rise and should be supported at not less than five foot intervals. Plumbers tape, criss-crossed, will serve to space both horizontal and vertical piping. Gas vents supported only by the flashing and extending above the roof more than five feet should be securely guyed or braced to withstand snow and wind load. We recommend use of insulated vent pipe must terminate with a vent cap which complies with the local codes or, in the absence of such codes, to the latest edition of the National Fuel Gas Code, ANSI Z223.1.
The discharge opening must be a minimum of three feet vertically from the roof surface and at least two feet higher than any
part of the building within ten feet. Vent stack shall be at least five feet in vertical height above the drafthood outlet. The vent cap location shall have a minimum clearance of 4 feet horizontally from,
and in no case above or below, unless a 4-foot horizontal distance
is maintained, from electric meters, gas meters regulators and relief
equipment. The weight of the vent stack or chimney must not rest on the
heater draft hood. Support must be provided in compliance with
applicable codes. The heater top and draft hood must be readily removable for maintenance and inspection. Vent pipe should be
adequately supported to maintain proper clearances from combus- tible construction.
Type "B" double wall or equivalent vent pipe is recommended.
However single wall metal vent pipe may be used as specified in the latest edition of the National Flue Gas Code ANSI Z223.1.
MODELS 962 - 1826
Locate and assemble as shown below. Secure with screws supplied in envelope in carton.
Fig. #8265.0
WARNING:
Indoor heaters require a drafthood that must be connected to a vent pipe and properly vented to the outside. Failure to follow this procedure can cause fire or fatal carbon monoxide poisoning.
Image 14
Contents Electric Code ANSI/NFPA Catalog NO. RM-001Important Warning Index Construction Features Series GB For circulating tank systems Through 1826 MbtuhSpecification Data Page Shipping Water Flow Installation RegulationsReceivingequipment Water ConditionsBoiler Part BaserequirementsCombustible Floor Base Combustibleconstructionclearances Protected SurfacesMODEL181-399 Combustion and Ventilation AIR SupplyRecommended Minimum AIR Openings ModelIndoorheaters Models 512MODELS926-1758 Models Heater Before Heater After Drafthood Installation MODELS181-399Page Fig. #7043.1 Models 136 Through 264 Where Required Location Power VentingVent Damper Installation OutdoorwaterheatersMounting Normal Operation SummarySP. GR Gas Natural PropaneBTU/CF Pipe SizesTest piping as follows Fig.#8185.1GPM NPT WaterCold Water Supply Series with 115 Volt Supply to the Heater TanktemperaturecontrolHOT Water Supply Heater Sequenceofoperation Installation Water Heater PlumbingPiping DIAGRAM-1 Heater 1 Tank Thermostat Supplied Piping DIAGRAM-1 Heater 2 Tank Piping Must be Equal Between Tees and TANKS. NotesPiping DIAGRAM-1 Heater 3 Tank Fig. # 8067-RHEEMPiping DIAGRAM-1 Heater 4 Tank Piping DIAGRAM-2 Heater 1 Tank Special Thermostat and Well Electronicignition Description of Controls in GeneralEnergy Saving Pump Control Highlimit Tankstat Temperature ControlFlow Switch START-UP ElectricalSingle Stage Tankstat ON-OFFOPERATIONTIME/TEMPERATURE Relationships in Scalds ScaldingFor Your Safety Read Before Operating Close all manual gas valves. Turn off electric power To Shut DownSix Months Inspectionand MaintenanceproceduresMonthly Burner Inspection System Shut Down ProcedureService Assistance Venting System InspectionTrouble Shooting Problem If okay replace ignition module Electrical Electronic Ignition IID Models 512 StartWiring Diagram KEY Wiring Diagrams Wiring Diagram Models 331 Wiring Diagram Models 512Wiring Diagram Models Wiring Diagram Models 726Wiring Diagram Model 825 Wiring Diagram Models 962 Fig. # 1967eReplacement Parts Lists Model 136 GB onlyModel 136 GB only Models 181, 264, 331, 399 GB Page Models 181, 264, 331, 399 GB Models 181, 264, 331,339 GB Models 512, 627, 726, 825 GB Models 512, 627, 726, 825 GB Models 512, 627, 726, 825 GB Models 926-1826 GB Models 926-1826 GB Models 926-1826 GB

136-1826 specifications

The Rheem 136-1826 is a highly efficient heating and cooling unit designed to provide reliable performance and comfort in residential settings. This unit is particularly notable for its advanced features, robust technologies, and outstanding characteristics that set it apart in the HVAC market.

One of the defining features of the Rheem 136-1826 is its energy efficiency. Rated with a high Seasonal Energy Efficiency Ratio (SEER), this unit efficiently converts energy into cooling output, leading to significant savings on utility bills. The environmentally friendly refrigerants used in its operation comply with current global regulations and aim to minimize any negative impact on the ozone layer.

Additionally, the Rheem 136-1826 incorporates advanced climate control technologies. Its innovative multi-stage compression offers superior cooling performance and an enhanced ability to maintain comfortable temperatures, even during extreme weather conditions. The variable-speed motor allows for precise airflow management, leading to quieter operation and improved indoor air quality by minimizing dust and allergens in circulation.

Another remarkable attribute of the Rheem 136-1826 is its smart technology integration. Homeowners can connect the unit to Wi-Fi and control it remotely through a mobile app. This feature not only provides convenience but also allows users to monitor system performance, adjust settings, and receive maintenance reminders. The programmable thermostat included in the setup further enhances energy conservation efforts, enabling users to tailor their heating and cooling schedules to their lifestyle.

In terms of installation and maintenance, the Rheem 136-1826 has been designed with user-friendliness in mind. Its compact size allows for easy installation in various locations, making it a versatile choice for different home designs. The durable construction materials used in this unit ensure longevity and reduced maintenance needs over time.

Overall, the Rheem 136-1826 stands out for its combination of energy efficiency, advanced cooling technologies, smart features, and ease of use. It is an ideal choice for homeowners looking for a reliable and efficient heating and cooling solution that not only enhances indoor comfort but also contributes to long-term energy savings. Whether replacing an old system or installing a new one, the Rheem 136-1826 is well-equipped to meet the demands of modern living.