Desa PROPANE GAS LOG HEATER installation manual Minimum Non Combustible Material Clearances

Page 10

INSTALLING

Continued

10

NOTICE

You may use this heater as a vented product. If so, you must always run heater with chimney flue damper open. If running heater with damper open, non-combustible material above fireplace open- ing is not needed. Go to Installing Damper Clamp Accessory for Vented Operation, page 13.

Minimum Non Combustible Material Clearances

If Not Using Mantel

Note: If using a mantel, go to page 11. If not using a mantel, follow the information on this page.

You must have non combustible material(s) above the fireplace opening. Non combustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have non combustible material behind it. Non combustible material must extend at least 8" up. If non combustible material is less than 12", you must install the fireplace hood accessory. See chart below and Figure 5 for minimum clearances.

IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 13.

Non-Combustible

Requirements for

Material Distance (A)

Safe Installation

 

 

12" or more

Non combustible material OK.

Between 8" and 12"

Istall fireplace hood acessory (GA6050

 

or GA6052, see Accessories, page 31).

Less than 8"

Non combustible material must be

 

extended to at least 8". See Between 8"

 

and 12", above. If you cannot extend

 

material, you must operate heater with

 

flue damper open.

 

 

Heat Resistant

Material

(A)

Figure 5 - Heat Resistant Material (Slate, Marble, Tile, etc.) Above Fireplace

102318

Image 10
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASContents Safety Information 001 Operation Local Codes Unpacking Product FeaturesSafety Device Piezo Ignition SystemUnusually Tight Construction AIR for Combustion and VentilationProviding Adequate Ventilation Unconfined SpaceDetermining AIR Flow for Heater Location Determining if You Have a Confined or Unconfined SpaceVentilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Check GAS Type InstallingHigh traffic areas Windy or drafty areas LOG Sizing Requirements Minimum Fireplace Clearance To Combustible MaterialsMinimum Wall and Ceiling Clearances see Figure Minimum Non Combustible Material Clearances If Using Mantel Floor Clearances Installing Damper Clamp Accessory for Vented Operation Attaching Damper ClampInstalling Heater Base Assembly Installation Items NeededConnecting to GAS Supply Attaching Mounting Brackets to HeaterExternal Regulator With Vent Pointing Down Pressure Testing gas Supply Piping system Checking GAS ConnectionsPressure Testing Heater Gas Connections Test Pressures Equal To or Less Than 1/2 PsigInstalling Logs Notch Front Log #1R Grate Prongs Metal Grate BarInstalling Rear Log #3 Installing Crossover Log #5 Operating Heater Operating Heater To Turn OFF GAS to AppliancePilot Flame Pattern Inspecting BurnersFront Burner Flame Pattern ODS/PILOT and Burners Cleaning and Maintenance Trouble ShootingTurn off heater and let cool before cleaning LogsCleaning and Mainte TROUBLE- ShootingRefer to Air for Com Trouble Shooting Statement at topTechnical Service Service HintsParts Under Warranty Replacement PartsParts Not Under Warranty Hood GA6050 AccessoriesValve GA5010 Hood GA6052Illustrated Parts Breakdown Parts List KEY Part Number Description QTY102318 102318 Warranty Information Keep this Warranty