TROUBLE- SHOOTING
Continued
OBSERVED | POSSIBLE |
|
|
|
|
| |
PROBLEM | CAUSE | REMEDY |
| ||||
|
|
|
|
|
|
| |
One or both burners | 1. | Burner orifice(s) | 1. | Clean burner(s) (see |
| ||
do not light after |
| clogged |
| Cleaning and Mainte- |
| ||
ODS/pilot is lit |
|
|
| nance, page 25) or |
| ||
|
|
|
| replace burner orifice(s) |
| ||
| 2. | Inlet gas pressure is | 2. | Contact local propane |
| ||
|
| too low |
| gas company |
| ||
| 3. | Mislocated crossover | 3. | Contact qualified service |
| ||
|
| tube |
| person |
| ||
| 4. | Burner orifice(s) | 4. | Replace burner orifice(s) |
| ||
|
| diameter is too small |
|
|
|
|
|
|
|
|
|
|
|
| |
Delayed ignition of | 1. | Manifold pressure is | 1. | Contact local propane |
| ||
one or both burners |
| too low |
| gas company |
| ||
| 2. | Burner orifice(s) | 2. | Clean burner(s) (see |
| ||
|
| clogged |
| Cleaning and Mainte- |
| ||
|
|
|
| nance, page 25) or |
| ||
|
|
|
| replace burner orifice(s) |
| ||
| 3. | Mislocated crossover | 3. | Contact qualified service |
| ||
|
| tube |
| person |
| ||
|
|
|
|
|
|
| |
Burner backfiring | 1. | Burner orifice is | 1. | Clean burner (see |
| ||
during combustion |
| clogged or damaged |
| Cleaning and Mainte- |
| ||
|
|
|
| nance, page 25) or |
| ||
|
|
|
| replace burner orifice |
| ||
| 2. | Damaged burner | 2. | Replace damaged burner |
| ||
| 3. | Gas regulator defective | 3. | Replace gas regulator |
| ||
|
|
|
|
|
|
| |
Yellow flame in front | 1. | Not enough air | 1. | Check burner(s) for dirt |
| ||
burner during burner |
|
|
| and debris. If found, |
| ||
combustion |
|
|
| clean burner(s) (see |
| ||
|
|
|
| Cleaning and Mainte- |
| ||
|
|
|
| nance, page 25) |
| ||
| 2. | Gas regulator defective | 2. | Replace gas regulator |
| ||
|
|
|
|
|
| ||
Slight smoke or odor | 1. Residues from manu- | 1. | Problem will stop after a |
| |||
during initial opera- |
| facturing processes |
| few hours of operation |
| ||
tion |
| and logs curing |
|
|
|
|
|
|
|
|
|
|
| ||
Moisture/condensation | 1. Not enough combus- | 1. | Refer to Air for Com- |
| |||
noticed on windows |
| tion/ventilation air |
| bustion and Ventilation |
| ||
|
|
|
| requirements (page 5) |
| ||
|
|
|
|
|
| ||
Heater produces a | 1. Turning control knob | 1. | Turn control knob to LO |
| |||
whistling noise when |
| to HI position when |
| position and let warm up |
| ||
burners are lit |
| burners are cold |
| for a minute |
| ||
| 2. | Air in gas line | 2. | Operate burners until air |
| ||
|
|
|
| is removed from line. |
| ||
|
|
|
| Have gas line checked |
| ||
|
|
|
| by local propane gas |
| ||
|
|
|
| company |
| ||
| 3. | Air passageways on | 3. | Observe minimum |
| ||
|
| heater blocked |
| installation clearances |
| ||
|
|
|
| (see pages |
| ||
| 4. | Dirty or partially | 4. | Clean burners (see |
| ||
|
| clogged burner |
| Cleaning and Maintenance, |
| ||
|
| orifice(s) |
| page 25) or replace |
| ||
|
|
|
| burner orifice(s) |
|
|
|
|
|
|
| 27 |
| ||
|
|
|
| Continued |
| ||
|
|
|
|
|
|
|
|
102318