Bradford-White Corp EF Series warranty Exceptions for Installations

Page 20

Vent terminals must terminate at least 3 feet (0.9 m) above any forced air inlet located within 10 feet (3.1 m). This provision does not apply to:

1.The combustion air intake of a direct vent appliance or the circulating air inlet and flue gas discharge of listed outdoor appliances.

2.The exhaust vent terminal must be installed with at least 12 inches (30 cm) clearance from any air opening into a building.

3.The bottom of the exhaust vent and combustion air intake terminals must be located at least 12 inches (30 cm) above grade and above the anticipated snow level.

4.Must be installed at least 3 feet (0.9 m) from any gas meter, gas valve or other gas regulating equipment.

5.Must be installed in a location where it will not be blocked by snow.

6.The exhaust vent and combustion air intake terminals must be installed so that the centerline distances are at least 18 inches (45.7cm) apart and the exhaust vent terminal elbow extends 6 inches (15.2 cm) past the combustion air intake terminal.

EXCEPTIONS FOR INSTALLATIONS

The vent terminal must not terminate:

1.Directly above a paved sidewalk or paved driveway which is located between two single -family dwellings and serves both dwellings;

2.Less than 7 feet (2.1 m) above a paved sidewalk or a paved driveway located on public property;

3.Within 6 feet (1.8 m) of a mechanical air supply inlet to any building;

4.Above a gas meter/regulator assembly within 3 feet (0.9 m) horizontally of the vertical centerline of the regulator;

5.Within 6 feet (1.8m) of any gas service regulator vent outlet;

6.Less than 1 foot (30.5 cm) above grade level;

7.Within 12 inches (30.5 cm) of a window or door, which can be opened in any building, any non- mechanical air, supply inlet to any building or the combustion air inlet of any other appliance;

8.Underneath a veranda, porch or deck, unless:

The veranda, porch or deck is fully open on a minimum of two sides beneath the floor and

The distance between the top of the vent termination and the underside of the veranda, porch or deck is greater than 1 foot (30.5 cm).

The vent system must terminate so that proper clearances are maintained as cited in local codes or the latest edition of the National Fuel Gas Code, ANSI Z223.1.73.4e and 7.8a, b as follows:

1.Do not terminate the exhaust vent terminal over public area where condensate or vapor can cause nuisance or hazard.

2.For direct vent, the venting system shall terminate at least 1 foot below, 1 foot horizontally from or 1 foot above any door, window, or gravity air inlet into building.

3.For horizontal, the venting system shall terminate 4 foot below, 4 foot horizontally from or 1 foot above any door, window, or gravity air inlet into building.

4.The manufacturer also recommends the vent system terminations not be installed closer than 3 feet from an inside corner of an L shaped structure.

5.he vent termination shall not be mounted directly above or within 3 feet horizontally from an oil tank vent or gas meter to avoid potential freeze -up from condensation.

6.The vent shall terminate a minimum of 12 inches above expected snowfall level to prevent blockage of vent termination.

Vent pipes serving power vented appliances are classified by building codes as “vent connectors”. Required clearances from combustible materials must be provided in accordance with information in this manual under LOCATION OF WATER HEATER and CLEARANCES, and with National Fuel Gas Code and local codes.

20

Image 20
Contents With Troubleshooting Guide What to do if YOU Smell GASTable of Contents Page If YOU Smell GAS Do not Operate the Appliance Until the Leakage is CorrectedSpecifications SectionFeatures Section III General InformationTemperature and Pressure Relief Valve Dishwashing Machine Requirements Condensate Elbow With LoopSection IV Installation Instructions Unpacking Minimum Clearance To CombustibleAIR Requ Rements LocationRemove Crate Mechanical Exhausting of Room AIR Unconfined SpaceConfined Space Chemical Vapor CorrosionTypical Installation Illustration Typical Front Inlet ConnectionTypical Two Water Heater Connection Section V Water Connections Instructions for ConnectionsApproximate TIME/TEMPERATURE Relationships in Scalds Scalding Alternate Space Heating Water Connections Alternate Space Heating ConnectionsTypical Plumbing Schematic for Zoned Heating Section VI VentingDirect Vent Installation VentingExceptions for Installations Page Typical Horizontal Direct Vent System Typical Vertical Direct Vent System Installation Power Vent Installation Direct Vent Maximum Vent LengthTypical Horizontal Power Vent System Typical Vertical Power Vent System Installation Power Vent Maximum Vent Length Coaxial Venting Installation ProcedureDimensional Layout of Concentric Vent Kit Concentric Vent Roof Top Attachment Vent Pipe Preparation Initial PreparationSection VII GAS Connections Selection of MaterialsGAS Meter Size Natural Gases only GAS Pressure RegulationWiring Diagram and Schematic Section Viii Electrical ConnectionsSection IX Operating Instructions General InstructionsTo Fill the Water Heater Sequence of OperationTemperature Adjustm NT Lighting InstructionsBurner Flame Check Sight Glass LocationGeneral Section X MaintenanceMaintenance Schedule Flushing Water Heater Draining Water HeaterFilling Water Heater Sediment and Lime Scale RemovalRelief Valve Anode Inspection and ReplacementDrain Valve and Tank Access Panel Vent and AIR Intake System Combustion System InspectionSection XI Troubleshooting Guide ReferenceIs there continuity across the Hot Surface Ignitor? If Section XI Parts List EF Series Water HeaterCombustion Surround Assy CC Ignition Control Assy